Emerson manual Variations On Motor Control, Rosemount 848L, Reference Manual

Page 78
VARIATIONS ON MOTOR CONTROL

Rosemount 848L

Reference Manual

00809-0100-4696, Rev AA September 2004

VARIATIONS ON MOTOR CONTROL

The contactor is never controlled with a toggle switch, because that would leave one side of the solenoid electrically hot when the motor overload trips. Standard procedure calls for start and stop push buttons in combination with an auxiliary contact on the contactor. This contact closes when the solenoid is energized and the motor contacts close. The auxiliary contact is rated for the control voltage and current, and is far away from the high voltage motor contacts. The stop button is normally closed and is in series with the control power. The start button is normally open and is also in series with the control power. The auxiliary contact is normally open and in parallel with the start button. When the start button is pushed, the solenoid is powered and the motor and auxiliary contacts eventually close. The start button can be released and control power will continue to flow in the auxiliary contact. Two things can stop the motor. Pressing the stop button removes power to the solenoid, causing the auxiliary contact to eventually open along with the motor power contacts. The stop button can then be released because there is no complete circuit to the solenoid. The same thing happens if an overload trip opens the circuit to the solenoid. When the overload is reset, no power will be applied to the solenoid until the start button is pushed.

___

 

___

 

 

Over

\_/STOP

 

\_/START

 

load

 

 

M

+

--OO-----

+--

O O--

+------------

( )

---OO--

+ Contactor M

 

 

 

 

 

M

 

 

 

+--

--

+

 

 

Interlock

There may be a process condition where it is not safe to run the motor. If this condition can be detected and transformed into the change of state of a contact, then the normally closed contact may be inserted in series with the control voltage. If the interlocked condition occurs then the motor will not run or start. An example is a low level condition in a tank feeding the suction of a pump. The pump will be damaged if the suction goes dry, so a low level switch is put in series with the control voltage for the pump’s motor starter.

Permissive

There may be a process condition that is required to be present when a motor is started, but is not required once the motor is running. A contact that is closed when the permissive condition is true is placed in series with the start button. An example is auxiliary lubrication for a large motor that is required to flood the bearing housings to prevent contact between the motor shaft and the bearing material (not ball bearings). Once the motor is turning, lubrication is maintained by shaft rotation and the auxiliary pump can be shut off.

Emergency Shutdown

A process may have an emergency shutdown requirement for all motors. This requires a contact or logic input for all affected motor controls. For example, there is an emergency stop button for a natural gas processing plant located near the exit, so that the operator can hit it while running away.

