| 1. Remove electrical power to unit. |
To avoid electrical shock or property damage, move the power switch to OFF and disconnect main circuit breaker, or unplug cord at wall receptacle.
Checkout:
2. Remove the side panel closest to the controls.
Step 3
3.Label and remove the wires from contactor.
4 . Perform a check on the contactor as follows:
Step 4
Test Points | Results |
from 23 to 29 | open circuit |
from 24 to 28 | open circuit |
from 25 to 27 | open circuit |
from 22 to 26 | ohm reading 415 |
Checkout - power supplied: |
|
To avoid electrical shock, make connections before apply- ing power, take reading, and remove power before remov- ing meter leads. The following checks are performed with the wall circuit breaker closed and the main power switch in the ON position.
5. With power reapplied, let unit start heating up.