6.Display Data: Chiller liquid return and leaving tem- peratures, ambient, lead compressor identifica- tion and lead/lag delay, clock and schedule, (vari- able) out of range, remote input indication, chilled liquid reset setpoint, leaving liquid
7.System Safeties: Shall cause individual compres- sor systems to perform
8.Unit Safeties: Shall be automatic reset and cause
compressors to shut down if: high or low ambi- ent, low leaving chilled liquid temperature, under voltage, and flow switch operation. Contractor shall provide flow switch and wiring per chiller manufacturer requirements.
9.Alarm Contacts: High or low ambient, low leaving chilled liquid temperature, low voltage, low bat- tery, and (per compressor circuit): high discharge pressure or temperature, low suction pressure, low or high motor current, low or high differential oil pressure, and high oil temperature.
E.Manufacturer shall provide any controls not listed above, necessary for automatic chiller operation. Mechanical Contractor shall provide field control wir- ing necessary to interface sensors to the chiller con- trol system.
2.06POWER CONNECTION and DISTRIBUTION
A. Power Panels:
1.NEMA 3R/12 (IP55) rain/dust tight, powder painted steel cabinets with hinged, latched, and gasket sealed outer doors equipped with wind struts for safer servicing. Provide main power connection(s), compressor and fan motor start contactors, current overloads, and factory wiring.
2.Field power supply wiring connections shall be to a single power center on the chiller, shall be 3 phase of scheduled voltage, and shall connect to terminal blocks per each of the two motor control panels. Separate disconnecting means and/or ex- ternal branch circuit protection (by Contractor) re- quired per applicable local or national codes.
3.Provide two electrically separate, adjacent motor control center cabinets, with independent doors and separated by a steel panel, for compressor and fan motor power distribution components.
B.Exposed compressor and fan motor power wiring shall be routed through liquid tight conduit.
2.07ACCESSORIES and OPTIONS
Some accessories and options supercede standard product features. Your YORK representative will be pleased to provide assistance.
A. Microprocessor controlled, Factory installed Wye- Delta compressor motor starters for reduced com- pressor inrush start current.
B. Power Supply Connections:
1.Two Compressor Machines –
a.Multiple Point with Individual System Circuit Breakers or