6.1.5Network Noise Minimization

Site environments will frequently have numerous sources of high EMI, or “noise,” that must be accounted for when routing RS485 network cable. Although the cable is shielded against noise, the installer must follow best practices for minimizing network noise.

In general, installers should follow these guidelines when installing RS485 networks:

Avoid running cable next to noise-generating devices, such as motor starters, contactors, invert- ers, fluorescent light ballasts, arc welders, etc. If possible, keep cable less than 1 foot away from noise-generating devices (ideally, at least 5 feet).

Do not run RS485 cable in the same conduit as high-voltage wiring, such as 120VAC or 240VAC power wiring. Keep RS485 cable a minimum of 3 inches away from high-voltage wiring (ideally, at least 12 inches). If RS485 must cross paths with high-voltage wiring, cross them perpendicular — running RS485 and high-voltage wire in parallel increases the amount of noise induced on the net- work.

Ensure you are grounding each input device’s 0V power terminal to a separate earth ground, and set- ting the termination and biasing jumpers as instructed in Section 6.1.8, Setting the Terminating and Biasing Jumpers.

For more instructions on best practices for minimizing noise, refer to publication 026-1903, E2 Controller Wir- ing Practices, available in the Product Manuals section of the Emerson Climate Technologies Web site:

www.emersonclimate.com

6.1.6Network ID Numbers (Board Numbers)

Each device on an RS485 segment has either a network dip switch or rotary dials that must be used to assign the board a unique network ID number.

The network ID number makes a board unique from other boards on the network of the same type. This allows E2 to find it and communicate with it easily.

Boards of the same type should be numbered in sequence, starting with one and continuing with two, three, and so forth. For example, if a segment contains four 16AI boards and five 8RO boards, you should num- ber the 16AIs one, two, three, and four; and the 8ROs one, two, three, four, and five. The same should be done with multiple 4AO and 8DO boards, and IRLDS leak detection units.

For all boards, except 8IO and 8DO boards, the net- work dip switch labeled S1 (or S3 for the 16AI board) is used to set the unique board number of the unit and the baud rate. The 8IO and 8DO uses rotary dials to set the board number of the unit.

Numbering the MultiFlex Combination I/O Boards

When it comes to network numbering, the MultiFlex

Combination Input/Output boards (88, 88AO, 168, 168AO, and 168DO) are special cases. They are actually a

combination of three types of Emerson Retail Solutions

boards: the inputs are configured like a 16AI, the relay outputs are configured like an 8RO, and the analog outputs are configured like a 4AO.

When a MultiFlex combo board is present on the net- work, it must be addressed like all three board types. Therefore, when numbering these boards, you must set a unique number for both the 16AI, 8RO, and 4AO compo- nents of the board.

Addressing the MultiFlex Boards

For MultiFlex boards, set positions 1 to 5 on S3 for the 16AI component and positions 1 to 5 on S4 for the 8RO component. Set positions 6 to 8 on S4 for the 4AO or 4DO segment. For MultiFlex board controllers, use positions 1 to 5 on S3 to set the address.

Addressing the MultiFlex ESR Boards

The MultiFlex ESR uses standard Emerson Retail Solutions I/O Network addressing. Set positions 1 to 5 on S1 to set the network ID (address) of the MultiFlex ESR from 1 to 31.

6.1.7Setting the Baud Rate

All I/O boards have dip switches that determine the baud rate at which they communicate. Currently, the baud rate dip switch in network components may be set at either 4800, 9600, 19200, and 38400. Setting of the baud rate is accomplished using dip switches (refer to the board’s installation sheets at the end of this section for specific dip switch settings).

Baud Rate for the E2

The baud rate default for E2 is 9600.

Baud Rate for the Gateway

The Gateway can be set to either 9600 baud or 19.2K baud by dip switch #6. “ON” places the rate at 9600 baud while “OFF” sets it at 19.2K baud.

Dip switches 6 and 7 control the baud rate at which the Gateway communicates with the site controller on the RS485RS485 Network. These switches must be set to the same baud rate setting as the E2 or REFLECS (usually 9600 baud).

