YORK INTERNATIONAL
95
FOR LEGEND | REFER TO BOTTOM OF PAGE 93 |
. |
|
|
|
NOTES: |
|
1. Field wiring to be in accordance with the current edition of the National Electrical Code as well as all other applicable codes and specifications. | LD04756 |
2.Contacts must be suitable for switching 24VDC, (gold contacts recommended). Wiring shall not be run in the same conduit with any line voltage wiring.
3.To cycle unit on and off automatically with contact shown, install a cycling device in series with the flow switch (flsw). See note 2 for contact rating and wiring specifications.
4.To stop unit (emergency stop) with contacts other than those shown, install the stop contact between terminals 5 and 1. If a stop device is not installed, a jumper must be connected between terminals 5 and 1. Device must have a minimum contact rating of 100va at 115 volts a.c.
5.Alarm contacts are for annunciating alarm/unit malfunction. Contacts are rated at 115V, 100va, resistive load only, and must be suppressed at load by user.
6.See Installation, Operation and Maintenance manual when optional equipment is used.