Rosemount 848L

Restart Delay

A motor may be used in a condition where starting is difficult, causing the motor to heat rapidly until it gets running. That heat must be allowed to dissipate before the motor is started again. A simple time delay prevents the start button from working until a fixed delay time expires. Another example is the time required for compressor head pressure to bleed off after the compressor motor stops.

Maximum Restarts

Another way of handling difficult starts is to count the number of starts in a given time and lock out the start button if the count is exceeded. Locking it out means that the start button will not function until a latching relay has been manually reset by an operator who has verified the safety of the situation.

Winding temperature

The above restart limiters may not be necessary if the winding temperature can be measured and used as a permissive for starting. The winding temperature sensor may be a ten ohm length of copper wire that is wound into the motor along with the power windings.

Hand-Off-Auto

An operator may be required to perform some function near the motor, such as clean a pump strainer or jog the motor to get its load into the right position. The motor is normally controlled by the central system but must have a local station to allow the local operator to control the motor. The local station has buttons for Stop and Start, and a three position switch for Hand-Off-Auto (HOA) selection. The control room has control when the switch is in the Auto position. The motor will not run when the switch is in the Off position. The Hand position allows the local start and stop buttons to control the motor. The Off position is not as secure as the lockout procedure required when the equipment or the operator would be damaged if the motor started. This requires all concerned people to physically put a padlock on the Off position of the main circuit breaker for the motor. The motor may be started after the last person removes their lock.

Intermediate Stop

A reversible motor may be required to come to a complete stop before starting to run in the other direction. This may be done with a timer or a motion sensor on the motor (or driven load) shaft.

Redundant Motors

The process may require redundant motors for reliability. Usually this applies to pumps, so that there is no mechanical connection between the two motors. One pump may be shut off to replace seals (or the entire pump and motor) while the redundant pump maintains flow in the line. There are three ways to control redundant pumps:

Alternate Start

When the start button is pressed the pump that was not in use is started. Not in use refers to now or since the last time start was pressed.

