Emerson operation manual Input Setup in E2

Page 100

P/N

Sensor

Input Type

Wiring

Dip Switch

 

 

 

 

 

 

550-2500

KW Transducer Down for 4-

4-20 mA output to input board

550-2550

 

20mA, Up for

1. Wire positive transducer terminal

 

 

Pulse

to positive 24VDC supply.

2. Wire negative transducer termi- nal to odd numbered input termi- nal.

3. Wire negative 24VDC supply to even numbered input terminal.

4. Place 250Ω resistor across odd and even numbered input termi- nals.

Pulse Accumulator output to input board

1. If the input board is an 8IO or a 16AI version E.02 or greater, connect the two KWh terminals to the input point (polarity insensitive)

2. If the input board is a 16AI version less than E.02, connect the KWh terminals to board point 1. Set input switch #1 DOWN, and set input switch #8 UP.

3. If the input board is a 16AIe, connect the two KWh terminals to input # 1, 2, 3, or 4 ONLY.

Table 9-1- Sensor Wiring

9.1.3Input Setup in E2

At this point in the setup process, you should have all sensors, transducers, and other input devices wired to points on MultiFlexes, 16AIs, and all output devices con- nected to 8ROs, 8DOs, or 4AOs outputs. Once the physi- cal wiring is complete, you will need to tell E2 the types of sensors or devices that are connected to each I/O point. This is achieved in the Input and Output Definitions screens.

9.1.3.1Configuring a Point from the Input Definitions/Status Screen

To configure a point, go to the Input Definitions/Status screen by pressing Alt + I or:

1.Press to open the Main Menu

2.Press (System Configuration)

3.Press (Input Definitions)

The Input Status screen opens:

Figure 9-4- Input Status Screen

Use the up and down arrow keys to move the cursor to the point you wish to set up, and press (SETUP).

Apop-up menu such as the one shown in Figure 9-5will prompt you to specify the point as analog or digital.

