Emerson E2 Set Up Echelon Network, Specifying Number Devices, Commissioning a Device

Page 130

work Status screen (See Figure 10-24). The Network Summary screen displays information such as the Subnet and Node addresses for each board, and the status of Eche- lon and I/O boards.

To get to the Network Summary Screen:

1.Press to open the Main Menu

2.Press (System Configuration)

3.Press (Network Setup)

4.Press (Network Summary)

From the Network Summary screen you can see the total (E2) devices online or offline, status, setup screens, change board or controller names, configure and commis- sion devices, delete a device, and view detailed status screens of controllers.

After determining if a board is offline, turn to Appen- dix E: Troubleshooting.

10.14Set Up Echelon Network

10.14.1Specifying Number of

Devices

To specify the number of devices on the Echelon Net- work, navigate to the Connected I/O screen:

1.Press to open the Main Menu

2.Press (System Configuration)

3.Press (Network Setup)

4.Press (Connected I/O Boards & Controllers)

Figure 10-25- Connected I/O Screen (RX version shown)

After logging in for the first time, the Connected I/O screen will ask you to specify how many of each type of device will be connected to the E2 you are currently pro- gramming. (Options will vary depending on the type of controller used.)

Unit Number (Echelon Subnet) Each E2 on the Echelon Network must have a different unit number. This can be any number from 1 to 255, but each E2’s number must be unique. No two E2s on the network may have the same unit number.

Enter this number in the Unit Number field. It is rec- ommended you number the first E2 “1” and number the other E2s on the network sequentially (2, 3, 4, etc.).

Unit Name Type a name for the E2 in the Unit Name field.

Unit Controllers (Echelon)

Liquid Ctrls (CC100P/CC100LS) Enter the com- bined number of pulse valve case controllers (CC100Ps) and liquid-side stepper valve case con- trollers (CC100LSs) in this field.

Suction Controllers (CC100H) Enter the num- ber of suction stepper case controllers (CC100Hs) in this field.

Circuit Suction (CS100) Enter the number of suc- tion lineup circuit controllers (CS100s) in this field.

ESR8 Line Up Boards Enter the number of ESR suction lineup circuit boards (SR100s) in this field.

TD3 Temperature Displays Enter the number of TD3 temperature display units in this field.

EC2- 29x Case Controllers Enter the number of EC2-29x refrigerated case controllers in this field.

EC2-39x Case Controllers Enter the number of EC2-39x refrigerated case controllers in this field.

Echelon 16AI Enter the number of 16AIe analog input boards in this field.

Echelon 8RO Enter the number of 8ROe analog input boards in this field.

10.14.2 Commissioning a Device

Once all records have been created and defined for all devices on the Echelon Network, they must be “commis- sioned.” Commissioning is necessary for the E2 to identify and establish communications with all devices on the net- work.

To start commissioning, open the Network Summary screen:

