Emerson E2 Integral Mode, Proportional Constant Kp, Why I Mode is Necessary, Proportional Offset

Page 248

Throttling Range on page D-1.

.

THROTTLING

OUTPUT AT

RANGE

SETPOINT

 

 

(shown here as 50%)

 

 

 

 

 

 

 

 

 

 

 

 

0% 100%

CONTROL INPUT

26512028

Figure D-1- Throttling Range

Example 1: Suppose a Case Control application has a throttling range of 10 degrees. Also, for simplicity’s sake, assume only the Proportional Mode is active and the pro- portional constant Kp is one. The system begins with a 0% output at the bottom of the Throttling Range and with an input value of 24°F. Because the throttling range is 10 degrees, Proportional Mode will gradually add 100% to the output percentage as the input changes to 34° over time.

Suppose, for example, the input increases by one degree every time an update occurs. The following adjust- ment would then likewise occur after every update:

“P” mode adj. = (1.0)(1 degree) / 10 degrees = 0.1 = 10%

After 10 updates, the input value would be 34°F and the output would be 100%. The same would happen if it were five updates at two degrees each or one hundred updates at 0.1 degrees each. In every case, the tempera- ture travels a total of 10 degrees, and because the throt- tling range is also 10 degrees, the output travels from 0% to 100% proportionally.

Higher Throttling Range values will result in a wider 0-100% range, and therefore will result in smaller reaction to changes in input values.

Proportional Constant (Kp)

The Proportional Constant is simply a multiplier that can be used to fine-tune the size of the Proportional Mode adjustment. Raising the value of Kp results in a greater reaction to input value changes, while lowering it results in a smaller reaction.

Changing Kp is essentially the same thing as changing the value of the throttling range. For example, having a TR of 10 and a Kp of 2 is the same as having a TR of 5 and a Kp of 1. Mathematically speaking, the effective propor- tional range is calculated by dividing the Throttling Range by Kp.

If Proportional Mode is functioning incorrectly in your system, it may be more appropriate for you to change the Throttling Range value to a more appropriate value. Kp is designed as a fine-tuning constant (for example, it might be used to speed up reaction slightly by setting it to 1.04, or to slow down reaction by setting it to 0.98).

Integral Mode

The Integral Mode (also called “I” Mode) is the por- tion of PID control that seeks to make the input equal to the setpoint. When an update occurs, the Integral Mode measures the difference between the current input value and the setpoint. The size of this difference determines Integral Mode’s output percentage adjustment.

Why “I” Mode is Necessary

Though Proportional Mode handles the majority of the workload during PID control, there are two major short- comings that make the “I” Mode necessary.

Proportional Offset

Proportional Mode, if left to operate all by itself, is only capable of stopping the error from changing. When the error is not changing, neither is the “P” portion of the output. This means the system may reach stability at any value, regardless of whether it is above or below the set- point (see Figure D-2). Proportional Mode alone has no mechanism that can bring the error to zero after stability has occurred. The “I” Mode is necessary in order to move the input in the direction of the setpoint.

