FORM 201.18-EG1

Guide Specifications

PART 1 — GENERAL

1.01SCOPE

A.The requirements of the General Conditions, Supple- mentary Conditions, Division 1, and Drawings apply to all Work herein.

B.Provide Microprocessor controlled, twin-screw com- pressor, air-cooled, liquid chillers of the scheduled capacities as shown and indicated on the Drawings, including but not limited to:

1.Chiller package

2.Charge of refrigerant and oil

3.Electrical power and control connections

4.Chilled water connections

1.02QUALITY ASSURANCE

A.Products shall be Designed, Tested, Rated and Cer- tified in accordance with, and installed in compliance with applicable sections of the following Standards and Codes:

1.ANSI/ASHRAE Standard 15 – Safety Code for Mechanical Refrigeration

2.ANSI/NFPA Standard 70 – National Electrical Code (N.E.C).

PART 2 — PRODUCTS

2.01CHILLER MATERIALS AND COMPONENTS

A. General: Install and commission, as shown on the schedules and plans, factory assembled, charged, and tested air cooled screw compressor chiller(s) as specified herein. Chiller shall be designed, selected, and constructed using a refrigerant with Flammabil- ity rating of “1”, as defined by ANSI/ASHRAE STAN- DARD-34 Number Designation and Safety Classifi- cation of Refrigerants. Chiller shall include, but is not limited to: a complete system with not less than two independent refrigerant circuits, semihermetic twin screw compressors, direct expansion type evapora- tor, air-cooled condenser, refrigerant, lubrication sys- tem, interconnecting wiring, safety and operating controls including capacity controller, control center, motor starting components, and special features as specified herein or required for safe, automatic op- eration.

B. Cabinet: External structural members shall be con- structed of heavy gauge, galvanized steel coated with baked on powder paint which, when subject to ASTM B117, 500 hour, 5% salt spray test, yields minimum ASTM 1654 rating of “6”.

2.02COMPRESSORS AND MOTORS

3.ASME Boiler and Pressure Vessel Code, Sec- tion VIII, Division 1.

4.ARI Standard 550/590 – Centrifugal and Rotary Screw Water Chilling Packages.

5.Conform to Underwriters Laboratories (U.L.) for construction of chillers and provide U.L./cU.L. List- ing label.

6.Manufactured in facility registered to ISO 9002.

B.Factory Test: Chiller shall be pressure-tested, evacu- ated and fully charged with refrigerant and oil, and shall be factory operational run tested with water flow- ing through the vessel.

C.Warranty: Manufacturer shall Warrant all equipment and material of its manufacture against defects in workmanship and material for a period of one year from date of initial start-up or eighteen (18) months from date of shipment, whichever occurs first.

1.03DELIVERY AND HANDLING

A. Unit shall be delivered to job site fully assembled, and charged with refrigerant and oil by the Manufac- turer.

B. Unit shall be stored and handled per Manufacturer’s instructions.

A. Compressors: Shall be direct drive, semihermetic, rotary twin-screw type, including: internal muffler, tem- perature actuated ‘off-cycle’ heater, rain-tight termi- nal box, internal discharge check, discharge and suction shut-off service valves, and precision ma- chined cast iron housing. Design working pressure of entire compressor, suction to discharge, shall be 450 PSIG (31 bar). Compressor shall be U.L. listed.

B.Motors: Refrigerant suction gas cooled two-pole ac- cessible hermetic compressor motor, full suction gas flow through 0.006" maximum mesh screen, with in- herent internal thermal overload protection and ex- ternal current overload on all three phases. Motor stator shall employ APT2000 type magnet wire.

C.Lubrication: External oil separators with no moving or fragile parts, 450 PSIG design working pressure, and UL listing. Refrigerant system differential pres- sure shall provide oil flow through service replace- able, 0.5 micron, full flow, cartridge type oil filter in- ternal to compressor. Filter bypass, less restrictive media, or oil pump not acceptable.

