Emerson E2 operation manual Analog and Digital Combiners, Lead/Lag

Page 192

adjustment.

As the value of the reset sensor varies within the mini- mum and maximum range, an equivalent portion of the maximum setpoint adjustment will be added or subtracted from the heating or cooling setpoint. When the reset sen- sor value is directly in between the minimum and maxi- mum range values, nothing will be added or subtracted from the setpoint. Between the halfway point and the min- imum value, part of the setpoint adjustment will be sub- tracted from the setpoint. Between the halfway point and the maximum value, part of the setpoint adjustment will be added to the setpoint. An example of this is shown in Fig- ure 11-28.

RESET

SET

SENSOR

POINT

RANGE

CHANGE

MAX

MAX

RANGE

CHANGE

 

ADD

MIDPOINT

+0

 

SUBTRACT

MIN

MAX

RANGE

CHANGE

Figure 11-28- Setpoint Reset Diagram

11.17.5 Lead/Lag

A Heat/Cool application may be linked with another Heat/Cool application in what is called a “Lead/Lag” arrangement. In this arrangement, one Heat/Cool is desig- nated as the Lead loop and used as the primary space tem- perature control device. The other Heat/Cool, the Lag loop, becomes active only to support the Lead loop when it is unable to keep the space temperature within a certain proximity of the setpoint (called the setpoint delta).

Figure 11-29shows how a pair of Heat/Cool applica- tions using a Lead/Lag arrangement would operate in Cooling mode. When the temperature is in between the

setpoint and the setpoint delta, the Lead loop alone will control cooling. However, when the temperature is above the setpoint delta, the Lag loop will come on-line, and both Lead and Lag loops will work to bring the tempera- ture down.

The Lead/Lag arrangement works similarly in Heating mode, except that the setpoint delta is below the Heating setpoint, and Lead and Lag are both on when the tempera- ture is below the setpoint delta.

TEMPERATURE

 

 

 

SETPT

 

 

 

DELTA

 

 

 

SET POINT

 

 

 

LEAD AND

LEAD ON ONLY

LEAD AND

LEAD ON ONLY

LAG ON

LAG ON

 

 

 

TIME

 

 

26512037

 

 

 

Figure 11-29- Lead/Lag Arrangement

 

 

Heat/Cools in a Lead/Lag arrangement take turns act- ing as the Lead loop. The user designates the maximum amount of time a Heat/Cool will act as a Lead loop; after this duration, the current Lead loop will switch places with its Lag loop.

Lead/Lag arrangements only work when both Heat/ Cools are in Occupied mode.

Dehumidification control uses the AHU’s existing cool stages (and a separate dehumidification device such as a desiccant wheel, if available) to remove moisture from the air.

The dehumidification setpoint is placed at the 0% end of the dehumidification PID throttling range. In other words, the dehumidification output will start at 0% when the humidity is equal to the setpoint and increase to 100% when the humidity is equal to or above the setpoint plus the throttling range.

The dehumidification output percentage is used much like a heating or cooling output percentage is used in Tem- perature Control. The percentage represents the percent- age of total dehumidification capacity available to the AHU (including cool stages and other dehumidification devices).

11.18Analog and Digital Combiners

Instead of using a single output source as an applica- tion input, you may use a combination of up to sixteen input sources. To use multiple inputs, a Multiple Input cell