Press if the input is analog, press if the input is dig-

9-6 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013

Image 100
Contents BX HVAC, and CX Convenience Store Controllers Rev 4 5-JAN-2013Page E2 Firmware Version Page Table of Contents Inside Temperature Sensor Outside Temperature SensorInsertion Temperature Probe Product Temperature Probes Humidity Sensors and HumidistatsBoard Installation Plug-In Digital I/O Network Card P/NPlug-InFour-Channel Internal Repeater 1 I/O Board Names and Terminology MultiFlex-Plus + BoardPowering Echelon Devices Configuring Echelon DevicesConnecting Sensors to Input Boards Power Connection Input Setup in E2Setting the Time and Date 10-9 10.9 Changing Required User Access LevelsWeb Services Specifying Alarm Reporting TypesPriority Settings Using and Configuring a Setup ScreenUsing the Help Key to get Property Help Clean and Door Switches 11-711.4.9 Clean/Wash Mode 11.4.11 Fail-Safe Mode11.4.12 Wiring Setting Up An Individual Case Controller11.7.4 Temperature Control 11.7.5 Zone Temperature11.7.7 Economization Enable 11.7.2 How Zones WorkSetpoint Reset Temperature Differential TD StrategyConfiguration AlarmsService Modes 11.21.12 ConfigurationLearning Mode Accessing the Alarm Advisory Log12.10.5 Ack/Reset State 12.10.8 Acknowledging, Resetting, and Clearing Log Entries12.10.9 Facility Status Display FSD Alarms 12.10.2 Viewing the Controller Advisory LogPage Introduction E2 Refrigeration Controller RXE2 Building Controller BX E2 Convenience Store Controller CX Networking Overview 1 E2 I/O NetworkE2 Echelon Lonworks Network Interconnection With Other E2sDocumentation Overview On-Line Help System Overview Software LicensingPage Hardware Overview E2 Hardware1 E2 Main Processor Board 3 E2 Keypad LEDsPIB LEDs Status PIB LED’s StatusI/O Network Boards and Peripherals Gateway BoardMain Board Status CPU LEDs Keyboard StatusMultiFlex Boards MultiFlex 16 Input BoardMultiFlex Combination Input/ Output Boards Gateway ModelModel Description Name MultiFlex Combination Input/Output Board Top ViewMultiFlex CUB MultiFlex RTU BX and CX OnlyMultiFlex Rooftop Control Board RCB BX and CX Only MultiFlex PAK BoardMultiFlex ESR Board Hand-held Terminal P/N8RO and 8ROSMT Relay Boards RJ-11 to male RJ-11 cable6 4AO Analog Output Board 15- 4AO Analog Output Board P/N16AIe Dis 8ROe DisEC-2s 5 TD3 Temperature Display Facility Status Display FSDMounting Mounting the E2Standard Mount Recessed MountRetrofit Mounting Standard Mount Inside Rear of EnclosureBlank Face Mounting I/O BoardsSingle/Double Enclosures Boards Without Enclosures Snap Track 4AO BoardEchelon Devices COM3 Internal Modem Plug-In Card P/NMultiFlex ESR 3 TD3Two-Channel and Four- Channel Repeaters Mounting Repeaters OverviewMounting the Two-Channel Repeater Mounting the Four-Channel RepeaterInside Temperature Sensor Outside Temperature SensorSensors Transducers Pressure TransducersInsertion Temperature Probe Supply and Return Air SensorsMounting Bullet and Pipe Mount Sensors Application Sensor TypeProduct Temperature Probes Humidity Sensors and HumidistatsIndoor RH Sensor Outdoor RH SensorsLight Level Sensor Dewpoint ProbeDuct-mounted Insertion RH Probe Liquid Level Sensors Refrigerant Leak DetectorsPage E2 Hardware Setup Setting up the E2Main Processor Board EnclosurePowering the E2 Add-On E2 PeripheralsPlug-In Digital I/O Network Card P/N 3 COM3 Internal Modem Plug- In Card P/NLEDs E2 Installation Guide Serial Device Software Setup OverviewCOM Ports Pre-SetsE2COM# Associations Connector Page Page RS485 Network and Hardware Setup I/O Network1 I/O Board Names and Terminology Or I/O NetWiring Types MultiFlex-Plus + BoardI/O Network Structure Daisy Chains Board DesignationNetwork Noise Minimization Setting the Baud RateNetwork ID Numbers Board Numbers Setting the Terminating and Biasing Jumpers Powering the I/O BoardsWiring Types Board Installation IMC/Prodigy Rooftop Unit ControllersControl Techniques Drive 14 AWG3 XR35CX, XR75CX, XEV22 Case Controllers IPro DACEnergy Meter 3.1 XR75CX-Case DisplayCopeland Discus with CoreSense Protection Supported System TypesLight Commercial Thermostat Advisory and AlarmsThermostat Inputs Comfort Alert Descriptions Cause E2 Advisory High/Low Occ/Unocc Space Temperature Alarms Supply Sensor Fail AlarmRefrigerant Leak Detection System Rlds Conditions for Return to Normal RTN on Diag- nostic CodesDiagnostic Alarms XM Series of Case Controllers12.1 XM670 12.2 XM679BACnet BACnet OverviewBACnet Communication Master Slave Token Passing3 MS/TP Network Connection To E2 BACnet IP Internet ProtocolDiscovery Client-ServerRescan 13- Commissioning Screen16 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Multiflex Combination I/O Board Installation Guide 18 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 BACnet 20 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 16AI Installation Guide MultiFlex ESR Installation Guide BACnet 24 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Page Page Ethernet IP Configurations Hardware SpecificationsEquipment Type Specifications E2 Ethernet Peer CommunicationsEthernet Network Layouts Closed Network LayoutOpen Network Layout Open Network LayoutTroubleshooting Peer Network Tab