E-2

Image 78
Contents Reference Manual 00809-0100-4696,Rev AA SeptemberRosemount 848L Rosemount 848L Discrete LogicTemperature Transmitter with FOUNDATION FieldbusSECTION 3 Configuration Table of ContentsSECTION 1 Introduction SECTION 2 Installation Rosemount 848LAPPENDIX C Function Blocks SECTION Operation and Maintenance APPENDIX AReference Data APPENDIX B Product Certifications Rosemount 848LAPPENDIX F Valve Control APPENDIX D Logic Equation Syntax APPENDIX EMotor Control Rosemount 848LRosemount 848L Reference ManualTOC-4 Introduction SAFETY MESSAGES WarningsSection Rosemount 848LManual OVERVIEWTransmitter Rosemount 848LRosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Reference ManualSection InstallationSAFETY MESSAGES Warnings MOUNTING Rosemount 848LRosemount 848L Mounting to a DIN Rail Without an EnclosureMounting to a Panel with a Junction Box Reference ManualReference Manual Mounting to a 2-InchPipe StandRosemount 848L 00809-0100-4696,Rev AA SeptemberRosemount 848L WIRINGPower Supply Connections Reference ManualGROUNDING SWITCHESSurges/Transients Rosemount 848LRosemount 848L Reference Manual00809-0100-4696,Rev AA September DISCRETE OUTPUT WIRING CONFIGURATION I/O WIRINGDISCRETE INPUT WIRING CONFIGURATION Rosemount 848LTAGGING Rosemount 848LReference Manual Rosemount 848L INSTALLATION Using Cable GlandsTRANSMITTER LABEL Reference ManualUsing Conduit Entries Rosemount 848LReference Manual Section ConfigurationOVERVIEW SAFETY MESSAGES Warnings Rosemount 848LGENERAL BLOCK INFORMATION Modes Rosemount 848LReference Manual Link Active Scheduler Block Instantiation Rosemount 848LReference Manual Rosemount 848L RESOURCE BLOCK FEATURES and FEATURES SELCapabilities Reference ManualMAX NOTIFY Rosemount 848LReference Manual PlantWeb Alarms Rosemount 848LReference Manual Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Alarms I/O TRANSDUCER BLOCK Rosemount 848LReference Manual LOGIC TRANSDUCER BLOCK Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual Figure 3-1.848L Logic Transmitter Data FlowRosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Reference Manual00809-0100-4696,Rev AA September DISCRETE INPUT BLOCKS Rosemount 848LReference Manual MULTIPLE DISCRETE OUTPUT BLOCK DISCRETE OUTPUT BLOCKSMULTIPLE DISCRETE INPUT BLOCK Rosemount 848LRosemount 848L Reference ManualSAFETY MESSAGES Warnings Section 4 Operation and MaintenanceFOUNDATION FIELDBUS INFORMATION Rosemount 848LResetting the Configuration RESTART MAINTENANCECommunication/Power CommissioningResource Block TROUBLESHOOTINGI/O Transducer and Logic Block Troubleshooting NAMUR SensorsRosemount 848L Reference ManualReference Data SPECIFICATIONS Functional SpecificationsAppendix A Rosemount 848LRosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Physical Specifications Function BlocksSpecification Reference ManualDIMENSIONAL DRAWINGS Rosemount 848LReference Manual Reference Manual Figure A-3.Rosemount 848L Wiring DiagramRosemount 848L 00809-0100-4696,Rev AA SeptemberORDERING INFORMATION Rosemount 848LReference Manual Rosemount 848L Reference ManualEUROPEAN DIRECTIVE INFORMATION HAZARDOUS Appendix B Product CertificationsAPPROVED MANUFACTURING LOCATIONS LOCATIONS CERTIFICATES North American ApprovalsEuropean Approvals Rosemount 848LReference Manual Rosemount 848L Appendix C Function BlocksRESOURCE BLOCK PARAMETERS Reference ManualRosemount 848L Reference ManualFREE SPACE Rosemount 848L Reference ManualOUTPUT ADVISE ENABLE Rosemount 848LReference Manual Reference Manual I/O TRANSDUCER PARAMETERSRosemount 848L 00809-0100-4696,Rev AA SeptemberRosemount 848L Reference ManualTRANSDUCER TYPE Rosemount 848L Reference ManualOUT 3 TAG Reference Manual LOGIC TRANSDUCER PARAMETERSRosemount 848L 00809-0100-4696,Rev AA SeptemberDISCRETE INPUT BLOCK Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual Table C-4.ParametersDISCRETE OUTPUT BLOCK Supported Modes Rosemount 848LReference Manual MULTIPLE DISCRETE INPUT BLOCKS Rosemount 848LReference Manual MULTIPLE DISCRETE OUTPUT BLOCK Rosemount 848LReference Manual 00809-0100-4696,Rev AA September00809-0100-4696,Rev AA September Rosemount 848LReference Manual Table C-7.Parameters andAppendix D Logic Equation Syntax Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual Table D-1.Supported FunctionsRosemount 848L Reference ManualPS channel number, divisor Rosemount 848L ERROR HANDLINGTable D-2.Error Handling Reference ManualEXAMPLES Rosemount 848LReference Manual Rosemount 848L Reference ManualINTRODUCTION TO MOTOR CONTROL Appendix EMotor Control Rosemount 848LVARIATIONS ON MOTOR CONTROL Rosemount 848LReference Manual Rosemount 848L Reference Manual00809-0100-4696,Rev AA September WRITING 848L EQUATIONS Basic Motor Control Rosemount 848LReference Manual Interlock Permissive Emergency Shutdown Rosemount 848LReference Manual Restart Delay Rosemount 848LReference Manual Maximum Restarts Rosemount 848LReference Manual Winding Temperature Rosemount 848LReference Manual Hand-Off-Auto Rosemount 848LReference Manual Intermediate Stop Rosemount 848LReference Manual Redundant Motors - Alternate Start Rosemount 848LReference Manual Redundant Motors - Timed Switch Rosemount 848LReference Manual Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Redundant Motors - Switch on Failure Rosemount 848LReference Manual Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Rosemount 848L Reference ManualE-16 INTRODUCTION TO VALVE CONTROL Appendix FValve Control Rosemount 848LAlarms Variations on Valve Control Rosemount 848LReference Manual Boolean Expressions Basic Valve Control Rosemount 848LReference Manual Rosemount 848L Open-Auto-Close Alarm VariationsOutput Variations Output with Interlock Reference ManualSimple Valve Variations Permissive Rosemount 848LReference Manual Double Block and Bleed Rosemount 848LReference Manual Motorized Valve Heat Exchange Medium Selection Rosemount 848LReference Manual Rosemount 848L Reference ManualReference Manual IndexRosemount 848L 00809-0100-4696,Rev AA 9/17/04Rosemount 848L Reference Manual00809-0100-4696,Rev AA 9/17/04 Rosemount 848L Reference Manual00809-0100-4696,Rev AA 9/17/04 Rosemount 848L Reference ManualIndex-4 ¢00809-0100-4697F¤ Reference Manual