D-2 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013

Image 248
Contents BX HVAC, and CX Convenience Store Controllers Rev 4 5-JAN-2013Page E2 Firmware Version Page Table of Contents Inside Temperature Sensor Outside Temperature SensorInsertion Temperature Probe Product Temperature Probes Humidity Sensors and HumidistatsBoard Installation Plug-In Digital I/O Network Card P/NPlug-InFour-Channel Internal Repeater 1 I/O Board Names and Terminology MultiFlex-Plus + BoardPowering Echelon Devices Configuring Echelon DevicesConnecting Sensors to Input Boards Power Connection Input Setup in E2Setting the Time and Date 10-9 10.9 Changing Required User Access LevelsWeb Services Specifying Alarm Reporting TypesPriority Settings Using and Configuring a Setup ScreenUsing the Help Key to get Property Help Clean and Door Switches 11-711.4.9 Clean/Wash Mode 11.4.11 Fail-Safe Mode11.4.12 Wiring Setting Up An Individual Case Controller11.7.4 Temperature Control 11.7.5 Zone Temperature11.7.7 Economization Enable 11.7.2 How Zones WorkSetpoint Reset Temperature Differential TD StrategyConfiguration AlarmsService Modes 11.21.12 ConfigurationLearning Mode Accessing the Alarm Advisory Log12.10.5 Ack/Reset State 12.10.8 Acknowledging, Resetting, and Clearing Log Entries12.10.9 Facility Status Display FSD Alarms 12.10.2 Viewing the Controller Advisory LogPage Introduction E2 Refrigeration Controller RXE2 Building Controller BX E2 Convenience Store Controller CX Networking Overview 1 E2 I/O NetworkE2 Echelon Lonworks Network Interconnection With Other E2sDocumentation Overview On-Line Help System Overview Software LicensingPage Hardware Overview E2 Hardware1 E2 Main Processor Board 3 E2 Keypad LEDsPIB LEDs Status PIB LED’s StatusI/O Network Boards and Peripherals Gateway BoardMain Board Status CPU LEDs Keyboard StatusMultiFlex Boards MultiFlex 16 Input BoardMultiFlex Combination Input/ Output Boards Gateway ModelModel Description Name MultiFlex Combination Input/Output Board Top ViewMultiFlex CUB MultiFlex RTU BX and CX OnlyMultiFlex Rooftop Control Board RCB BX and CX Only MultiFlex PAK BoardMultiFlex ESR Board Hand-held Terminal P/N8RO and 8ROSMT Relay Boards RJ-11 to male RJ-11 cable6 4AO Analog Output Board 15- 4AO Analog Output Board P/N16AIe Dis 8ROe DisEC-2s 5 TD3 Temperature Display Facility Status Display FSDMounting Mounting the E2Standard Mount Recessed MountRetrofit Mounting Standard Mount Inside Rear of EnclosureSingle/Double Enclosures Mounting I/O BoardsBlank Face Boards Without Enclosures Snap Track 4AO BoardEchelon Devices COM3 Internal Modem Plug-In Card P/NMultiFlex ESR 3 TD3Two-Channel and Four- Channel Repeaters Mounting Repeaters OverviewMounting the Two-Channel Repeater Mounting the Four-Channel RepeaterInside Temperature Sensor Outside Temperature SensorSensors Transducers Pressure TransducersInsertion Temperature Probe Supply and Return Air SensorsMounting Bullet and Pipe Mount Sensors Application Sensor TypeProduct Temperature Probes Humidity Sensors and HumidistatsIndoor RH Sensor Outdoor RH SensorsDuct-mounted Insertion RH Probe Dewpoint ProbeLight Level Sensor Liquid Level Sensors Refrigerant Leak DetectorsPage E2 Hardware Setup Setting up the E2Main Processor Board EnclosurePowering the E2 Add-On E2 PeripheralsLEDs 3 COM3 Internal Modem Plug- In Card P/NPlug-In Digital I/O Network Card P/N E2 Installation Guide Serial Device Software Setup OverviewCOM Ports Pre-SetsE2COM# Associations Connector Page Page RS485 Network and Hardware Setup I/O Network1 I/O Board Names and Terminology Or I/O NetWiring Types MultiFlex-Plus + BoardI/O Network Structure Daisy Chains Board DesignationNetwork ID Numbers Board Numbers Setting the Baud RateNetwork Noise Minimization Setting the Terminating and Biasing Jumpers Powering the I/O BoardsWiring Types Board Installation IMC/Prodigy Rooftop Unit ControllersControl Techniques Drive 14 