E-3

Image 79
Contents 00809-0100-4696,Rev AA September Reference ManualFOUNDATION Fieldbus Rosemount 848L Discrete LogicTemperature Transmitter with Rosemount 848LRosemount 848L Table of ContentsSECTION 1 Introduction SECTION 2 Installation SECTION 3 ConfigurationRosemount 848L SECTION Operation and Maintenance APPENDIX AReference Data APPENDIX B Product Certifications APPENDIX C Function BlocksRosemount 848L APPENDIX D Logic Equation Syntax APPENDIX EMotor Control APPENDIX F Valve ControlReference Manual Rosemount 848LTOC-4 Rosemount 848L SAFETY MESSAGES WarningsSection IntroductionRosemount 848L OVERVIEWTransmitter ManualReference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848LRosemount 848L InstallationSAFETY MESSAGES Warnings MOUNTING SectionReference Manual Mounting to a DIN Rail Without an EnclosureMounting to a Panel with a Junction Box Rosemount 848L00809-0100-4696,Rev AA September Mounting to a 2-InchPipe StandRosemount 848L Reference ManualReference Manual WIRINGPower Supply Connections Rosemount 848LRosemount 848L SWITCHESSurges/Transients GROUNDINGReference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L I/O WIRINGDISCRETE INPUT WIRING CONFIGURATION DISCRETE OUTPUT WIRING CONFIGURATIONRosemount 848L TAGGINGReference Manual Reference Manual INSTALLATION Using Cable GlandsTRANSMITTER LABEL Rosemount 848LRosemount 848L Using Conduit EntriesReference Manual Rosemount 848L ConfigurationOVERVIEW SAFETY MESSAGES Warnings SectionRosemount 848L GENERAL BLOCK INFORMATION ModesReference Manual Rosemount 848L Link Active Scheduler Block InstantiationReference Manual Reference Manual RESOURCE BLOCK FEATURES and FEATURES SELCapabilities Rosemount 848LRosemount 848L MAX NOTIFYReference Manual Rosemount 848L PlantWeb AlarmsReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L Alarms I/O TRANSDUCER BLOCKReference Manual Rosemount 848L LOGIC TRANSDUCER BLOCKReference Manual Figure 3-1.848L Logic Transmitter Data Flow Rosemount 848LReference Manual 00809-0100-4696,Rev AA SeptemberReference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L DISCRETE INPUT BLOCKSReference Manual Rosemount 848L DISCRETE OUTPUT BLOCKSMULTIPLE DISCRETE INPUT BLOCK MULTIPLE DISCRETE OUTPUT BLOCKReference Manual Rosemount 848LRosemount 848L Section 4 Operation and MaintenanceFOUNDATION FIELDBUS INFORMATION SAFETY MESSAGES WarningsCommissioning MAINTENANCECommunication/Power Resetting the Configuration RESTARTNAMUR Sensors TROUBLESHOOTINGI/O Transducer and Logic Block Troubleshooting Resource BlockReference Manual Rosemount 848LRosemount 848L SPECIFICATIONS Functional SpecificationsAppendix A Reference DataReference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Physical Specifications Function BlocksSpecification Rosemount 848LRosemount 848L DIMENSIONAL DRAWINGSReference Manual 00809-0100-4696,Rev AA September Figure A-3.Rosemount 848L Wiring DiagramRosemount 848L Reference ManualRosemount 848L ORDERING INFORMATIONReference Manual Reference Manual Rosemount 848LLOCATIONS CERTIFICATES North American Approvals Appendix B Product CertificationsAPPROVED MANUFACTURING LOCATIONS EUROPEAN DIRECTIVE INFORMATION HAZARDOUSRosemount 848L European ApprovalsReference Manual Reference Manual Appendix C Function BlocksRESOURCE BLOCK PARAMETERS Rosemount 848LReference Manual Rosemount 848LFREE SPACE Reference Manual Rosemount 848LOUTPUT Rosemount 848L ADVISE ENABLEReference Manual 00809-0100-4696,Rev AA September I/O TRANSDUCER PARAMETERSRosemount 848L Reference ManualReference Manual Rosemount 848LTRANSDUCER TYPE Reference Manual Rosemount 848LOUT 3 TAG 00809-0100-4696,Rev AA September LOGIC TRANSDUCER PARAMETERSRosemount 848L Reference ManualRosemount 848L DISCRETE INPUT BLOCKReference Manual Table C-4.Parameters Rosemount 848LReference Manual 00809-0100-4696,Rev AA SeptemberRosemount 848L DISCRETE OUTPUT BLOCK Supported ModesReference Manual Rosemount 848L MULTIPLE DISCRETE INPUT BLOCKSReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual MULTIPLE DISCRETE OUTPUT BLOCKTable C-7.Parameters and Rosemount 848LReference Manual 00809-0100-4696,Rev AA SeptemberRosemount 848L Appendix D Logic Equation SyntaxReference Manual Table D-1.Supported Functions Rosemount 848LReference Manual 00809-0100-4696,Rev AA SeptemberReference Manual Rosemount 848LPS channel number, divisor Reference Manual ERROR HANDLINGTable D-2.Error Handling Rosemount 848LRosemount 848L EXAMPLESReference Manual Reference Manual Rosemount 848LRosemount 848L Appendix EMotor Control INTRODUCTION TO MOTOR CONTROLRosemount 848L VARIATIONS ON MOTOR CONTROLReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L WRITING 848L EQUATIONS Basic Motor ControlReference Manual Rosemount 848L Interlock Permissive Emergency ShutdownReference Manual Rosemount 848L Restart DelayReference Manual Rosemount 848L Maximum RestartsReference Manual Rosemount 848L Winding TemperatureReference Manual Rosemount 848L Hand-Off-AutoReference Manual Rosemount 848L Intermediate StopReference Manual Rosemount 848L Redundant Motors - Alternate StartReference Manual Rosemount 848L Redundant Motors - Timed SwitchReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848L Redundant Motors - Switch on FailureReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA September Reference Manual Rosemount 848LE-16 Rosemount 848L Appendix FValve Control INTRODUCTION TO VALVE CONTROLRosemount 848L Alarms Variations on Valve ControlReference Manual Rosemount 848L Boolean Expressions Basic Valve ControlReference Manual Reference Manual Open-Auto-Close Alarm VariationsOutput Variations Output with Interlock Rosemount 848LRosemount 848L Simple Valve Variations PermissiveReference Manual Rosemount 848L Double Block and BleedReference Manual Rosemount 848L Motorized Valve Heat Exchange Medium SelectionReference Manual Reference Manual Rosemount 848L00809-0100-4696,Rev AA 9/17/04 IndexRosemount 848L Reference ManualReference Manual Rosemount 848L00809-0100-4696,Rev AA 9/17/04 Reference Manual Rosemount 848L00809-0100-4696,Rev AA 9/17/04 Reference Manual Rosemount 848LIndex-4 Reference Manual ¢00809-0100-4697F¤