Set Group NameEchelon Network and Hardware Setup Wiring TypeEchelon Network Cable Specifications Cable Type Emerson Retail Solutions Part NumberDevice Termination Maximum Number of Echelon DevicesWire Restrictions Installing Echelon DevicesPowering Echelon Devices Maximum Total Segment LengthConfiguring Echelon Devices Echelon Board Status Red D1 ResetRed Service LEDsTroubleshooting Connected/IO Setup Screen RX Unit ShownE2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 One pin when unterminating an E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Input and Output Setup WiringSensor Wiring Types Input Type Dip SwitchesPower Connection Input Type Dip Switches for MultiFlex 16 and 16AI BoardsSensor Input Type Wiring Dip Switch DownWall-mounted Down Down LevelInput Setup in E2 Using the Input Definitions/ Status Screen Setting Up Analog InputsApplication AssociationSensor Type Description Per Pulse onSetting Up Digital Inputs Digital Input Screen8RO, 8IO, and MultiFlex Outputs Wiring Form C ContactsMultiFlex Relay Outputs Setting the Fail-Safe Dip Switch Relay Output Test ModeOutput Board Fail-Safe and Switch Settings Board Type VersionWiring Outputs to Points Output Setup in E2Output LED Old 8ROsUsing the Output Definitions/ Status Screen Setting Up Digital OutputsSetting Up Analog Outputs 12- Digital Output Screen13- Analog Output Screen CC-100 Case Controllers InputsValve Cable Power Module Wiring335-3263 Pulse Valve CCB Case Controllers 335-3260 to Valve Connection InformationESR8 Boards Dis MultiFlex ESR BoardESR8 and MultiFlex ESR Valve Output Wiring Page Cleaning Out the Controller Performing a Clean OutQuick Start Logging OnBoards on the I/O Network Setting Number of Network DevicesUnit Controllers Echelon Setting Number of Applications Customizing the Home ScreenCommon Screen Elements HeaderFunction Keys Help LineScreen Types Main MenuStatus Screens Key Function for RXSetup Screens Actions MenuActions Menu Item Description Actions Menu Options and DescriptionsSystem Configuration Menu Options System Configuration MenuMenu Option Description System Information Menu System Information Menu OptionsTime/Date Setup Setting the Time and DateSet Up Modem Set Up TCP/IP 17- TCP/IP Addressing10.11.1 COM1 Serial RS232 Baud Rate Set Up Network Baud Rates10.11.2 I/O Network Baud Rate User Access Levels Set Up User AccessLevel Creating a New User Account Changing Required User Access LevelsDeleting a User Specify Number of Boards Set Up I/O NetworkChecking Online Status Specifying Number Devices Set Up Echelon NetworkCommissioning a Device Service Button Method How Echelon Commissioning WorksModbus Commissioning Network CommissioningCC-100’s Service Button TD3’s Service ButtonESR8’s Service Button Manual ID Entry MethodLicense Management 31- Commissioning MenuSet Up Alarming Web ServicesSpecifying Alarm Reporting Types Alarm OutputEchelon Network Alarm Annunciator Display LineAlarm Dial-Out Setting up an E2 to be an Alarm AnnunciatorSet Alarm Annunc field to Yes Set Up Global Data Introduction Alarm ReportingPriority Settings 10-24 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013Set Up Applications Example Setting Up an Outdoor Temperature Sen- sorUsing and Configuring a Setup Screen 10.18.1 Add/Delete an ApplicationAdd an Application Delete an ApplicationEdit Menu Navigating the Setup ScreenEntering Setpoints Function Keys For Setup Function Keys for Setup ScreensIndex Tabs Help LineUsing the Help Key to get Property Help Page Software Overview Suction GroupsIntroduction Standard Suction Group ApplicationLearning Mode Hardware OverviewCircuit Load Analysis Control/Cycles ParameterTemperature Differential Strategy Input Sensor Type Wiring InstructionsCondenser Control Air Cooled CondensersCondenser Split Mode Fast RecoveryEvaporative Condensers Fan ControlStandard Circuits Evaporative CondenserRefrigeration Control Defrost ControlClean and Door Switches Clean SwitchesDefrost Termination Emergency DefrostTD3 Temperature Display WiringDoor Switches Control Link CD Case DisplayTypical Case in a Standard Circuit Case Control Circuits OverviewValve Control EEVs Liquid Pulse and Liquid StepperThermostatic Expansion Valves TXVs EEPRs Suction StepperOff Cycle Timed Temperature Termination Anti-Sweat ControlDemand Defrost Wait StateClean/Wash Mode Dual Temp ControlLight Control Dewpoint Input SourcesRecoverable Sensor Failures Fail-Safe ModeWalk-In Freezer Control Setting Up An Individual Case Controller Logging GroupsPossible Data Errors Data CompressionBase Log Group ClippingSetting Up Logging Logging Setup MenuLogging Group Status Screen Log ReportsLogging Group Report Application Log ReportTemperature Control Air Handling UnitsAlternate Setpoints System Log ReportTwo-Speed Fans Single-Speed FansVariable-Speed Fans Economizer Control Digital Economizer ControlAnalog Economizer Control Dehumidification ControlOptimum Start/Stop OSS CurtailmentIntelligent Pre-Starts and Pre-Stops Separate Setpoints AHU Zone ControlOutput Device Wire 8RO contacts Set Fail-safe Dip Switch to Zone ControlHow Zones Work 11- Suction Group OutputsApplications That May Be Connected To Zones MultiFlex RTU BoardMultiFlex RCB Board MultiFlex RCB-P