Emerson manual Alarms Variations on Valve Control, Rosemount 848L, Reference Manual

Page 94
Alarms

Rosemount 848L

Reference Manual

00809-0100-4696, Rev AA September 2004

Alarms

Variations on Valve Control

There are at least three permutations of any valve circuit:

1.Steady or pulse output to the pilot solenoid (or whatever, piezoelectric bars are in use). Steady requires one output, pulse requires two.

2.Confirmed position switches for open, closed or both, using one or two inputs.

3.Automatic control or a local selector for Open-Auto-Close using no or two inputs (these are not common).

Interlock and permissive may be additional permutations.

If a valve has one or both position switches then it is possible to alert the operator to the fact that the valve is not where it should be. This is not a permuted choice because the main reason for having position switches is to alarm this condition. It is not a simple alarm because time must be allowed for the valve to complete its stroke after it receives a command. An On Delay timer set for the travel time is required.

All numbers in 848L equations are examples. The user will want to change them.

Interlock

There may be a process condition where it is not safe to open the valve. If this condition can be detected and transformed into the change of state of a contact, then the normally closed contact may be inserted in series with the control output. If the interlocked condition occurs then the valve will close if open or stay closed. An example is the drain valve of a batch reactor, which may have two interlocks. One prevents opening the drain if any feed valve is open. The other will not let material in the reactor drain into a tank that isn’t ready for it.

Permissive

There may be a process condition that is required to be present when a valve is opened, but is not required once it has been opened. A contact that is closed when the permissive condition is true is placed in series with the open command. A latch is required because the permissive may go false after the valve is opened. One application for a permissive involves a gas storage tank. The pressure must be above a certain amount to allow the valve to be opened, but once opened, the pressure will fall below the permissive level.

Open-Auto-Close

An operator may be required to perform some function near the valve, such as unplugging a pipe or locally directing material flow. The valve is normally controlled by the central system but must have a local station to allow the local operator to control it. The local station has a three position switch for Open-Auto-Close selection. The control room has control when the switch is in the Auto position. If the switch is turned to Open then the valve will open, possibly bypassing interlocks, and the same for Close. There is no bump going through Auto because the command is either Open or Close.