11-48 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013

Image 192
Contents BX HVAC, and CX Convenience Store Controllers Rev 4 5-JAN-2013Page E2 Firmware Version Page Table of Contents Inside Temperature Sensor Outside Temperature SensorInsertion Temperature Probe Product Temperature Probes Humidity Sensors and HumidistatsBoard Installation Plug-In Digital I/O Network Card P/NPlug-InFour-Channel Internal Repeater 1 I/O Board Names and Terminology MultiFlex-Plus + BoardPowering Echelon Devices Configuring Echelon DevicesConnecting Sensors to Input Boards Power Connection Input Setup in E2Setting the Time and Date 10-9 10.9 Changing Required User Access LevelsWeb Services Specifying Alarm Reporting TypesPriority Settings Using and Configuring a Setup ScreenUsing the Help Key to get Property Help Clean and Door Switches 11-711.4.9 Clean/Wash Mode 11.4.11 Fail-Safe Mode11.4.12 Wiring Setting Up An Individual Case Controller11.7.4 Temperature Control 11.7.5 Zone Temperature11.7.7 Economization Enable 11.7.2 How Zones WorkSetpoint Reset Temperature Differential TD StrategyConfiguration AlarmsService Modes 11.21.12 ConfigurationLearning Mode Accessing the Alarm Advisory Log12.10.5 Ack/Reset State 12.10.8 Acknowledging, Resetting, and Clearing Log Entries12.10.9 Facility Status Display FSD Alarms 12.10.2 Viewing the Controller Advisory LogPage Introduction E2 Refrigeration Controller RXE2 Building Controller BX E2 Convenience Store Controller CX Networking Overview 1 E2 I/O NetworkE2 Echelon Lonworks Network Interconnection With Other E2sDocumentation Overview On-Line Help System Overview Software LicensingPage Hardware Overview E2 Hardware1 E2 Main Processor Board 3 E2 Keypad LEDsPIB LEDs Status PIB LED’s StatusI/O Network Boards and Peripherals Gateway BoardMain Board Status CPU LEDs Keyboard StatusMultiFlex Boards MultiFlex 16 Input BoardMultiFlex Combination Input/ Output Boards Gateway ModelModel Description Name MultiFlex Combination Input/Output Board Top ViewMultiFlex CUB MultiFlex RTU BX and CX OnlyMultiFlex Rooftop Control Board RCB BX and CX Only MultiFlex PAK BoardMultiFlex ESR Board Hand-held Terminal P/N8RO and 8ROSMT Relay Boards RJ-11 to male RJ-11 cable6 4AO Analog Output Board 15- 4AO Analog Output Board P/N16AIe Dis 8ROe DisEC-2s 5 TD3 Temperature Display Facility Status Display FSDMounting Mounting the E2Standard Mount Recessed MountRetrofit Mounting Standard Mount Inside Rear of EnclosureMounting I/O Boards Blank FaceSingle/Double Enclosures Boards Without Enclosures Snap Track 4AO BoardEchelon Devices COM3 Internal Modem Plug-In Card P/NMultiFlex ESR 3 TD3Two-Channel and Four- Channel Repeaters Mounting Repeaters OverviewMounting the Two-Channel Repeater Mounting the Four-Channel RepeaterInside Temperature Sensor Outside Temperature SensorSensors Transducers Pressure TransducersInsertion Temperature Probe Supply and Return Air SensorsMounting Bullet and Pipe Mount Sensors Application Sensor TypeProduct Temperature Probes Humidity Sensors and HumidistatsIndoor RH Sensor Outdoor RH SensorsDewpoint Probe Light Level SensorDuct-mounted Insertion RH Probe Liquid Level Sensors Refrigerant Leak DetectorsPage E2 Hardware Setup Setting up the E2Main Processor Board EnclosurePowering the E2 Add-On E2 Peripherals3 COM3 Internal Modem Plug- In Card P/N Plug-In Digital I/O Network Card P/NLEDs E2 Installation Guide Serial Device Software Setup OverviewCOM Ports Pre-SetsE2COM# Associations Connector Page Page RS485 Network and Hardware Setup I/O Network1 I/O Board Names and Terminology Or I/O NetWiring Types MultiFlex-Plus + BoardI/O Network Structure Daisy Chains Board DesignationSetting the Baud Rate Network Noise MinimizationNetwork ID Numbers Board Numbers Setting the Terminating and Biasing Jumpers Powering the I/O BoardsWiring Types Board Installation IMC/Prodigy Rooftop Unit ControllersControl Techniques