Emerson 848L Commissioning, Addressing, Hardware, Maintenance, Sensor Check, Communication/Power

Page 44
Commissioning

Rosemount 848L

Reference Manual

000809-0100-4696, Rev AA September 2004

Commissioning

To be able to setup, configure, and have a device communicate with other

(Addressing)

devices on a segment, a device must be assigned a permanent address.

 

Unless requested otherwise, it is assigned a temporary address when

 

shipped from the factory.

 

If there are two or more devices on a segment with the same address, the first

 

device to start up will use the assigned address (ex. Address 20). Each of the

 

other devices will be given one of the four available temporary addresses. If a

 

temporary address is not available, the device will be unavailable until a

 

temporary address becomes available.

 

Use the host system documentation to commission a device and assign a

 

permanent address.

HARDWARE

The 848L has no moving parts and requires a minimal amount of scheduled

MAINTENANCE

maintenance. If a malfunction is suspected, check for an external cause

 

before performing the diagnostics presented below. The 848L has a green

 

LED which indicates that the device has both DC I/O power and power from

 

the bus. Once powered the green LED will remain illuminated as long as the

 

I/O power is available even if bus power is lost.

 

The red LED indicates that the Resource block is Out of Service. Any

 

hardware fault detected except open or shorted sensors will place the

 

Resource block in the Out of Service mode.

Sensor Check

The amber LEDs indicate if the 848L is detecting the sensor as open or

 

closed. To check the input circuit you can connect a working sensor at the

 

transmitter and check it's operation. Consult an Emerson Process

 

Management representative for additional assistance.

 

It is possible that the sensor LEDs do not reflect the actual state of a sensor

 

since they are activated by the electronics and not directly by the sensor. Use

 

appropriate electrical test equipment to verify actual sensor states.

Communication/Power

If the transmitter does not communicate or provides an erratic output, check

Check

for adequate voltage to the transmitter. The transmitter requires between 9.0

 

and 32.0 VDC at the bus terminals to operate with complete functionality.

 

Check for wire shorts, open circuits, and multiple grounds.

Resetting the Configuration (RESTART)

There are two types of restarts available in the Resource Block. The following section outlines the usage for each of these.

Restart Processor (cycling)

Performing a Restart Processor has the same effect as removing power from the device and reapplying power.

Restart with Defaults

Performing a Restart with Defaults resets the static parameters for all of the blocks to their initial state. This is commonly used to change the configuration and/or control strategy of the device, including any custom configurations done at the Rosemount factory.