1.Press to open the Main Menu

10-16 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013

Image 130
Contents BX HVAC, and CX Convenience Store Controllers Rev 4 5-JAN-2013Page E2 Firmware Version Page Table of Contents Insertion Temperature Probe Inside Temperature SensorOutside Temperature Sensor Product Temperature Probes Humidity Sensors and HumidistatsPlug-InFour-Channel Internal Repeater Board InstallationPlug-In Digital I/O Network Card P/N 1 I/O Board Names and Terminology MultiFlex-Plus + BoardConnecting Sensors to Input Boards Powering Echelon DevicesConfiguring Echelon Devices Power Connection Input Setup in E2Web Services Setting the Time and Date 10-9 10.9Changing Required User Access Levels Specifying Alarm Reporting TypesUsing the Help Key to get Property Help Priority SettingsUsing and Configuring a Setup Screen Clean and Door Switches 11-711.4.12 Wiring 11.4.9 Clean/Wash Mode11.4.11 Fail-Safe Mode Setting Up An Individual Case Controller11.7.7 Economization Enable 11.7.4 Temperature Control11.7.5 Zone Temperature 11.7.2 How Zones WorkConfiguration Setpoint ResetTemperature Differential TD Strategy AlarmsLearning Mode Service Modes11.21.12 Configuration Accessing the Alarm Advisory Log12.10.9 Facility Status Display FSD Alarms 12.10.5 Ack/Reset State12.10.8 Acknowledging, Resetting, and Clearing Log Entries 12.10.2 Viewing the Controller Advisory LogPage Introduction E2 Refrigeration Controller RXE2 Building Controller BX E2 Convenience Store Controller CX Networking Overview 1 E2 I/O NetworkE2 Echelon Lonworks Network Interconnection With Other E2sDocumentation Overview On-Line Help System Overview Software LicensingPage Hardware Overview E2 HardwarePIB LEDs Status 1 E2 Main Processor Board 3 E2 KeypadLEDs PIB LED’s StatusMain Board Status CPU LEDs I/O Network Boards and PeripheralsGateway Board Keyboard StatusMultiFlex Combination Input/ Output Boards MultiFlex BoardsMultiFlex 16 Input Board Gateway ModelModel Description Name MultiFlex Combination Input/Output Board Top ViewMultiFlex Rooftop Control Board RCB BX and CX Only MultiFlex CUBMultiFlex RTU BX and CX Only MultiFlex PAK BoardMultiFlex ESR Board Hand-held Terminal P/N8RO and 8ROSMT Relay Boards RJ-11 to male RJ-11 cable6 4AO Analog Output Board 15- 4AO Analog Output Board P/N16AIe Dis 8ROe DisEC-2s 5 TD3 Temperature Display Facility Status Display FSDStandard Mount MountingMounting the E2 Recessed MountRetrofit Mounting Standard Mount Inside Rear of EnclosureBlank Face Mounting I/O BoardsSingle/Double Enclosures Boards Without Enclosures Snap Track 4AO BoardMultiFlex ESR Echelon DevicesCOM3 Internal Modem Plug-In Card P/N 3 TD3Mounting the Two-Channel Repeater Two-Channel and Four- Channel RepeatersMounting Repeaters Overview Mounting the Four-Channel RepeaterSensors Transducers Inside Temperature SensorOutside Temperature Sensor Pressure TransducersMounting Bullet and Pipe Mount Sensors Insertion Temperature ProbeSupply and Return Air Sensors Application Sensor TypeIndoor RH Sensor Product Temperature ProbesHumidity Sensors and Humidistats Outdoor RH SensorsLight Level Sensor Dewpoint ProbeDuct-mounted Insertion RH Probe Liquid Level Sensors Refrigerant Leak DetectorsPage Main Processor Board E2 Hardware SetupSetting up the E2 EnclosurePowering the E2 Add-On E2 PeripheralsPlug-In Digital I/O Network Card P/N 3 COM3 Internal Modem Plug- In Card P/NLEDs E2 Installation Guide COM Ports Serial Device Software SetupOverview Pre-SetsE2COM# Associations Connector Page Page 1 I/O Board Names and Terminology RS485 Network and Hardware SetupI/O Network Or I/O NetI/O Network Structure Daisy Chains Wiring TypesMultiFlex-Plus + Board Board DesignationNetwork Noise Minimization Setting the Baud RateNetwork ID Numbers Board Numbers Setting the Terminating and Biasing Jumpers Powering the I/O BoardsWiring Types Control Techniques Drive Board InstallationIMC/Prodigy