Drive 14 AWG3 XR35CX, XR75CX, XEV22 Case Controllers IPro DACEnergy Meter 3.1 XR75CX-Case DisplayCopeland Discus with CoreSense Protection Supported System TypesAdvisory and Alarms Light Commercial ThermostatThermostat Inputs Comfort Alert Descriptions Cause E2 Advisory High/Low Occ/Unocc Space Temperature Alarms Supply Sensor Fail AlarmRefrigerant Leak Detection System Rlds Conditions for Return to Normal RTN on Diag- nostic CodesDiagnostic Alarms XM Series of Case Controllers12.1 XM670 12.2 XM679BACnet BACnet OverviewBACnet Communication Master Slave Token Passing3 MS/TP Network Connection To E2 BACnet IP Internet ProtocolDiscovery Client-ServerRescan 13- Commissioning Screen16 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Multiflex Combination I/O Board Installation Guide 18 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 BACnet 20 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 16AI Installation Guide MultiFlex ESR Installation Guide BACnet 24 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Page Page Ethernet IP Configurations Hardware SpecificationsEquipment Type Specifications E2 Ethernet Peer CommunicationsEthernet Network Layouts Closed Network LayoutOpen Network Layout Open Network LayoutTroubleshooting Peer Network Tab Set Group NameEchelon Network and Hardware Setup Wiring TypeEchelon Network Cable Specifications Cable Type Emerson Retail Solutions Part NumberDevice Termination Maximum Number of Echelon DevicesWire Restrictions Installing Echelon DevicesPowering Echelon Devices Maximum Total Segment LengthConfiguring Echelon Devices Echelon Board Status Red D1 ResetRed Service LEDsTroubleshooting Connected/IO Setup Screen RX Unit ShownE2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 One pin when unterminating an E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Input and Output Setup WiringSensor Wiring Types Input Type Dip SwitchesPower Connection Input Type Dip Switches for MultiFlex 16 and 16AI BoardsSensor Input Type Wiring Dip Switch DownWall-mounted Down Down LevelInput Setup in E2 Using the Input Definitions/ Status Screen Setting Up Analog InputsApplication AssociationSensor Type Description Per Pulse onSetting Up Digital Inputs Digital Input ScreenWiring Form C Contacts 8RO, 8IO, and MultiFlex OutputsMultiFlex Relay Outputs Setting the Fail-Safe Dip Switch Relay Output Test ModeOutput Board Fail-Safe and Switch Settings Board Type VersionWiring Outputs to Points Output Setup in E2Output LED Old 8ROsUsing the Output Definitions/ Status Screen Setting Up Digital OutputsSetting Up Analog Outputs 12- Digital Output Screen13- Analog Output Screen CC-100 Case Controllers InputsPower Module Wiring Valve Cable335-3263 Pulse Valve CCB Case Controllers 335-3260 to Valve Connection InformationESR8 Boards Dis MultiFlex ESR BoardESR8 and MultiFlex ESR Valve Output Wiring Page Cleaning Out the Controller Performing a Clean OutQuick Start Logging OnSetting Number of Network Devices Boards on the I/O NetworkUnit Controllers Echelon Setting Number of Applications Customizing the Home ScreenCommon Screen Elements HeaderFunction Keys Help LineScreen Types Main MenuStatus Screens Key Function for RXSetup Screens Actions MenuActions Menu Item Description Actions Menu Options and DescriptionsSystem Configuration Menu System Configuration Menu OptionsMenu Option Description System Information Menu System Information Menu OptionsTime/Date Setup Setting the Time and DateSet Up Modem Set Up TCP/IP 17- TCP/IP AddressingSet Up Network Baud Rates 10.11.1 COM1 Serial RS232 Baud Rate10.11.2 I/O Network Baud Rate Set Up User Access User Access LevelsLevel Changing Required User Access Levels Creating a New User AccountDeleting a User Set Up I/O Network Specify Number of BoardsChecking Online Status Set Up Echelon Network Specifying Number DevicesCommissioning a Device Service Button Method How Echelon