Reference Manual
Rosemount 848L
I/O TRANSDUCER
PARAMETERS
Table C-2. I/O Transducer Parameters
Numbe |
|
|
r | Parameter | Description |
|
|
|
1 | ST_ REV | The revision level of the static data associated with the function block. |
|
|
|
2 | TAG_ DESC | The user description of the intended application of the block. |
3 | STRATEGY | The strategy field can be used to identify grouping of blocks. |
|
|
|
4 | ALERT_ KEY | The identification number of the plant unit. |
5 | MODE_ BLK | The actual, target, permitted, and normal modes of the block. For further description, see the Mode |
|
| parameter formal model in |
|
|
|
6 | BLOCK_ ERR | This parameter reflects the error status associated with the hardware or software components |
|
| associated with a block. Multiple errors may be shown. For a list of enumeration values, see |
|
| Block_ Err formal model. |
7 | UPDATE_ EVT | This alert is generated by any change to the static data. |
|
|
|
8 | BLOCK_ ALM | The block alarm is used for all configuration, hardware, connection failure, or system problems in the |
|
| block. The cause of the alert is entered in the subcode field. The first alert to become active will set the |
|
| Active status in the Status attribute. As soon as the Unreported status is cleared by the alert reporting |
|
| task, another block alert may be reported without clearing the Active status, if the subcode has |
|
| changed. |
9 | TRANSDUCER_ | A directory that specifies the number and starting indices of the transducers in the transducer block. For |
| DIRECTORY | further information, please refer to the Transducer Block Application Process - Part 1 |
|
| specification. |
|
|
|
10 | TRANSDUCER_ TYPE | Identifies the transducer that follows. |
11 | XD_ ERROR | One of the error codes defined in |
|
|
|
12 | COLLECTION_ | A directory that specifies the number, starting indices, and DD item IDs of the data collections in each |
| DIRECTORY | transducer within a transducer block. For further information, please refer |
13 | IN_ 1_ TAG | An identifier associated with discrete input 1. |
|
|
|
14 | IN1 | The value and status of discrete input 1. |
15 | PULSE_ COUNT_ 1 | The number of pulses that have occurred on IN1 since last reset. |
|
|
|
16 | IN_ 1_ CONFIG.IO_TYPE | The transducer type of discrete sensor 1. |
16 | IN_ 1_ CONFIG.FILTER | Any state change on IN1 that lasts for a duration less than this filter value, will be ignored by the device. |
|
|
|
16 | IN_ 1_ CONFIG.FAIL_ | When the device detects a failure, IO1 will have its value set to this value. |
| SAFE |
|
17 | IN_ 2_ TAG | An identifier associated with discrete input 2. |
|
|
|
18 | IN2 | The value and status of discrete input 2. |
19 | PULSE_ COUNT_ 2 | The number of pulses that have occurred on IN2 since last reset. |
|
|
|
20 | IN_ 2_ CONFIG.IO_TYPE | The transducer type of discrete sensor 2. |
20 | IN_ 2_ CONFIG.FILTER | Any state change on IN2 that lasts for a duration less than this filter value, will be ignored by the device. |
|
|
|
20 | IN_ 2_ CONFIG.FAIL_ | When the device detects a failure, IO2 will have its value set to this value. |
| SAFE |
|
21 | IN_ 3_ TAG | An identifier associated with discrete input 3. |
|
|
|
22 | IN3 | The value and status of discrete input 3. |
23 | PULSE_ COUNT_ 3 | The number of pulses that have occurred on IN3 since last reset. |
|
|
|
24 | IN_ 3_ CONFIG.IO_TYPE | The transducer type of discrete sensor 3. |
24 | IN_ 3_ CONFIG.FILTER | Any state change on IN3 that lasts for a duration less than this filter value, will be ignored by the device. |
|
|
|
24 | IN_ 3_ CONFIG.FAIL_ | When the device detects a failure, IO3 will have its value set to this value. |
| SAFE |
|
25 | IN_ 4_ TAG | An identifier associated with discrete input 4. |
|
|
|
26 | IN4 | The value and status of discrete input 4. |
27 | PULSE_ COUNT_ 4 | The number of pulses that have occurred on IN4 since last reset. |
|
|
|
28 | IN_ 4_ CONFIG.IO_TYPE | The transducer type of discrete sensor 4. |
28 | IN_ 4_ CONFIG.FILTER | Any state change on IN4 that lasts for a duration less than this filter value, will be ignored by the device. |
|
|
|
28 | IN_ 4_ CONFIG.FAIL_ | When the device detects a failure, IO4 will have its value set to this value. |
| SAFE |
|
|
|
|