The I/O Network

The RS485 Network and Hardware Setup 6-3

Image 59
Contents Rev 4 5-JAN-2013 BX HVAC, and CX Convenience Store ControllersPage E2 Firmware Version Page Table of Contents Product Temperature Probes Humidity Sensors and Humidistats Inside Temperature SensorOutside Temperature Sensor Insertion Temperature Probe1 I/O Board Names and Terminology MultiFlex-Plus + Board Board InstallationPlug-In Digital I/O Network Card P/N Plug-InFour-Channel Internal RepeaterPower Connection Input Setup in E2 Powering Echelon DevicesConfiguring Echelon Devices Connecting Sensors to Input BoardsSpecifying Alarm Reporting Types Setting the Time and Date 10-9 10.9Changing Required User Access Levels Web ServicesClean and Door Switches 11-7 Priority SettingsUsing and Configuring a Setup Screen Using the Help Key to get Property HelpSetting Up An Individual Case Controller 11.4.9 Clean/Wash Mode11.4.11 Fail-Safe Mode 11.4.12 Wiring11.7.2 How Zones Work 11.7.4 Temperature Control11.7.5 Zone Temperature 11.7.7 Economization EnableAlarms Setpoint ResetTemperature Differential TD Strategy ConfigurationAccessing the Alarm Advisory Log Service Modes11.21.12 Configuration Learning Mode12.10.2 Viewing the Controller Advisory Log 12.10.5 Ack/Reset State12.10.8 Acknowledging, Resetting, and Clearing Log Entries 12.10.9 Facility Status Display FSD AlarmsPage E2 Refrigeration Controller RX IntroductionE2 Building Controller BX E2 Convenience Store Controller CX 1 E2 I/O Network Networking OverviewInterconnection With Other E2s E2 Echelon Lonworks NetworkDocumentation Overview Software Licensing On-Line Help System OverviewPage E2 Hardware Hardware OverviewPIB LED’s Status 1 E2 Main Processor Board 3 E2 KeypadLEDs PIB LEDs StatusKeyboard Status I/O Network Boards and PeripheralsGateway Board Main Board Status CPU LEDsGateway Model MultiFlex BoardsMultiFlex 16 Input Board MultiFlex Combination Input/ Output BoardsMultiFlex Combination Input/Output Board Top View Model Description NameMultiFlex PAK Board MultiFlex CUBMultiFlex RTU BX and CX Only MultiFlex Rooftop Control Board RCB BX and CX OnlyHand-held Terminal P/N MultiFlex ESR BoardRJ-11 to male RJ-11 cable 8RO and 8ROSMT Relay Boards15- 4AO Analog Output Board P/N 6 4AO Analog Output Board8ROe Dis 16AIe DisEC-2s Facility Status Display FSD 5 TD3 Temperature DisplayRecessed Mount MountingMounting the E2 Standard MountStandard Mount Inside Rear of Enclosure Retrofit MountingSingle/Double Enclosures Mounting I/O BoardsBlank Face 4AO Board Boards Without Enclosures Snap Track3 TD3 Echelon DevicesCOM3 Internal Modem Plug-In Card P/N MultiFlex ESRMounting the Four-Channel Repeater Two-Channel and Four- Channel RepeatersMounting Repeaters Overview Mounting the Two-Channel RepeaterPressure Transducers Inside Temperature SensorOutside Temperature Sensor Sensors TransducersApplication Sensor Type Insertion Temperature ProbeSupply and Return Air Sensors Mounting Bullet and Pipe Mount SensorsOutdoor RH Sensors Product Temperature ProbesHumidity Sensors and Humidistats Indoor RH SensorDuct-mounted Insertion RH Probe Dewpoint ProbeLight Level Sensor Refrigerant Leak Detectors Liquid Level SensorsPage Enclosure E2 Hardware SetupSetting up the E2 Main Processor BoardAdd-On E2 Peripherals Powering the E2LEDs 3 COM3 Internal Modem Plug- In Card P/NPlug-In Digital I/O Network Card P/N E2 Installation Guide Pre-Sets Serial Device Software SetupOverview COM PortsE2COM# Associations Connector Page Page Or I/O Net RS485 Network and Hardware SetupI/O Network 1 I/O Board Names and TerminologyBoard Designation Wiring TypesMultiFlex-Plus + Board I/O Network Structure Daisy ChainsNetwork ID Numbers Board Numbers Setting the Baud RateNetwork Noise Minimization Powering the I/O Boards Setting the Terminating and Biasing JumpersWiring Types 14 AWG Board InstallationIMC/Prodigy Rooftop Unit Controllers Control Techniques