York 28971AR manual 20A 30A

Page 89

FORM 201.18-EG1

Electrical Notes (Continued)

CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMER)

NO. OF

CONTROL

MCA

MAX DUAL

NON-FUSED

POWER

(MAX LOAD

ELEMENT

DISCONNECT

COMPRESSORS

SUPPLY

CURRENT)

FUSE SIZE

SWITCH SIZE

 

 

 

 

 

 

2

115V-1Ø

20A

20A

30A

 

 

 

 

 

3 or 4

115V-1Ø

30A

30A

30A

(Non-CE 50/60Hz)

 

 

 

 

 

 

 

 

 

3 or 4

115V-1Ø

25A

30A

30A

(CE 50Hz)

 

 

 

 

 

 

 

 

 

CONTROL POWER SUPPLY (UNITS WITH STANDARD CONTROL CIRCUIT TRANSFORMER)

NO. OF

CONTROL

MCA

RECOMMENDED

NON-FUSED

POWER

(MAX LOAD

DUAL ELEMENT

DISCONNECT

COMPRESSORS

SUPPLY

CURRENT)

FUSE SIZE

SWITCH SIZE

 

 

 

 

 

 

 

200V - 60 HZ

12.5A

30A

 

230V - 60 HZ

10.9A

30A

2

380V - 60 HZ

6.6A

15A

 

460V - 60 HZ

5.4A

15A

 

575V - 60HZ

4.3A

15A

 

380V - 60 HZ

9.9A

30A

3 or 4

460V - 60 HZ

8.2A

15A

 

575V - 60 HZ

6.5A

15A

 

 

 

 

 

NOTES (for pages 78 - 89)

1.Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the system #1 MCA values in the YCAS Tables: -17, add 15 amps; -28, add 12 amps; -40, add 7 amps; -46, add 6 amps; -58, add 5 amps.

2.The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the circuit, per N.E.C. 440 - 12A1.

3.Minimum recommended fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs. Minimum fuse rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

4.Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. 440-22. Maximum fuse rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

5.Minimum recommended circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit. Minimum circuit breaker rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

6.Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + ( # fans x each fan motor FLA).

7.The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), or (3) indicate the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must be determined based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based on the National Electric Code and using copper conductors only. Field wiring must also comply with local codes.

8.A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.

9.The field supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.

10.Two-Compressor machines with single-point power connection, and equipped with Star (Wye)-Delta Compressor motor start must also include factory-provided individual system circuit breakers in each motor control center. All 3 & 4 Compressor machines equipped with Star-Delta compressor motor start must also include factory-provided individual system circuit breakers in each motor control center.

11.Consult factory for Electrical Data on units equipped with “High Static Fan” option. High Static Fans are 3.8 kW each.

12.FLA for “Low Noise Fan” motors: 200V = 8.0A, 230V = 7.8A, 380V = 4.4A, 460V = 3.6A, 575V = 2.9A.

13.Group Rated breaker must be HACR type for cUL Machines.

YORK INTERNATIONAL

89

Image 89
Contents Millennium Table of Contents York Millennium Air Cooled Screw Liquid Chillers IntroductionComplete Factory Package SpecificationsSEMI-HERMETIC York Screw Compressors Condenser SectionMicroprocessor Controls Refrigerant CircuitPower Panel Accessories and Options Vibration Isolation DX Cooler OptionsSound Reduction Options High Static FansTemperature and Flows Temperatures and FlowsSI Units English Units Water Pressure DropPressure Drop kPa SI UnitsModel YCAS0110EC Iplv = Ratings English UnitsModel YCAS0100EC Model YCAS0090ECModel YCAS0110EC 100 105 110 115 120 125Model YCAS0120EC Iplv = Model YCAS0140EC Model YCAS0120ECModel YCAS0130EC Model YCAS0150EC Iplv = Model YCAS0170EC Model YCAS0150ECModel YCAS0160EC Model YCAS0180EC Iplv = Model YCAS0210EC Model YCAS0180ECModel YCAS0200EC Model YCAS0230EC Iplv = Model YCAS0270EC Model YCAS0230ECModel YCAS0250EC Model YCAS0300EC Iplv = Model YCAS0360EC Model YCAS0300ECModel YCAS0330EC Model YCAS0400EC Iplv = Model YCAS0440EC Model YCAS0400ECRatings SI Units Model YCAS0120EC YCAS0170EC YCAS0160ECModel YCAS0200EC YCAS0180ECModel YCAS0230EC Model YCAS0300EC Model YCAS0400EC Model YCAS0440EC English Units Physical DataCondenser Fans SI Units Refrig. Charge, R-22,Ckt.-1 / Ckt.-2, kg View A-A Dimensions YCAS0090 0100EC English0090 73.7 41.9 38.4 0100 73.8 41.7 30.01 Center of Gravity AlumDimensions YCAS0090 0100EC SI 0100 1875.4 1059.8 0090 1872.9 1063.3Dimensions YCAS0110 0120EC English 82.8 43.2 38.9 0120Dimensions YCAS0110 0120EC SI 0120 1837.0 1093.8 1834.7 1095.7130 150 Dimensions YCAS0130 0180 English0140 01300150 0160130 150 438 457 Dimensions YCAS0130 0180 SI2573.0 1127.8 960.1 Dimensions YCAS0200 0230 English 0230 02000210 Dimensions YCAS0200 0230 SI 965.2 0200 3032.80210 3032.8 0230 3032.816 Egde of Unit to Cooler Connection Dimensions YCAS0250 0270 English144.5 42.0 40.3 0250 141.6 33.8 0270 140.6 41.7 33.7All dimensions are Mm unless otherwise noted Dimensions YCAS0250 0270 SI1066 1023 02501063 1030 0270 16 Edge of Unit to Cooler Connection Dimensions YCAS0300 0330 English0330 0300Dimensions YCAS0300 0330 SI 3842 1058 876 0330 3911 1057 883 0300View A-A View C-C Dimensions YCAS0360 English0360 200.7 44.0 39.6 0360 197.3 44.0 33.2Dimensions YCAS0360 SI 0360 5011 1117 844 5097 1005 Dimensions YCAS0400 0440 English 218.7 44.0 34.1 Dimensions YCAS0400 0440 SI 0440 0400Lbs Operating Weights Aluminum Fin CoilsIsolator Selection Aluminum Fin Coils Copper FIN Coil Weight Distribution by Model LBS Ycas Total Operating Weights Copper Fin CoilsIsolator Selection Copper Fin Coils Or RD-4 Isolator DetailsOr RD-3 AWMR-2-XXX CP-2-XXAWMR-1-XXX Electrical Data System #1 FIELD-SUPPLIED WiringOPT. NF FLA See page 89 for Electrical Data footnotes MIN NF OVER-CURRENT Wire Range Data Ycas Chiller FIELD-SUPPLIED Wiring System #1 System #2 Model Volts Compressor Data Field Supplied Wiring LRA RLA Standard Optional NF FLA LRA RLA RLA LRA QTY Electrical Notes20A 30A Style F 2 Compressor Power Wiring Connections Power Connection OptionsLD05550 See Note Control Power Wiring As Shown OnTwo Compressor Diagrams CB1 CB3 CB2 CB4 Typical Control Wiring 2-Compressor Units For Legend Refer to Bottom Unit Location Application DataFoundation Chilled Liquid PipingGuide Specifications Controls Refrigerant Circuit ComponentsHeat Exchangers Power Connection and Distribution 100 Part 3 Execution Installation 102 103 Proud Sponsor