Rooftop Unit Controllers 14 AWGEnergy Meter 3 XR35CX, XR75CX, XEV22 Case ControllersIPro DAC 3.1 XR75CX-Case DisplayCopeland Discus with CoreSense Protection Supported System TypesLight Commercial Thermostat Advisory and AlarmsThermostat Inputs Comfort Alert Descriptions Cause E2 Advisory Refrigerant Leak Detection System Rlds High/Low Occ/Unocc Space Temperature AlarmsSupply Sensor Fail Alarm Conditions for Return to Normal RTN on Diag- nostic Codes12.1 XM670 Diagnostic AlarmsXM Series of Case Controllers 12.2 XM679BACnet Communication BACnetBACnet Overview Master Slave Token PassingDiscovery 3 MS/TP Network Connection To E2BACnet IP Internet Protocol Client-ServerRescan 13- Commissioning Screen16 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Multiflex Combination I/O Board Installation Guide 18 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 BACnet 20 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 16AI Installation Guide MultiFlex ESR Installation Guide BACnet 24 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Page Page Equipment Type Specifications Ethernet IP ConfigurationsHardware Specifications E2 Ethernet Peer CommunicationsEthernet Network Layouts Closed Network LayoutOpen Network Layout Open Network LayoutTroubleshooting Peer Network Tab Set Group NameEchelon Network Cable Specifications Echelon Network and Hardware SetupWiring Type Cable Type Emerson Retail Solutions Part NumberDevice Termination Maximum Number of Echelon DevicesPowering Echelon Devices Wire RestrictionsInstalling Echelon Devices Maximum Total Segment LengthRed Service Configuring Echelon DevicesEchelon Board Status Red D1 Reset LEDsTroubleshooting Connected/IO Setup Screen RX Unit ShownE2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 One pin when unterminating an E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Sensor Wiring Types Input and Output SetupWiring Input Type Dip SwitchesPower Connection Input Type Dip Switches for MultiFlex 16 and 16AI BoardsSensor Input Type Wiring Dip Switch DownWall-mounted Down Down LevelInput Setup in E2 Application Using the Input Definitions/ Status ScreenSetting Up Analog Inputs AssociationSensor Type Description Per Pulse onSetting Up Digital Inputs Digital Input Screen8RO, 8IO, and MultiFlex Outputs Wiring Form C ContactsMultiFlex Relay Outputs Output Board Fail-Safe and Switch Settings Setting the Fail-Safe Dip SwitchRelay Output Test Mode Board Type VersionOutput LED Wiring Outputs to PointsOutput Setup in E2 Old 8ROsUsing the Output Definitions/ Status Screen Setting Up Digital OutputsSetting Up Analog Outputs 12- Digital Output Screen13- Analog Output Screen CC-100 Case Controllers InputsValve Cable Power Module Wiring335-3263 Pulse Valve ESR8 Boards Dis CCB Case Controllers335-3260 to Valve Connection Information MultiFlex ESR BoardESR8 and MultiFlex ESR Valve Output Wiring Page Quick Start Cleaning Out the ControllerPerforming a Clean Out Logging OnBoards on the I/O Network Setting Number of Network DevicesUnit Controllers Echelon Setting Number of Applications Customizing the Home ScreenFunction Keys Common Screen ElementsHeader Help LineStatus Screens Screen TypesMain Menu Key Function for RXActions Menu Item Description Setup ScreensActions Menu Actions Menu Options and DescriptionsSystem Configuration Menu Options System Configuration MenuMenu Option Description System Information Menu System Information Menu OptionsTime/Date Setup Setting the Time and DateSet Up Modem Set Up TCP/IP 17- TCP/IP Addressing10.11.1 COM1 Serial RS232 Baud Rate Set Up Network Baud Rates10.11.2 I/O Network Baud Rate User Access Levels Set Up User AccessLevel Creating a New User Account Changing Required User Access LevelsDeleting a User Specify Number of Boards Set Up I/O NetworkChecking Online Status Specifying Number Devices Set Up Echelon NetworkCommissioning a Device Modbus Commissioning