AWG3 XR35CX, XR75CX, XEV22 Case Controllers IPro DACEnergy Meter 3.1 XR75CX-Case DisplayCopeland Discus with CoreSense Protection Supported System TypesThermostat Inputs Advisory and AlarmsLight Commercial Thermostat Comfort Alert Descriptions Cause E2 Advisory High/Low Occ/Unocc Space Temperature Alarms Supply Sensor Fail AlarmRefrigerant Leak Detection System Rlds Conditions for Return to Normal RTN on Diag- nostic CodesDiagnostic Alarms XM Series of Case Controllers12.1 XM670 12.2 XM679BACnet BACnet OverviewBACnet Communication Master Slave Token Passing3 MS/TP Network Connection To E2 BACnet IP Internet ProtocolDiscovery Client-ServerRescan 13- Commissioning Screen16 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Multiflex Combination I/O Board Installation Guide 18 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 BACnet 20 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 16AI Installation Guide MultiFlex ESR Installation Guide BACnet 24 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Page Page Ethernet IP Configurations Hardware SpecificationsEquipment Type Specifications E2 Ethernet Peer CommunicationsEthernet Network Layouts Closed Network LayoutOpen Network Layout Open Network LayoutTroubleshooting Peer Network Tab Set Group NameEchelon Network and Hardware Setup Wiring TypeEchelon Network Cable Specifications Cable Type Emerson Retail Solutions Part NumberDevice Termination Maximum Number of Echelon DevicesWire Restrictions Installing Echelon DevicesPowering Echelon Devices Maximum Total Segment LengthConfiguring Echelon Devices Echelon Board Status Red D1 ResetRed Service LEDsTroubleshooting Connected/IO Setup Screen RX Unit ShownE2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 One pin when unterminating an E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Input and Output Setup WiringSensor Wiring Types Input Type Dip SwitchesPower Connection Input Type Dip Switches for MultiFlex 16 and 16AI BoardsSensor Input Type Wiring Dip Switch DownWall-mounted Down Down LevelInput Setup in E2 Using the Input Definitions/ Status Screen Setting Up Analog InputsApplication AssociationSensor Type Description Per Pulse onSetting Up Digital Inputs Digital Input ScreenMultiFlex Relay Outputs Wiring Form C Contacts8RO, 8IO, and MultiFlex Outputs Setting the Fail-Safe Dip Switch Relay Output Test ModeOutput Board Fail-Safe and Switch Settings Board Type VersionWiring Outputs to Points Output Setup in E2Output LED Old 8ROsUsing the Output Definitions/ Status Screen Setting Up Digital OutputsSetting Up Analog Outputs 12- Digital Output Screen13- Analog Output Screen CC-100 Case Controllers Inputs335-3263 Pulse Valve Power Module WiringValve Cable CCB Case Controllers 335-3260 to Valve Connection InformationESR8 Boards Dis MultiFlex ESR BoardESR8 and MultiFlex ESR Valve Output Wiring Page Cleaning Out the Controller Performing a Clean OutQuick Start Logging OnUnit Controllers Echelon Setting Number of Network DevicesBoards on the I/O Network Setting Number of Applications Customizing the Home ScreenCommon Screen Elements HeaderFunction Keys Help LineScreen Types Main MenuStatus Screens Key Function for RXSetup Screens Actions MenuActions Menu Item Description Actions Menu Options and DescriptionsMenu Option Description System Configuration MenuSystem Configuration Menu Options System Information Menu System Information Menu OptionsTime/Date Setup Setting the Time and DateSet Up Modem Set Up TCP/IP 17- TCP/IP Addressing10.11.2 I/O Network Baud Rate Set Up Network Baud Rates10.11.1 COM1 Serial RS232 Baud Rate Level Set Up User AccessUser Access Levels Deleting a User Changing Required User Access LevelsCreating a New User Account Checking Online Status Set Up I/O NetworkSpecify Number of Boards Commissioning a Device Set Up Echelon NetworkSpecifying Number Devices Service Button Method How Echelon Commissioning