Rosemount 848L

Counter Functions

CTU (clock, reset, target)- The parameters clock and reset are functions. The target is a 16 bit constant. Whenever reset is true, the internal counter is set to zero and the value of the function is false. The value of clock is ignored while reset is true. If reset is false, the internal counter will increment once for each rise of the clock parameter. When the internal counter equals the target value, the value of the function is true and the counter stops counting in order to avoid rollover. The value of the function is false if the internal counter does not equal the target.

The internal counter is not visible from Fieldbus and is not available to any other function. The value of the internal counter is not retained during a device restart. This function is not suitable for a totalizer, but can be used as a prescaler to adjust the external mechanical counter rate. The pulse rate must be less than five per second.

The following expression increments the counter whenever hardware input 1 turns on. The counter is reset whenever hardware input 2 is on. If input one is from a mechanical displacement flowmeter that delivers 76.54 pulses per gallon, then the highest flow rate is 3.5 gallons per minute. The following equation will deliver one 0.1 second pulse per 100 gallons:

OUT1_EQ contains CTU(IN(1),OUT(1),7654);

Starting at zero, 7653 pulses go by and then pulse 7654 turns on the output. On the next evaluation cycle, the counter is reset because Output 1 is on. This is a result of the order of execution of equations. Output 1 becomes true because the count is reached, but the OUT(1) function has already been evaluated as false. The counter must reset before the next pulse comes in. The output pulse may be extended with a TP function.

TON (power, target) - Whenever power is false, the value of the internal timer is set to zero and the value of the function is false. When power is true then the value of the function will become true after the target amount f time has elapsed. This condition persists as long as power is true. The timer resets when power is false.

The following equation filters the level switch in a stirred tank so that high level bouncing of the float does not create nuisance alarms for the operator. Hardware input 1 senses the level switch and hardware output 1 drives the alarm annunciator with its big horn. The level switch must stay closed for 5 minutes before the alarm is energized and the operator is startled by the horn.

OUT1_EQ contains: TON(IN(1),3000);

TOF (power, target) - Whenever power is true, the value of the internal timer is set to the target and the value of the function is true. The value of the function will become false after the target amount of time has elapsed. This condition persists as long as power is false.

The following equation keeps the outlet valve open for about 5 seconds after the pump is shut off, so that the pressure across the pump can equalize. Hardware output 1 runs the pump and hardware output 2 opens the valve

OUT1_EQ contains: <something that controls the pump>;

OUT2_EQ contains: TOF(OUT(1),50);