4-2

Image 44
Contents Reference Manual 00809-0100-4696,Rev AA SeptemberRosemount 848L Discrete Logic Temperature Transmitter withRosemount 848L FOUNDATION FieldbusTable of Contents SECTION 1 Introduction SECTION 2 InstallationSECTION 3 Configuration Rosemount 848LSECTION Operation and Maintenance APPENDIX A Reference Data APPENDIX B Product CertificationsAPPENDIX C Function Blocks Rosemount 848LAPPENDIX D Logic Equation Syntax APPENDIX E Motor ControlAPPENDIX F Valve Control Rosemount 848LTOC-4 Rosemount 848LReference Manual SAFETY MESSAGES Warnings SectionIntroduction Rosemount 848LOVERVIEW TransmitterManual Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848LReference Manual Rosemount 848L Reference ManualInstallation SAFETY MESSAGES Warnings MOUNTINGSection Rosemount 848LMounting to a DIN Rail Without an Enclosure Mounting to a Panel with a Junction BoxRosemount 848L Reference ManualMounting to a 2-InchPipe Stand Rosemount 848LReference Manual 00809-0100-4696,Rev AA SeptemberWIRING Power Supply ConnectionsRosemount 848L Reference ManualSWITCHES Surges/TransientsGROUNDING Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848LReference Manual I/O WIRING DISCRETE INPUT WIRING CONFIGURATIONDISCRETE OUTPUT WIRING CONFIGURATION Rosemount 848LReference Manual TAGGINGRosemount 848L INSTALLATION Using Cable Glands TRANSMITTER LABELRosemount 848L Reference ManualReference Manual Using Conduit EntriesRosemount 848L Configuration OVERVIEW SAFETY MESSAGES WarningsSection Rosemount 848LReference Manual GENERAL BLOCK INFORMATION ModesRosemount 848L Reference Manual Link Active Scheduler Block InstantiationRosemount 848L RESOURCE BLOCK FEATURES and FEATURES SEL CapabilitiesRosemount 848L Reference ManualReference Manual MAX NOTIFYRosemount 848L Reference Manual PlantWeb AlarmsRosemount 848L 00809-0100-4696,Rev AA September Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual Reference Manual Alarms I/O TRANSDUCER BLOCKRosemount 848L Reference Manual LOGIC TRANSDUCER BLOCKRosemount 848L Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Figure 3-1.848L Logic Transmitter Data Flow00809-0100-4696,Rev AA September Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual Reference Manual DISCRETE INPUT BLOCKSRosemount 848L DISCRETE OUTPUT BLOCKS MULTIPLE DISCRETE INPUT BLOCKMULTIPLE DISCRETE OUTPUT BLOCK Rosemount 848LRosemount 848L Reference ManualSection 4 Operation and Maintenance FOUNDATION FIELDBUS INFORMATIONSAFETY MESSAGES Warnings Rosemount 848LMAINTENANCE Communication/PowerResetting the Configuration RESTART CommissioningTROUBLESHOOTING I/O Transducer and Logic Block TroubleshootingResource Block NAMUR SensorsRosemount 848L Reference ManualSPECIFICATIONS Functional Specifications Appendix AReference Data Rosemount 848L00809-0100-4696,Rev AA September Rosemount 848LReference Manual 00809-0100-4696,Rev AA September Rosemount 848LReference Manual Physical Specifications Function Blocks SpecificationRosemount 848L Reference ManualReference Manual DIMENSIONAL DRAWINGSRosemount 848L Figure A-3.Rosemount 848L Wiring Diagram Rosemount 848LReference Manual 00809-0100-4696,Rev AA SeptemberReference Manual ORDERING INFORMATIONRosemount 848L Rosemount 848L Reference ManualAppendix B Product Certifications APPROVED MANUFACTURING LOCATIONSEUROPEAN DIRECTIVE INFORMATION HAZARDOUS LOCATIONS CERTIFICATES North American ApprovalsReference Manual European ApprovalsRosemount 848L Appendix C Function Blocks RESOURCE BLOCK PARAMETERSRosemount 848L Reference ManualFREE SPACE Rosemount 848LReference Manual OUTPUT Rosemount 848LReference Manual Reference Manual ADVISE ENABLERosemount 848L I/O TRANSDUCER PARAMETERS Rosemount 848LReference Manual 00809-0100-4696,Rev AA SeptemberTRANSDUCER TYPE Rosemount 848LReference Manual OUT 3 TAG Rosemount 848LReference Manual LOGIC TRANSDUCER PARAMETERS Rosemount 848LReference Manual 00809-0100-4696,Rev AA SeptemberReference Manual DISCRETE INPUT BLOCKRosemount 848L Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Table C-4.ParametersReference Manual DISCRETE OUTPUT BLOCK Supported ModesRosemount 848L Reference Manual MULTIPLE DISCRETE INPUT BLOCKSRosemount 848L Rosemount 848L Reference ManualMULTIPLE DISCRETE OUTPUT BLOCK 00809-0100-4696,Rev AA SeptemberRosemount 848L Reference Manual00809-0100-4696,Rev AA September Table C-7.Parameters andReference Manual Appendix D Logic Equation SyntaxRosemount 848L Rosemount 848L Reference Manual00809-0100-4696,Rev AA September Table D-1.Supported FunctionsPS channel number, divisor Rosemount 848LReference Manual ERROR HANDLING Table D-2.Error HandlingRosemount 848L Reference ManualReference Manual EXAMPLESRosemount 848L Rosemount 848L Reference ManualAppendix E Motor ControlINTRODUCTION TO MOTOR CONTROL Rosemount 848LReference Manual VARIATIONS ON MOTOR CONTROLRosemount 848L 00809-0100-4696,Rev AA September Rosemount 848LReference Manual Reference Manual WRITING 848L EQUATIONS Basic Motor ControlRosemount 848L Reference Manual Interlock Permissive Emergency ShutdownRosemount 848L Reference Manual Restart DelayRosemount 848L Reference Manual Maximum RestartsRosemount 848L Reference Manual Winding TemperatureRosemount 848L Reference Manual Hand-Off-AutoRosemount 848L Reference Manual Intermediate StopRosemount 848L Reference Manual Redundant Motors - Alternate StartRosemount 848L Reference Manual Redundant Motors - Timed SwitchRosemount 848L 00809-0100-4696,Rev AA September Rosemount 848LReference Manual Reference Manual Redundant Motors - Switch on FailureRosemount 848L 00809-0100-4696,Rev AA September Rosemount 848LReference Manual E-16 Rosemount 848LReference Manual Appendix F Valve ControlINTRODUCTION TO VALVE CONTROL Rosemount 848LReference Manual Alarms Variations on Valve ControlRosemount 848L Reference Manual Boolean Expressions Basic Valve ControlRosemount 848L Open-Auto-Close Alarm Variations Output Variations Output with InterlockRosemount 848L Reference ManualReference Manual Simple Valve Variations PermissiveRosemount 848L Reference Manual Double Block and BleedRosemount 848L Reference Manual Motorized Valve Heat Exchange Medium SelectionRosemount 848L Rosemount 848L Reference ManualIndex Rosemount 848LReference Manual 00809-0100-4696,Rev AA 9/17/0400809-0100-4696,Rev AA 9/17/04 Rosemount 848LReference Manual 00809-0100-4696,Rev AA 9/17/04 Rosemount 848LReference Manual Index-4 Rosemount 848LReference Manual ¢00809-0100-4697F¤ Reference Manual