Drive3.1 XR75CX-Case Display 3 XR35CX, XR75CX, XEV22 Case ControllersIPro DAC Energy MeterSupported System Types Copeland Discus with CoreSense ProtectionThermostat Inputs Advisory and AlarmsLight Commercial Thermostat Comfort Alert Descriptions Cause E2 Advisory Conditions for Return to Normal RTN on Diag- nostic Codes High/Low Occ/Unocc Space Temperature AlarmsSupply Sensor Fail Alarm Refrigerant Leak Detection System Rlds12.2 XM679 Diagnostic AlarmsXM Series of Case Controllers 12.1 XM670Master Slave Token Passing BACnetBACnet Overview BACnet CommunicationClient-Server 3 MS/TP Network Connection To E2BACnet IP Internet Protocol Discovery13- Commissioning Screen Rescan16 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Multiflex Combination I/O Board Installation Guide 18 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 BACnet 20 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 16AI Installation Guide MultiFlex ESR Installation Guide BACnet 24 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Page Page E2 Ethernet Peer Communications Ethernet IP ConfigurationsHardware Specifications Equipment Type SpecificationsClosed Network Layout Ethernet Network LayoutsOpen Network Layout Open Network LayoutPeer Network Tab Set Group Name TroubleshootingCable Type Emerson Retail Solutions Part Number Echelon Network and Hardware SetupWiring Type Echelon Network Cable SpecificationsMaximum Number of Echelon Devices Device TerminationMaximum Total Segment Length Wire RestrictionsInstalling Echelon Devices Powering Echelon DevicesLEDs Configuring Echelon DevicesEchelon Board Status Red D1 Reset Red ServiceConnected/IO Setup Screen RX Unit Shown TroubleshootingE2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 One pin when unterminating an E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Input Type Dip Switches Input and Output SetupWiring Sensor Wiring TypesInput Type Dip Switches for MultiFlex 16 and 16AI Boards Power ConnectionDown Sensor Input Type Wiring Dip SwitchWall-mounted Down Level DownInput Setup in E2 Association Using the Input Definitions/ Status ScreenSetting Up Analog Inputs ApplicationPer Pulse on Sensor Type DescriptionDigital Input Screen Setting Up Digital InputsMultiFlex Relay Outputs Wiring Form C Contacts8RO, 8IO, and MultiFlex Outputs Board Type Version Setting the Fail-Safe Dip SwitchRelay Output Test Mode Output Board Fail-Safe and Switch SettingsOld 8ROs Wiring Outputs to PointsOutput Setup in E2 Output LEDSetting Up Digital Outputs Using the Output Definitions/ Status Screen12- Digital Output Screen Setting Up Analog Outputs13- Analog Output Screen Inputs CC-100 Case Controllers335-3263 Pulse Valve Power Module WiringValve Cable MultiFlex ESR Board CCB Case Controllers335-3260 to Valve Connection Information ESR8 Boards DisESR8 and MultiFlex ESR Valve Output Wiring Page Logging On Cleaning Out the ControllerPerforming a Clean Out Quick StartUnit Controllers Echelon Setting Number of Network DevicesBoards on the I/O Network Customizing the Home Screen Setting Number of ApplicationsHelp Line Common Screen ElementsHeader Function KeysKey Function for RX Screen TypesMain Menu Status ScreensActions Menu Options and Descriptions Setup ScreensActions Menu Actions Menu Item DescriptionMenu Option Description System Configuration MenuSystem Configuration Menu Options System Information Menu Options System Information MenuSetting the Time and Date Time/Date SetupSet Up Modem 17- TCP/IP Addressing Set Up TCP/IP10.11.2 I/O Network Baud Rate Set Up Network Baud Rates10.11.1 COM1 Serial RS232 Baud Rate Level Set Up User AccessUser Access Levels Deleting a User Changing Required User Access LevelsCreating a New User Account Checking Online Status Set Up I/O NetworkSpecify Number of Boards Commissioning a Device Set Up Echelon NetworkSpecifying Number Devices Network Commissioning Service