3-17

Image 37
Contents 00809-0100-4696,Rev AA September Reference ManualTemperature Transmitter with Rosemount 848L Discrete LogicRosemount 848L FOUNDATION FieldbusSECTION 1 Introduction SECTION 2 Installation Table of ContentsSECTION 3 Configuration Rosemount 848LReference Data APPENDIX B Product Certifications SECTION Operation and Maintenance APPENDIX AAPPENDIX C Function Blocks Rosemount 848LMotor Control APPENDIX D Logic Equation Syntax APPENDIX EAPPENDIX F Valve Control Rosemount 848LReference Manual Rosemount 848LTOC-4 Section SAFETY MESSAGES WarningsIntroduction Rosemount 848LTransmitter OVERVIEWManual Rosemount 848LReference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848LSAFETY MESSAGES Warnings MOUNTING InstallationSection Rosemount 848LMounting to a Panel with a Junction Box Mounting to a DIN Rail Without an EnclosureRosemount 848L Reference ManualRosemount 848L Mounting to a 2-InchPipe StandReference Manual 00809-0100-4696,Rev AA SeptemberPower Supply Connections WIRINGRosemount 848L Reference ManualSurges/Transients SWITCHESGROUNDING Rosemount 848LReference Manual Rosemount 848L00809-0100-4696,Rev AA September DISCRETE INPUT WIRING CONFIGURATION I/O WIRINGDISCRETE OUTPUT WIRING CONFIGURATION Rosemount 848LRosemount 848L TAGGINGReference Manual TRANSMITTER LABEL INSTALLATION Using Cable GlandsRosemount 848L Reference ManualRosemount 848L Using Conduit EntriesReference Manual OVERVIEW SAFETY MESSAGES Warnings ConfigurationSection Rosemount 848LRosemount 848L GENERAL BLOCK INFORMATION ModesReference Manual Rosemount 848L Link Active Scheduler Block InstantiationReference Manual Capabilities RESOURCE BLOCK FEATURES and FEATURES SELRosemount 848L Reference ManualRosemount 848L MAX NOTIFYReference Manual Rosemount 848L PlantWeb AlarmsReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L Alarms I/O TRANSDUCER BLOCKReference Manual Rosemount 848L LOGIC TRANSDUCER BLOCKReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Figure 3-1.848L Logic Transmitter Data FlowReference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L DISCRETE INPUT BLOCKSReference Manual MULTIPLE DISCRETE INPUT BLOCK DISCRETE OUTPUT BLOCKSMULTIPLE DISCRETE OUTPUT BLOCK Rosemount 848LReference Manual Rosemount 848LFOUNDATION FIELDBUS INFORMATION Section 4 Operation and MaintenanceSAFETY MESSAGES Warnings Rosemount 848LCommunication/Power MAINTENANCEResetting the Configuration RESTART CommissioningI/O Transducer and Logic Block Troubleshooting TROUBLESHOOTINGResource Block NAMUR SensorsReference Manual Rosemount 848LAppendix A SPECIFICATIONS Functional SpecificationsReference Data Rosemount 848LReference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Specification Physical Specifications Function BlocksRosemount 848L Reference ManualRosemount 848L DIMENSIONAL DRAWINGSReference Manual Rosemount 848L Figure A-3.Rosemount 848L Wiring DiagramReference Manual 00809-0100-4696,Rev AA SeptemberRosemount 848L ORDERING INFORMATIONReference Manual Reference Manual Rosemount 848LAPPROVED MANUFACTURING LOCATIONS Appendix B Product CertificationsEUROPEAN DIRECTIVE INFORMATION HAZARDOUS LOCATIONS CERTIFICATES North American ApprovalsRosemount 848L European ApprovalsReference Manual RESOURCE BLOCK PARAMETERS Appendix C Function BlocksRosemount 848L Reference ManualReference Manual Rosemount 848LFREE SPACE Reference Manual Rosemount 848LOUTPUT Rosemount 848L ADVISE ENABLEReference Manual Rosemount 848L I/O TRANSDUCER PARAMETERSReference Manual 00809-0100-4696,Rev AA SeptemberReference Manual Rosemount 848LTRANSDUCER TYPE Reference Manual Rosemount 848LOUT 3 TAG Rosemount 848L LOGIC TRANSDUCER PARAMETERSReference Manual 00809-0100-4696,Rev AA SeptemberRosemount 848L DISCRETE INPUT BLOCKReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Table C-4.ParametersRosemount 848L DISCRETE OUTPUT BLOCK Supported ModesReference Manual Rosemount 848L MULTIPLE DISCRETE INPUT BLOCKSReference Manual Reference Manual Rosemount 848LMULTIPLE DISCRETE OUTPUT BLOCK 00809-0100-4696,Rev AA SeptemberReference Manual Rosemount 848L00809-0100-4696,Rev AA September Table C-7.Parameters andRosemount 848L Appendix D Logic Equation SyntaxReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Table D-1.Supported FunctionsReference Manual Rosemount 848LPS channel number, divisor Table D-2.Error Handling ERROR HANDLINGRosemount 848L Reference ManualRosemount 848L EXAMPLESReference Manual Reference Manual Rosemount 848LMotor Control Appendix EINTRODUCTION TO MOTOR CONTROL Rosemount 848LRosemount 848L VARIATIONS ON MOTOR CONTROLReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L WRITING 848L EQUATIONS Basic Motor ControlReference Manual Rosemount 848L Interlock Permissive Emergency ShutdownReference Manual Rosemount 848L Restart DelayReference Manual Rosemount 848L Maximum RestartsReference Manual Rosemount 848L Winding TemperatureReference Manual Rosemount 848L Hand-Off-AutoReference Manual Rosemount 848L Intermediate StopReference Manual Rosemount 848L Redundant Motors - Alternate StartReference Manual Rosemount 848L Redundant Motors - Timed SwitchReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L Redundant Motors - Switch on FailureReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848LE-16 Valve Control Appendix FINTRODUCTION TO VALVE CONTROL Rosemount 848LRosemount 848L Alarms Variations on Valve ControlReference Manual Rosemount 848L Boolean Expressions Basic Valve ControlReference Manual Output Variations Output with Interlock Open-Auto-Close Alarm VariationsRosemount 848L Reference ManualRosemount 848L Simple Valve Variations PermissiveReference Manual Rosemount 848L Double Block and BleedReference Manual Rosemount 848L Motorized Valve Heat Exchange Medium SelectionReference Manual Reference Manual Rosemount 848LRosemount 848L IndexReference Manual 00809-0100-4696,Rev AA 9/17/04Reference Manual Rosemount 848L00809-0100-4696,Rev AA 9/17/04 Reference Manual Rosemount 848L00809-0100-4696,Rev AA 9/17/04 Reference Manual Rosemount 848LIndex-4 Reference Manual ¢00809-0100-4697F¤