Service Button MethodHow Echelon Commissioning Works Network CommissioningESR8’s Service Button CC-100’s Service ButtonTD3’s Service Button Manual ID Entry MethodLicense Management 31- Commissioning MenuSet Up Alarming Web ServicesEchelon Network Alarm Annunciator Specifying Alarm Reporting TypesAlarm Output Display LineAlarm Dial-Out Setting up an E2 to be an Alarm AnnunciatorSet Alarm Annunc field to Yes Set Up Global Data Introduction Alarm ReportingPriority Settings 10-24 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013Set Up Applications Example Setting Up an Outdoor Temperature Sen- sorAdd an Application Using and Configuring a Setup Screen10.18.1 Add/Delete an Application Delete an ApplicationEdit Menu Navigating the Setup ScreenEntering Setpoints Index Tabs Function Keys For SetupFunction Keys for Setup Screens Help LineUsing the Help Key to get Property Help Page Introduction Software OverviewSuction Groups Standard Suction Group ApplicationCircuit Load Analysis Learning ModeHardware Overview Control/Cycles ParameterCondenser Control Temperature Differential StrategyInput Sensor Type Wiring Instructions Air Cooled CondensersEvaporative Condensers Condenser Split ModeFast Recovery Fan ControlStandard Circuits Evaporative CondenserRefrigeration Control Defrost ControlDefrost Termination Clean and Door SwitchesClean Switches Emergency DefrostDoor Switches TD3 Temperature DisplayWiring Control Link CD Case DisplayTypical Case in a Standard Circuit Case Control Circuits OverviewValve Control EEVs Liquid Pulse and Liquid StepperThermostatic Expansion Valves TXVs EEPRs Suction StepperOff Cycle Timed Demand Defrost Temperature TerminationAnti-Sweat Control Wait StateLight Control Clean/Wash ModeDual Temp Control Dewpoint Input SourcesRecoverable Sensor Failures Fail-Safe ModeWalk-In Freezer Control Setting Up An Individual Case Controller Logging GroupsBase Log Group Possible Data ErrorsData Compression ClippingSetting Up Logging Logging Setup MenuLogging Group Report Logging Group Status ScreenLog Reports Application Log ReportAlternate Setpoints Temperature ControlAir Handling Units System Log ReportTwo-Speed Fans Single-Speed FansVariable-Speed Fans Analog Economizer Control Economizer ControlDigital Economizer Control Dehumidification ControlOptimum Start/Stop OSS CurtailmentIntelligent Pre-Starts and Pre-Stops Separate Setpoints AHU Zone ControlHow Zones Work Output Device Wire 8RO contacts Set Fail-safe Dip Switch toZone Control 11- Suction Group OutputsMultiFlex RCB Board Applications That May Be Connected To ZonesMultiFlex RTU Board MultiFlex RCB-P BoardEconomization Enable Zone TemperatureAHUs Zone Humidity Input Effect of Enabling Dehumidification Effect of Enabling EconomizationMultiFlex RTUs and RCBs 17- Diagram of Pre-Start and Pre-Stop Operation Stand-Alone MultiFlex RTUs MultiFlex CUB BoardLosing Contact With Zone Applications MultiFlex RTU/ARTC and AHU Zone AssociationMultiFlex PAK Board Lighting SchedulesStandard Control Functions of the Lighting Schedule ApplicationControl Method Select Light Level Interface CellSchedule Interface Cell Alternate ControlMulti-Logic Combiner Proof Cell Basic Schedule CellMin ON/OFF Cell Offset Solar ControlIntroduction to Demand Limit Control Demand ControlOutput Light Dimming Demand MonitoringPriority Levels Load SheddingShedding Levels DefinitionLast Shed Rotational ShedOther Notes About Priority Levels Mode 3 Integral Error Approaching Zero Mode 1 KW Input Is Greater Than SetpointHow Demand Control Uses Load Shedding Sensor Control Power Monitoring InputSettings Analog Sensor ControlLogical Combination Digital Sensor ControlControl Cells Output Cells DiagramLoop/Sequence Control Cell Descriptions Select CellOutput Cell Descriptions PWM Cell Time Scheduling and HolidaysHow Schedules Work EventsTemporary Schedule Events Power MonitoringHoliday Schedules OverlappingDaily