Button MethodHow Echelon Commissioning Works Modbus CommissioningManual ID Entry Method CC-100’s Service ButtonTD3’s Service Button ESR8’s Service Button31- Commissioning Menu License ManagementWeb Services Set Up AlarmingDisplay Line Specifying Alarm Reporting TypesAlarm Output Echelon Network Alarm AnnunciatorSet Alarm Annunc field to Yes Setting up an E2 to be an Alarm AnnunciatorAlarm Dial-Out Introduction Alarm Reporting Set Up Global Data10-24 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Priority SettingsExample Setting Up an Outdoor Temperature Sen- sor Set Up ApplicationsDelete an Application Using and Configuring a Setup Screen10.18.1 Add/Delete an Application Add an ApplicationEntering Setpoints Navigating the Setup ScreenEdit Menu Help Line Function Keys For SetupFunction Keys for Setup Screens Index TabsUsing the Help Key to get Property Help Page Standard Suction Group Application Software OverviewSuction Groups IntroductionControl/Cycles Parameter Learning ModeHardware Overview Circuit Load AnalysisAir Cooled Condensers Temperature Differential StrategyInput Sensor Type Wiring Instructions Condenser ControlFan Control Condenser Split ModeFast Recovery Evaporative CondensersEvaporative Condenser Standard CircuitsDefrost Control Refrigeration ControlEmergency Defrost Clean and Door SwitchesClean Switches Defrost TerminationControl Link CD Case Display TD3 Temperature DisplayWiring Door SwitchesTypical Case in a Standard Circuit Overview Case Control CircuitsEEVs Liquid Pulse and Liquid Stepper Valve ControlOff Cycle Timed EEPRs Suction StepperThermostatic Expansion Valves TXVs Wait State Temperature TerminationAnti-Sweat Control Demand DefrostDewpoint Input Sources Clean/Wash ModeDual Temp Control Light ControlWalk-In Freezer Control Fail-Safe ModeRecoverable Sensor Failures Logging Groups Setting Up An Individual Case ControllerClipping Possible Data ErrorsData Compression Base Log GroupLogging Setup Menu Setting Up LoggingApplication Log Report Logging Group Status ScreenLog Reports Logging Group ReportSystem Log Report Temperature ControlAir Handling Units Alternate SetpointsVariable-Speed Fans Single-Speed FansTwo-Speed Fans Dehumidification Control Economizer ControlDigital Economizer Control Analog Economizer ControlIntelligent Pre-Starts and Pre-Stops CurtailmentOptimum Start/Stop OSS AHU Zone Control Separate Setpoints11- Suction Group Outputs Output Device Wire 8RO contacts Set Fail-safe Dip Switch toZone Control How Zones WorkMultiFlex RCB-P Board Applications That May Be Connected To ZonesMultiFlex RTU Board MultiFlex RCB BoardAHUs Zone TemperatureEconomization Enable MultiFlex RTUs and RCBs Effect of Enabling EconomizationZone Humidity Input Effect of Enabling Dehumidification 17- Diagram of Pre-Start and Pre-Stop Operation MultiFlex RTU/ARTC and AHU Zone Association MultiFlex CUB BoardLosing Contact With Zone Applications Stand-Alone MultiFlex RTUsLighting Schedules MultiFlex PAK BoardLight Level Interface Cell Functions of the Lighting Schedule ApplicationControl Method Select Standard ControlMulti-Logic Combiner Alternate ControlSchedule Interface Cell Offset Solar Control Basic Schedule CellMin ON/OFF Cell Proof CellDemand Monitoring Demand ControlOutput Light Dimming Introduction to Demand Limit ControlDefinition Load SheddingShedding Levels Priority LevelsOther Notes About Priority Levels Rotational ShedLast Shed How Demand Control Uses Load Shedding Mode 1 KW Input Is Greater Than SetpointMode 3 Integral Error Approaching Zero Analog Sensor Control Power Monitoring InputSettings Sensor ControlControl Cells Digital Sensor ControlLogical Combination Select Cell DiagramLoop/Sequence Control Cell Descriptions Output CellsOutput Cell Descriptions Events Time Scheduling and HolidaysHow Schedules Work PWM CellOverlapping Power MonitoringHoliday Schedules Temporary Schedule EventsMonthly