WorksModbus Commissioning Network CommissioningCC-100’s Service Button TD3’s Service ButtonESR8’s Service Button Manual ID Entry MethodLicense Management 31- Commissioning MenuSet Up Alarming Web ServicesSpecifying Alarm Reporting Types Alarm OutputEchelon Network Alarm Annunciator Display LineSet Alarm Annunc field to Yes Setting up an E2 to be an Alarm AnnunciatorAlarm Dial-Out Set Up Global Data Introduction Alarm ReportingPriority Settings 10-24 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013Set Up Applications Example Setting Up an Outdoor Temperature Sen- sorUsing and Configuring a Setup Screen 10.18.1 Add/Delete an ApplicationAdd an Application Delete an ApplicationEntering Setpoints Navigating the Setup ScreenEdit Menu Function Keys For Setup Function Keys for Setup ScreensIndex Tabs Help LineUsing the Help Key to get Property Help Page Software Overview Suction GroupsIntroduction Standard Suction Group ApplicationLearning Mode Hardware OverviewCircuit Load Analysis Control/Cycles ParameterTemperature Differential Strategy Input Sensor Type Wiring InstructionsCondenser Control Air Cooled CondensersCondenser Split Mode Fast RecoveryEvaporative Condensers Fan ControlStandard Circuits Evaporative CondenserRefrigeration Control Defrost ControlClean and Door Switches Clean SwitchesDefrost Termination Emergency DefrostTD3 Temperature Display WiringDoor Switches Control Link CD Case DisplayTypical Case in a Standard Circuit Case Control Circuits OverviewValve Control EEVs Liquid Pulse and Liquid StepperOff Cycle Timed EEPRs Suction StepperThermostatic Expansion Valves TXVs Temperature Termination Anti-Sweat ControlDemand Defrost Wait StateClean/Wash Mode Dual Temp ControlLight Control Dewpoint Input SourcesWalk-In Freezer Control Fail-Safe ModeRecoverable Sensor Failures Setting Up An Individual Case Controller Logging GroupsPossible Data Errors Data CompressionBase Log Group ClippingSetting Up Logging Logging Setup MenuLogging Group Status Screen Log ReportsLogging Group Report Application Log ReportTemperature Control Air Handling UnitsAlternate Setpoints System Log ReportVariable-Speed Fans Single-Speed FansTwo-Speed Fans Economizer Control Digital Economizer ControlAnalog Economizer Control Dehumidification ControlIntelligent Pre-Starts and Pre-Stops CurtailmentOptimum Start/Stop OSS Separate Setpoints AHU Zone ControlOutput Device Wire 8RO contacts Set Fail-safe Dip Switch to Zone ControlHow Zones Work 11- Suction Group OutputsApplications That May Be Connected To Zones MultiFlex RTU BoardMultiFlex RCB Board MultiFlex RCB-P BoardAHUs Zone TemperatureEconomization Enable MultiFlex RTUs and RCBs Effect of Enabling EconomizationZone Humidity Input Effect of Enabling Dehumidification 17- Diagram of Pre-Start and Pre-Stop Operation MultiFlex CUB Board Losing Contact With Zone ApplicationsStand-Alone MultiFlex RTUs MultiFlex RTU/ARTC and AHU Zone AssociationMultiFlex PAK Board Lighting SchedulesFunctions of the Lighting Schedule Application Control Method SelectStandard Control Light Level Interface CellMulti-Logic Combiner Alternate ControlSchedule Interface Cell Basic Schedule Cell Min ON/OFF CellProof Cell Offset Solar ControlDemand Control Output Light DimmingIntroduction to Demand Limit Control Demand MonitoringLoad Shedding Shedding LevelsPriority Levels DefinitionOther Notes About Priority Levels Rotational ShedLast Shed How Demand Control Uses Load Shedding Mode 1 KW Input Is Greater Than SetpointMode 3 Integral Error Approaching Zero Power Monitoring Input SettingsSensor Control Analog Sensor ControlControl Cells Digital Sensor ControlLogical Combination Diagram Loop/Sequence Control Cell DescriptionsOutput Cells Select CellOutput Cell Descriptions Time Scheduling and Holidays How Schedules WorkPWM Cell EventsPower Monitoring Holiday SchedulesTemporary Schedule Events OverlappingLogging HourlyDaily MonthlyHow