LoggingHourly MonthlyHeat/Cool Control Anti-Sweat SetupHow Anti-Sweat Works Setpoint Reset Unoccupied HysteresisAnalog and Digital Combiners Lead/LagTD Control Temperature Differential TD StrategyConfiguration TD Control Fail-SafesPulse Accumulation AlarmsOutputs High Trip Accumulator Reset TypesIrrigation Control Zones and CyclesZone Inhibit Cycle SchedulingZone Bypass Inputs Flow Sensor-Related Tests Service ModesTwo Speed Fan Control Flexible Combiner Modular Chiller Control MCCLearning Mode Compressor ControlDigital Scroll Compressor BoilerBypass Valve Control Variable Frequency Drive CompressorLog Information RMS AssetRMS Scale Device ConstraintsLogged Changes Unlogged ChangesPage Page BX Home Screen Operator’s Guide to Using the E2E2 Home Screen RX Home ScreenLogging On and Access Levels CX Home ScreenNavigation System Configuration MenuToggling Full Options MenusPress System Configuration Press System Information System Information MenuSummary Screens Screen TypesActions Menu Status ScreensIndex Tabs Setup ScreensHeader Icons Tab Key E2 KeypadCursor Enter KeyUp/Page Down Keys Log In/Out KeyFour Directional Arrow Keys Ctrl Page Up/Ctrl Page Down KeysManual Defrost and Clean Mode Customizing the Home ScreenList menu and choose End Manual Mode OverridesChecking Boards Online Checking Status Screens Viewing the Controller Advisory Log AlarmsAccessing the Alarm Advi Sory Log Date and TimeArea Ctrl Application Property 12.10.5 Ack/Reset StateAlarm States Advisory MessageResetting ClearingLocating Logged Inputs Outputs Facility Status Display FSD AlarmsViewing Logs and Graphs Home/Status ScreensSetting Up Input and Output Pointers Setup ScreensLog View Graph View Zooming In and OutMultiple Languages High Alarm, Low Alarm, and Delay Appendix a Case Type DefaultsDefrost Type Hdbx Eclipse Transducers Voltage Pressure PSI Table B-1- Temp Sensor Temperature/Resistance ChartTable B-2- Eclipse Voltage to Pressure Chart 100 lb 200 lb 500 lb XducerPage Appendix C Alarm Advisory Messages Alarm Name Default Definition PriorityE2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Appendix C Alarm Advisory Messages C-3 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-5 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-7 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-9 10 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Appendix C Alarm Advisory Messages C-11 12 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 RAM 14 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Copeland CoreSense E2 Alarms ISD 2.0/2.1 CoreSense DiagnosticsNo 3PHASE PWR CoreSense Device Performance Alert CoreSense DiagnosticsOther Advisories Discus P470 CoreSense Protection K5 Ref Scroll P510 Copeland Scroll CoreSense CommP47 CoreSense Comm Appendix D PID Control Proportional P ModeThrottling Range Proportional Constant Kp Integral ModeWhy I Mode is Necessary Throttling Range on page D-1I Mode Calculation Derivative ModeSaturation Output at Setpoint D Mode CalculationHow Condenser Control Hvac PID Differs From Others Output at Setpoint for Non-CondenserOutput at Minimum / Output at Maximum Other PID FeaturesChanging the Output at Setpoint Output at Setpoint for Condenser/HVAC PID ControlMinimum Accumulated Error FilteringPage Page Medium Resolution Reuccf Page Page Appendix F Troubleshooting Refer to .1.9, PoweringEchelon Network Appendix F Troubleshooting F-3 Symptom Possible Problem Solution Number of Fans field? TripSymptom Possible Problem Solution Appendix F Troubleshooting F-7 Figured as an analog input Page Page Appendix G Revision Log Page Index NumericsBlue R. See Cold Reset Wash mode. See Clean Mode Demand Defrost. See Defrost, demand Hot Gas Defrost. See Defrost, hot gas Tion Probe LonWorks Network. See Echelon Network Pmac Hansen probe. See Sensors, liquid level 10 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Valves