F-2

Image 94
Contents Reference Manual 00809-0100-4696,Rev AA SeptemberRosemount 848L Rosemount 848L Discrete LogicTemperature Transmitter with FOUNDATION FieldbusSECTION 3 Configuration Table of ContentsSECTION 1 Introduction SECTION 2 Installation Rosemount 848LAPPENDIX C Function Blocks SECTION Operation and Maintenance APPENDIX AReference Data APPENDIX B Product Certifications Rosemount 848LAPPENDIX F Valve Control APPENDIX D Logic Equation Syntax APPENDIX EMotor Control Rosemount 848LReference Manual Rosemount 848LTOC-4 Introduction SAFETY MESSAGES WarningsSection Rosemount 848LManual OVERVIEWTransmitter Rosemount 848LReference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L Reference ManualSection InstallationSAFETY MESSAGES Warnings MOUNTING Rosemount 848LRosemount 848L Mounting to a DIN Rail Without an EnclosureMounting to a Panel with a Junction Box Reference ManualReference Manual Mounting to a 2-InchPipe StandRosemount 848L 00809-0100-4696,Rev AA SeptemberRosemount 848L WIRINGPower Supply Connections Reference ManualGROUNDING SWITCHESSurges/Transients Rosemount 848LReference Manual Rosemount 848L00809-0100-4696,Rev AA September DISCRETE OUTPUT WIRING CONFIGURATION I/O WIRINGDISCRETE INPUT WIRING CONFIGURATION Rosemount 848LRosemount 848L TAGGINGReference Manual Rosemount 848L INSTALLATION Using Cable GlandsTRANSMITTER LABEL Reference ManualRosemount 848L Using Conduit EntriesReference Manual Section ConfigurationOVERVIEW SAFETY MESSAGES Warnings Rosemount 848LRosemount 848L GENERAL BLOCK INFORMATION ModesReference Manual Rosemount 848L Link Active Scheduler Block InstantiationReference Manual Rosemount 848L RESOURCE BLOCK FEATURES and FEATURES SELCapabilities Reference ManualRosemount 848L MAX NOTIFYReference Manual Rosemount 848L PlantWeb AlarmsReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L Alarms I/O TRANSDUCER BLOCKReference Manual Rosemount 848L LOGIC TRANSDUCER BLOCKReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual Figure 3-1.848L Logic Transmitter Data FlowReference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L DISCRETE INPUT BLOCKSReference Manual MULTIPLE DISCRETE OUTPUT BLOCK DISCRETE OUTPUT BLOCKSMULTIPLE DISCRETE INPUT BLOCK Rosemount 848LRosemount 848L Reference ManualSAFETY MESSAGES Warnings Section 4 Operation and MaintenanceFOUNDATION FIELDBUS INFORMATION Rosemount 848LResetting the Configuration RESTART MAINTENANCECommunication/Power CommissioningResource Block TROUBLESHOOTINGI/O Transducer and Logic Block Troubleshooting NAMUR SensorsRosemount 848L Reference ManualReference Data SPECIFICATIONS Functional SpecificationsAppendix A Rosemount 848LReference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L Physical Specifications Function BlocksSpecification Reference ManualRosemount 848L DIMENSIONAL DRAWINGSReference Manual Reference Manual Figure A-3.Rosemount 848L Wiring DiagramRosemount 848L 00809-0100-4696,Rev AA SeptemberRosemount 848L ORDERING INFORMATIONReference Manual Rosemount 848L Reference ManualEUROPEAN DIRECTIVE INFORMATION HAZARDOUS Appendix B Product CertificationsAPPROVED MANUFACTURING LOCATIONS LOCATIONS CERTIFICATES North American ApprovalsRosemount 848L European ApprovalsReference Manual Rosemount 848L Appendix C Function BlocksRESOURCE BLOCK PARAMETERS Reference ManualReference Manual Rosemount 848LFREE SPACE Reference Manual Rosemount 848LOUTPUT Rosemount 848L ADVISE ENABLEReference Manual Reference Manual I/O TRANSDUCER PARAMETERSRosemount 848L 00809-0100-4696,Rev AA SeptemberReference Manual Rosemount 848LTRANSDUCER TYPE Reference Manual Rosemount 848LOUT 3 TAG Reference Manual LOGIC TRANSDUCER PARAMETERSRosemount 848L 00809-0100-4696,Rev AA SeptemberRosemount 848L DISCRETE INPUT BLOCKReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual Table C-4.ParametersRosemount 848L DISCRETE OUTPUT BLOCK Supported ModesReference Manual Rosemount 848L MULTIPLE DISCRETE INPUT BLOCKSReference Manual MULTIPLE DISCRETE OUTPUT BLOCK Rosemount 848LReference Manual 00809-0100-4696,Rev AA September00809-0100-4696,Rev AA September Rosemount 848LReference Manual Table C-7.Parameters andRosemount 848L Appendix D Logic Equation SyntaxReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual Table D-1.Supported FunctionsReference Manual Rosemount 848LPS channel number, divisor Rosemount 848L ERROR HANDLINGTable D-2.Error Handling Reference ManualRosemount 848L EXAMPLESReference Manual Rosemount 848L Reference ManualINTRODUCTION TO MOTOR CONTROL Appendix EMotor Control Rosemount 848LRosemount 848L VARIATIONS ON MOTOR CONTROLReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L WRITING 848L EQUATIONS Basic Motor ControlReference Manual Rosemount 848L Interlock Permissive Emergency ShutdownReference Manual Rosemount 848L Restart DelayReference Manual Rosemount 848L Maximum RestartsReference Manual Rosemount 848L Winding TemperatureReference Manual Rosemount 848L Hand-Off-AutoReference Manual Rosemount 848L Intermediate StopReference Manual Rosemount 848L Redundant Motors - Alternate StartReference Manual Rosemount 848L Redundant Motors - Timed SwitchReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L Redundant Motors - Switch on FailureReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848LE-16 INTRODUCTION TO VALVE CONTROL Appendix FValve Control Rosemount 848LRosemount 848L Alarms Variations on Valve ControlReference Manual Rosemount 848L Boolean Expressions Basic Valve ControlReference Manual Rosemount 848L Open-Auto-Close Alarm VariationsOutput Variations Output with Interlock Reference ManualRosemount 848L Simple Valve Variations PermissiveReference Manual Rosemount 848L Double Block and BleedReference Manual Rosemount 848L Motorized Valve Heat Exchange Medium SelectionReference Manual Rosemount 848L Reference ManualReference Manual IndexRosemount 848L 00809-0100-4696,Rev AA 9/17/04Reference Manual Rosemount 848L00809-0100-4696,Rev AA 9/17/04 Reference Manual Rosemount 848L00809-0100-4696,Rev AA 9/17/04 Reference Manual Rosemount 848LIndex-4 ¢00809-0100-4697F¤ Reference Manual