Commissioning WorksModbus Commissioning Network CommissioningCC-100’s Service Button TD3’s Service ButtonESR8’s Service Button Manual ID Entry MethodLicense Management 31- Commissioning MenuSet Up Alarming Web ServicesSpecifying Alarm Reporting Types Alarm OutputEchelon Network Alarm Annunciator Display LineSetting up an E2 to be an Alarm Annunciator Alarm Dial-OutSet Alarm Annunc field to Yes Set Up Global Data Introduction Alarm ReportingPriority Settings 10-24 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013Set Up Applications Example Setting Up an Outdoor Temperature Sen- sorUsing and Configuring a Setup Screen 10.18.1 Add/Delete an ApplicationAdd an Application Delete an ApplicationNavigating the Setup Screen Edit MenuEntering Setpoints Function Keys For Setup Function Keys for Setup ScreensIndex Tabs Help LineUsing the Help Key to get Property Help Page Software Overview Suction GroupsIntroduction Standard Suction Group ApplicationLearning Mode Hardware OverviewCircuit Load Analysis Control/Cycles ParameterTemperature Differential Strategy Input Sensor Type Wiring InstructionsCondenser Control Air Cooled CondensersCondenser Split Mode Fast RecoveryEvaporative Condensers Fan ControlStandard Circuits Evaporative CondenserRefrigeration Control Defrost ControlClean and Door Switches Clean SwitchesDefrost Termination Emergency DefrostTD3 Temperature Display WiringDoor Switches Control Link CD Case DisplayTypical Case in a Standard Circuit Case Control Circuits OverviewValve Control EEVs Liquid Pulse and Liquid StepperEEPRs Suction Stepper Thermostatic Expansion Valves TXVsOff Cycle Timed Temperature Termination Anti-Sweat ControlDemand Defrost Wait StateClean/Wash Mode Dual Temp ControlLight Control Dewpoint Input SourcesFail-Safe Mode Recoverable Sensor FailuresWalk-In Freezer Control Setting Up An Individual Case Controller Logging GroupsPossible Data Errors Data CompressionBase Log Group ClippingSetting Up Logging Logging Setup MenuLogging Group Status Screen Log ReportsLogging Group Report Application Log ReportTemperature Control Air Handling UnitsAlternate Setpoints System Log ReportSingle-Speed Fans Two-Speed FansVariable-Speed Fans Economizer Control Digital Economizer ControlAnalog Economizer Control Dehumidification ControlCurtailment Optimum Start/Stop OSSIntelligent Pre-Starts and Pre-Stops Separate Setpoints AHU Zone ControlOutput Device Wire 8RO contacts Set Fail-safe Dip Switch to Zone ControlHow Zones Work 11- Suction Group OutputsApplications That May Be Connected To Zones MultiFlex RTU BoardMultiFlex RCB Board MultiFlex RCB-P BoardZone Temperature Economization EnableAHUs Effect of Enabling Economization Zone Humidity Input Effect of Enabling DehumidificationMultiFlex RTUs and RCBs 17- Diagram of Pre-Start and Pre-Stop Operation MultiFlex CUB Board Losing Contact With Zone ApplicationsStand-Alone MultiFlex RTUs MultiFlex RTU/ARTC and AHU Zone AssociationMultiFlex PAK Board Lighting SchedulesFunctions of the Lighting Schedule Application Control Method SelectStandard Control Light Level Interface CellAlternate Control Schedule Interface CellMulti-Logic Combiner Basic Schedule Cell Min ON/OFF CellProof Cell Offset Solar ControlDemand Control Output Light DimmingIntroduction to Demand Limit Control Demand MonitoringLoad Shedding Shedding LevelsPriority Levels DefinitionRotational Shed Last ShedOther Notes About Priority Levels Mode 1 KW Input Is Greater Than Setpoint Mode 3 Integral Error Approaching ZeroHow Demand Control Uses Load Shedding Power Monitoring Input SettingsSensor Control Analog Sensor ControlDigital Sensor Control Logical CombinationControl Cells Diagram Loop/Sequence Control Cell DescriptionsOutput Cells Select CellOutput Cell Descriptions Time Scheduling and Holidays How Schedules WorkPWM Cell EventsPower Monitoring Holiday SchedulesTemporary Schedule Events OverlappingLogging