Anti-Sweat Works Anti-Sweat SetupHeat/Cool Control Setpoint Reset Unoccupied HysteresisAnalog and Digital Combiners Lead/LagTemperature Differential TD Strategy ConfigurationTD Control TD Control Fail-SafesOutputs AlarmsPulse Accumulation Accumulator Reset Types Irrigation ControlHigh Trip Zones and CyclesZone Bypass Inputs Cycle SchedulingZone Inhibit Two Speed Fan Control Service ModesFlow Sensor-Related Tests Flexible Combiner Modular Chiller Control MCCLearning Mode Compressor ControlBoiler Bypass Valve ControlDigital Scroll Compressor Variable Frequency Drive CompressorRMS Asset RMS ScaleLog Information Device ConstraintsLogged Changes Unlogged ChangesPage Page Operator’s Guide to Using the E2 E2 Home ScreenBX Home Screen RX Home ScreenLogging On and Access Levels CX Home ScreenSystem Configuration Menu Toggling Full OptionsNavigation MenusPress System Configuration Press System Information System Information MenuScreen Types Actions MenuSummary Screens Status ScreensHeader Icons Setup ScreensIndex Tabs E2 Keypad CursorTab Key Enter KeyLog In/Out Key Four Directional Arrow KeysUp/Page Down Keys Ctrl Page Up/Ctrl Page Down KeysManual Defrost and Clean Mode Customizing the Home ScreenList menu and choose End Manual Mode OverridesChecking Boards Online Checking Status Screens Alarms Accessing the Alarm Advi Sory LogViewing the Controller Advisory Log Date and Time12.10.5 Ack/Reset State Alarm StatesArea Ctrl Application Property Advisory MessageResetting ClearingFacility Status Display FSD Alarms Viewing Logs and GraphsLocating Logged Inputs Outputs Home/Status ScreensLog View Setup ScreensSetting Up Input and Output Pointers Graph View Zooming In and OutMultiple Languages Defrost Type Appendix a Case Type DefaultsHigh Alarm, Low Alarm, and Delay Hdbx Table B-1- Temp Sensor Temperature/Resistance Chart Table B-2- Eclipse Voltage to Pressure ChartEclipse Transducers Voltage Pressure PSI 100 lb 200 lb 500 lb XducerPage Appendix C Alarm Advisory Messages Alarm Name Default Definition PriorityE2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Appendix C Alarm Advisory Messages C-3 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-5 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-7 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-9 10 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Appendix C Alarm Advisory Messages C-11 12 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 RAM 14 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Copeland CoreSense E2 Alarms ISD 2.0/2.1 CoreSense DiagnosticsNo 3PHASE PWR Other Advisories Performance Alert CoreSense DiagnosticsCoreSense Device Discus P470 CoreSense Protection K5 Ref Scroll P510 Copeland Scroll CoreSense CommP47 CoreSense Comm Throttling Range Proportional P ModeAppendix D PID Control Integral Mode Why I Mode is NecessaryProportional Constant Kp Throttling Range on page D-1Saturation Derivative ModeI Mode Calculation D Mode Calculation How Condenser Control Hvac PID Differs From OthersOutput at Setpoint Output at Setpoint for Non-CondenserOther PID Features Changing the Output at SetpointOutput at Minimum / Output at Maximum Output at Setpoint for Condenser/HVAC PID ControlMinimum Accumulated Error FilteringPage Page Medium Resolution Reuccf Page Page Appendix F Troubleshooting Refer to .1.9, PoweringEchelon Network Appendix F Troubleshooting F-3 Symptom Possible Problem Solution Number of Fans field? TripSymptom Possible Problem Solution Appendix F Troubleshooting F-7 Figured as an analog input Page Page Appendix G Revision Log Page Index NumericsBlue R. See Cold Reset Wash mode. See Clean Mode Demand Defrost. See Defrost, demand Hot Gas Defrost. See Defrost, hot gas Tion Probe LonWorks Network. See Echelon Network Pmac Hansen probe. See Sensors, liquid level 10 E2 RX/BX/CX I&O Manual Rev 4 5-JAN-2013 Valves
Related manuals
Manual 273 pages 39.74 Kb