D.Capacity Control: Compressors shall start at mini- mum load position. Capacity control range from 100% to 10% of chiller full load using continuous function slide valves, and without hot gas bypass. Step un- loading unacceptable. Provide Microprocessor con- trolled, output pressure regulating capacity control

YORK INTERNATIONAL

97

Image 97
Contents Millennium Table of Contents York Millennium Air Cooled Screw Liquid Chillers IntroductionComplete Factory Package SpecificationsSEMI-HERMETIC York Screw Compressors Condenser SectionMicroprocessor Controls Refrigerant CircuitPower Panel Accessories and Options Vibration Isolation DX Cooler OptionsSound Reduction Options High Static FansTemperature and Flows Temperatures and FlowsSI Units English Units Water Pressure DropPressure Drop kPa SI UnitsModel YCAS0110EC Iplv = Ratings English UnitsModel YCAS0100EC Model YCAS0090ECModel YCAS0110EC 100 105 110 115 120 125Model YCAS0120EC Iplv = Model YCAS0130EC Model YCAS0120ECModel YCAS0140EC Model YCAS0150EC Iplv = Model YCAS0160EC Model YCAS0150ECModel YCAS0170EC Model YCAS0180EC Iplv = Model YCAS0200EC Model YCAS0180ECModel YCAS0210EC Model YCAS0230EC Iplv = Model YCAS0250EC Model YCAS0230ECModel YCAS0270EC Model YCAS0300EC Iplv = Model YCAS0330EC Model YCAS0300ECModel YCAS0360EC Model YCAS0400EC Iplv = Model YCAS0440EC Model YCAS0400ECRatings SI Units Model YCAS0120EC YCAS0170EC YCAS0160ECModel YCAS0200EC YCAS0180ECModel YCAS0230EC Model YCAS0300EC Model YCAS0400EC Model YCAS0440EC English Units Physical DataCondenser Fans SI Units Refrig. Charge, R-22,Ckt.-1 / Ckt.-2, kg View A-A Dimensions YCAS0090 0100EC English0090 73.7 41.9 38.4 0100 73.8 41.7 30.01 Center of Gravity AlumDimensions YCAS0090 0100EC SI 0100 1875.4 1059.8 0090 1872.9 1063.3Dimensions YCAS0110 0120EC English 82.8 43.2 38.9 0120Dimensions YCAS0110 0120EC SI 0120 1837.0 1093.8 1834.7 1095.7130 150 Dimensions YCAS0130 0180 English0140 01300150 0160130 150 438 457 Dimensions YCAS0130 0180 SI2573.0 1127.8 960.1 Dimensions YCAS0200 0230 English 0210 02000230 Dimensions YCAS0200 0230 SI 965.2 0200 3032.80210 3032.8 0230 3032.816 Egde of Unit to Cooler Connection Dimensions YCAS0250 0270 English144.5 42.0 40.3 0250 141.6 33.8 0270 140.6 41.7 33.7All dimensions are Mm unless otherwise noted Dimensions YCAS0250 0270 SI1063 1030 0270 02501066 1023 16 Edge of Unit to Cooler Connection Dimensions YCAS0300 0330 English0330 0300Dimensions YCAS0300 0330 SI 3842 1058 876 0330 3911 1057 883 0300View A-A View C-C Dimensions YCAS0360 English0360 200.7 44.0 39.6 0360 197.3 44.0 33.2Dimensions YCAS0360 SI 0360 5011 1117 844 5097 1005 Dimensions YCAS0400 0440 English 218.7 44.0 34.1 Dimensions YCAS0400 0440 SI 0440 0400Lbs Operating Weights Aluminum Fin CoilsIsolator Selection Aluminum Fin Coils Copper FIN Coil Weight Distribution by Model LBS Ycas Total Operating Weights Copper Fin CoilsIsolator Selection Copper Fin Coils Or RD-3 Isolator DetailsOr RD-4 AWMR-1-XXX CP-2-XXAWMR-2-XXX Electrical Data System #1 FIELD-SUPPLIED WiringOPT. NF FLA See page 89 for Electrical Data footnotes MIN NF OVER-CURRENT Wire Range Data Ycas Chiller FIELD-SUPPLIED Wiring System #1 System #2 Model Volts Compressor Data Field Supplied Wiring LRA RLA Standard Optional NF FLA LRA RLA RLA LRA QTY Electrical Notes20A 30A Style F 2 Compressor Power Wiring Connections Power Connection OptionsLD05550 Two Compressor Diagrams Control Power Wiring As Shown OnSee Note CB1 CB3 CB2 CB4 Typical Control Wiring 2-Compressor Units For Legend Refer to Bottom Unit Location Application DataFoundation Chilled Liquid PipingGuide Specifications Heat Exchangers Refrigerant Circuit ComponentsControls Power Connection and Distribution 100 Part 3 Execution Installation 102 103 Proud Sponsor