HourlyDaily MonthlyAnti-Sweat Setup Heat/Cool ControlHow Anti-Sweat Works Setpoint Reset Unoccupied HysteresisAnalog and Digital Combiners Lead/LagTemperature Differential TD Strategy ConfigurationTD Control TD Control Fail-SafesAlarms Pulse AccumulationOutputs Accumulator Reset Types Irrigation ControlHigh Trip Zones and CyclesCycle Scheduling Zone InhibitZone Bypass Inputs Service Modes Flow Sensor-Related TestsTwo Speed Fan Control Flexible Combiner Modular Chiller Control MCCLearning Mode Compressor ControlBoiler Bypass Valve ControlDigital Scroll Compressor Variable Frequency Drive CompressorRMS Asset RMS ScaleLog Information Device ConstraintsLogged Changes Unlogged ChangesPage Page Operator’s Guide to Using the E2 E2 Home ScreenBX Home Screen RX Home ScreenLogging On and Access Levels CX Home ScreenSystem Configuration Menu Toggling Full OptionsNavigation MenusPress System Configuration Press System Information System Information MenuScreen Types Actions MenuSummary Screens Status ScreensSetup Screens Index TabsHeader Icons E2 Keypad CursorTab Key Enter KeyLog In/Out Key Four Directional Arrow KeysUp/Page Down Keys Ctrl Page Up/Ctrl Page Down KeysManual Defrost and Clean Mode Customizing the Home ScreenList menu and choose End Manual Mode OverridesChecking Boards Online Checking Status Screens Alarms Accessing the Alarm Advi Sory LogViewing the Controller Advisory Log Date and Time12.10.5 Ack/Reset State Alarm StatesArea Ctrl Application Property Advisory MessageResetting ClearingFacility Status Display FSD Alarms Viewing Logs and GraphsLocating Logged Inputs Outputs Home/Status ScreensSetup Screens Setting Up Input and Output PointersLog View Graph View Zooming In and OutMultiple Languages Appendix a Case Type Defaults High Alarm, Low Alarm, and DelayDefrost Type Hdbx Table B-1- Temp Sensor Temperature/Resistance Chart Table B-2- Eclipse Voltage to Pressure ChartEclipse Transducers Voltage Pressure PSI 100 lb 200 lb 500 lb XducerPage Appendix C Alarm Advisory Messages Alarm Name Default Definition PriorityE2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Appendix C Alarm Advisory Messages C-3 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-5 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-7 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-9 10 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Appendix C Alarm Advisory Messages C-11 12 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 RAM 14 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Copeland CoreSense E2 Alarms ISD 2.0/2.1 CoreSense DiagnosticsNo 3PHASE PWR Performance Alert CoreSense Diagnostics CoreSense DeviceOther Advisories Discus P470 CoreSense Protection K5 Ref Scroll P510 Copeland Scroll CoreSense CommP47 CoreSense Comm Proportional P Mode Appendix D PID ControlThrottling Range Integral Mode Why I Mode is NecessaryProportional Constant Kp Throttling Range on page D-1Derivative Mode I Mode CalculationSaturation D Mode Calculation How Condenser Control Hvac PID Differs From OthersOutput at Setpoint Output at Setpoint for Non-CondenserOther PID Features Changing the Output at SetpointOutput at Minimum / Output at Maximum Output at Setpoint for Condenser/HVAC PID ControlMinimum Accumulated Error FilteringPage Page Medium Resolution Reuccf Page Page Appendix F Troubleshooting Refer to .1.9, PoweringEchelon Network Appendix F Troubleshooting F-3 Symptom Possible Problem Solution Number of Fans field? TripSymptom Possible Problem Solution Appendix F Troubleshooting F-7 Figured as an analog input Page Page Appendix G Revision Log Page Index NumericsBlue R. See Cold Reset Wash mode. See Clean Mode Demand Defrost. See Defrost, demand Hot Gas Defrost. See Defrost, hot gas Tion Probe LonWorks Network. See Echelon Network Pmac Hansen probe. See Sensors, liquid level 10 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Valves