BoardEconomization Enable Zone TemperatureAHUs Zone Humidity Input Effect of Enabling Dehumidification Effect of Enabling EconomizationMultiFlex RTUs and RCBs 17- Diagram of Pre-Start and Pre-Stop Operation MultiFlex CUB Board Losing Contact With Zone ApplicationsStand-Alone MultiFlex RTUs MultiFlex RTU/ARTC and AHU Zone AssociationMultiFlex PAK Board Lighting SchedulesFunctions of the Lighting Schedule Application Control Method SelectStandard Control Light Level Interface CellSchedule Interface Cell Alternate ControlMulti-Logic Combiner Basic Schedule Cell Min ON/OFF CellProof Cell Offset Solar ControlDemand Control Output Light DimmingIntroduction to Demand Limit Control Demand MonitoringLoad Shedding Shedding LevelsPriority Levels DefinitionLast Shed Rotational ShedOther Notes About Priority Levels Mode 3 Integral Error Approaching Zero Mode 1 KW Input Is Greater Than SetpointHow Demand Control Uses Load Shedding Power Monitoring Input SettingsSensor Control Analog Sensor ControlLogical Combination Digital Sensor ControlControl Cells Diagram Loop/Sequence Control Cell DescriptionsOutput Cells Select CellOutput Cell Descriptions Time Scheduling and Holidays How Schedules WorkPWM Cell EventsPower Monitoring Holiday SchedulesTemporary Schedule Events OverlappingLogging HourlyDaily MonthlyHeat/Cool Control Anti-Sweat SetupHow Anti-Sweat Works Setpoint Reset Unoccupied HysteresisAnalog and Digital Combiners Lead/LagTemperature Differential TD Strategy ConfigurationTD Control TD Control Fail-SafesPulse Accumulation AlarmsOutputs Accumulator Reset Types Irrigation ControlHigh Trip Zones and CyclesZone Inhibit Cycle SchedulingZone Bypass Inputs Flow Sensor-Related Tests Service ModesTwo Speed Fan Control Flexible Combiner Modular Chiller Control MCCLearning Mode Compressor ControlBoiler Bypass Valve ControlDigital Scroll Compressor Variable Frequency Drive CompressorRMS Asset RMS ScaleLog Information Device ConstraintsLogged Changes Unlogged ChangesPage Page Operator’s Guide to Using the E2 E2 Home ScreenBX Home Screen RX Home ScreenLogging On and Access Levels CX Home ScreenSystem Configuration Menu Toggling Full OptionsNavigation MenusPress System Configuration Press System Information System Information MenuScreen Types Actions MenuSummary Screens Status ScreensIndex Tabs Setup ScreensHeader Icons E2 Keypad CursorTab Key Enter KeyLog In/Out Key Four Directional Arrow KeysUp/Page Down Keys Ctrl Page Up/Ctrl Page Down KeysManual Defrost and Clean Mode Customizing the Home ScreenList menu and choose End Manual Mode OverridesChecking Boards Online Checking Status Screens Alarms Accessing the Alarm Advi Sory LogViewing the Controller Advisory Log Date and Time12.10.5 Ack/Reset State Alarm StatesArea Ctrl Application Property Advisory MessageResetting ClearingFacility Status Display FSD Alarms Viewing Logs and GraphsLocating Logged Inputs Outputs Home/Status ScreensSetting Up Input and Output Pointers Setup ScreensLog View Graph View Zooming In and OutMultiple Languages High Alarm, Low Alarm, and Delay Appendix a Case Type DefaultsDefrost Type Hdbx Table B-1- Temp Sensor Temperature/Resistance Chart Table B-2- Eclipse Voltage to Pressure ChartEclipse Transducers Voltage Pressure PSI 100 lb 200 lb 500 lb XducerPage Appendix C Alarm Advisory Messages Alarm Name Default Definition PriorityE2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Appendix C Alarm Advisory Messages C-3 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-5 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-7 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-9 10 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Appendix C Alarm Advisory Messages C-11 12 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 RAM 14 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Copeland CoreSense E2 Alarms ISD 2.0/2.1 CoreSense DiagnosticsNo 3PHASE PWR CoreSense Device Performance Alert CoreSense DiagnosticsOther Advisories Discus P470 CoreSense Protection K5 Ref Scroll P510 Copeland Scroll CoreSense CommP47 CoreSense Comm Appendix D PID Control Proportional P ModeThrottling Range Integral Mode Why I Mode is NecessaryProportional Constant Kp Throttling Range on page D-1I Mode Calculation Derivative ModeSaturation D Mode Calculation How Condenser Control Hvac PID Differs From OthersOutput at Setpoint Output at Setpoint for Non-CondenserOther PID Features Changing the Output at SetpointOutput at Minimum / Output at Maximum Output at Setpoint for Condenser/HVAC PID ControlMinimum Accumulated Error FilteringPage Page Medium Resolution Reuccf Page Page Appendix F Troubleshooting Refer to .1.9, PoweringEchelon Network Appendix F Troubleshooting F-3 Symptom Possible Problem Solution Number of Fans field? TripSymptom Possible Problem Solution Appendix F Troubleshooting F-7 Figured as an analog input Page Page Appendix G Revision Log Page Index NumericsBlue R. See Cold Reset Wash mode. See Clean Mode Demand Defrost. See Defrost, demand Hot Gas Defrost. See Defrost, hot gas Tion Probe LonWorks Network. See Echelon Network Pmac Hansen probe. See Sensors, liquid level 10 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Valves
Related manuals
Manual 273 pages 39.74 Kb