LoggingHourly DailyHow Anti-Sweat Works Anti-Sweat SetupHeat/Cool Control Unoccupied Hysteresis Setpoint ResetLead/Lag Analog and Digital CombinersTD Control Fail-Safes Temperature Differential TD StrategyConfiguration TD ControlOutputs AlarmsPulse Accumulation Zones and Cycles Accumulator Reset TypesIrrigation Control High TripZone Bypass Inputs Cycle SchedulingZone Inhibit Two Speed Fan Control Service ModesFlow Sensor-Related Tests Modular Chiller Control MCC Flexible CombinerCompressor Control Learning ModeVariable Frequency Drive Compressor BoilerBypass Valve Control Digital Scroll CompressorDevice Constraints RMS AssetRMS Scale Log InformationUnlogged Changes Logged ChangesPage Page RX Home Screen Operator’s Guide to Using the E2E2 Home Screen BX Home ScreenCX Home Screen Logging On and Access LevelsMenus System Configuration MenuToggling Full Options NavigationSystem Information Menu Press System Configuration Press System InformationStatus Screens Screen TypesActions Menu Summary ScreensHeader Icons Setup ScreensIndex Tabs Enter Key E2 KeypadCursor Tab KeyCtrl Page Up/Ctrl Page Down Keys Log In/Out KeyFour Directional Arrow Keys Up/Page Down KeysCustomizing the Home Screen Manual Defrost and Clean ModeOverrides List menu and choose End Manual ModeChecking Boards Online Checking Status Screens Date and Time AlarmsAccessing the Alarm Advi Sory Log Viewing the Controller Advisory LogAdvisory Message 12.10.5 Ack/Reset StateAlarm States Area Ctrl Application PropertyClearing ResettingHome/Status Screens Facility Status Display FSD AlarmsViewing Logs and Graphs Locating Logged Inputs OutputsLog View Setup ScreensSetting Up Input and Output Pointers Zooming In and Out Graph ViewMultiple Languages Defrost Type Appendix a Case Type DefaultsHigh Alarm, Low Alarm, and Delay Hdbx 100 lb 200 lb 500 lb Xducer Table B-1- Temp Sensor Temperature/Resistance ChartTable B-2- Eclipse Voltage to Pressure Chart Eclipse Transducers Voltage Pressure PSIPage Alarm Name Default Definition Priority Appendix C Alarm Advisory MessagesE2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Appendix C Alarm Advisory Messages C-3 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-5 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-7 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-9 10 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Appendix C Alarm Advisory Messages C-11 12 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 RAM 14 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 ISD 2.0/2.1 CoreSense Diagnostics Copeland CoreSense E2 AlarmsNo 3PHASE PWR Other Advisories Performance Alert CoreSense DiagnosticsCoreSense Device Discus P470 CoreSense Protection K5 Ref Scroll P510 Copeland Scroll CoreSense CommP47 CoreSense Comm Throttling Range Proportional P ModeAppendix D PID Control Throttling Range on page D-1 Integral ModeWhy I Mode is Necessary Proportional Constant KpSaturation Derivative ModeI Mode Calculation Output at Setpoint for Non-Condenser D Mode CalculationHow Condenser Control Hvac PID Differs From Others Output at SetpointOutput at Setpoint for Condenser/HVAC PID Control Other PID FeaturesChanging the Output at Setpoint Output at Minimum / Output at MaximumFiltering Minimum Accumulated ErrorPage Page Medium Resolution Reuccf Page Page Refer to .1.9, Powering Appendix F TroubleshootingEchelon Network Appendix F Troubleshooting F-3 Symptom Possible Problem Solution Trip Number of Fans field?Symptom Possible Problem Solution Appendix F Troubleshooting F-7 Figured as an analog input Page Page Appendix G Revision Log Page Numerics IndexBlue R. See Cold Reset Wash mode. See Clean Mode Demand Defrost. See Defrost, demand Hot Gas Defrost. See Defrost, hot gas Tion Probe LonWorks Network. See Echelon Network Pmac Hansen probe. See Sensors, liquid level 10 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Valves