Temperatures and Flows
TEMPERATURE AND FLOWS
(English Units)
MODEL | LEAVING WATER | COOLER FLOW |
| AIR ON | ||||
NUMBER | TEMPERATURE (°F) |
| (GPM3) | CONDENSER (°F) | ||||
YCAS | MIN.1 | MAX.2 | MIN. |
| MAX. | MIN. |
| MAX |
0090EC | 40 | 55 | 113 |
| 600 | 0 |
| 125 |
0100EC | 40 | 55 | 122 |
| 600 | 0 |
| 125 |
0110EC | 40 | 55 | 127 |
| 600 | 0 |
| 125 |
0120EC | 40 | 55 | 134 |
| 600 | 0 |
| 125 |
0130EC | 40 | 55 | 147 |
| 600 | 0 |
| 125 |
0140EC | 40 | 55 | 170 |
| 600 | 0 |
| 125 |
0150EC | 40 | 55 | 182 |
| 700 | 0 |
| 125 |
0160EC | 40 | 55 | 188 |
| 747 | 0 |
| 125 |
0170EC | 40 | 55 | 203 |
| 747 | 0 |
| 125 |
0180EC | 40 | 55 | 218 |
| 747 | 0 |
| 125 |
0200EC | 40 | 55 | 228 |
| 747 | 0 |
| 125 |
0210EC | 40 | 55 | 248 |
| 747 | 0 |
| 125 |
0230EC | 40 | 55 | 272 |
| 747 | 0 |
| 125 |
0250EC | 40 | 55 | 225 |
| 800 | 0 |
| 125 |
0270EC | 40 | 55 | 225 |
| 800 | 0 |
| 125 |
0300EC | 40 | 55 | 255 |
| 800 | 0 |
| 125 |
0330EC | 40 | 55 | 255 |
| 800 | 0 |
| 125 |
0360EC | 40 | 55 | 300 |
| 1060 | 0 |
| 125 |
0400EC | 40 | 55 | 330 |
| 1060 | 0 |
| 125 |
0440EC | 40 | 55 | 330 |
| 1060 | 0 |
| 125 |
|
|
|
|
|
|
|
|
|
NOTES:
1.For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.
2.For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK office for application guidelines.
3.The evaporator is protected against freezing to
10 | YORK INTERNATIONAL |