York 28971AR manual Power Connection and Distribution

Page 99

FORM 201.18-EG1

6.Display Data: Chiller liquid return and leaving tem- peratures, ambient, lead compressor identifica- tion and lead/lag delay, clock and schedule, (vari- able) out of range, remote input indication, chilled liquid reset setpoint, leaving liquid pull-down rate setpoint, leaving liquid error (deviation from set- point), and history data for last six shutdown faults. Compressor suction, discharge, and oil pressures and temperatures, suction and discharge super- heats, percent of full-load motor current, operat- ing hours, starts, and anti-recycle timer status. Status Messages for manual override, unit switch off, compressor run, run permissive, remote con- trolled shut down, no cooling load, daily/holiday shut down, anti-recycle/anti-coincident timer, high pressure low suction temperature limit.

7.System Safeties: Shall cause individual compres- sor systems to perform auto-reset shut down; manual reset required after the third trip in 90 minutes. Includes: high discharge pressure or temperature, low suction pressure, high / low motor current, high pressure switch, high / low differential oil pressure, high oil temperature, and motor protector. Compressor motor protector shall protect against damage due to: low or high input current, phase reversal (reverse rotation), current unbalance, phase loss, thermal overload of wind- ings, and low voltage.

8.Unit Safeties: Shall be automatic reset and cause

compressors to shut down if: high or low ambi- ent, low leaving chilled liquid temperature, under voltage, and flow switch operation. Contractor shall provide flow switch and wiring per chiller manufacturer requirements.

9.Alarm Contacts: High or low ambient, low leaving chilled liquid temperature, low voltage, low bat- tery, and (per compressor circuit): high discharge pressure or temperature, low suction pressure, low or high motor current, low or high differential oil pressure, and high oil temperature.

E.Manufacturer shall provide any controls not listed above, necessary for automatic chiller operation. Mechanical Contractor shall provide field control wir- ing necessary to interface sensors to the chiller con- trol system.

2.06POWER CONNECTION and DISTRIBUTION

A. Power Panels:

1.NEMA 3R/12 (IP55) rain/dust tight, powder painted steel cabinets with hinged, latched, and gasket sealed outer doors equipped with wind struts for safer servicing. Provide main power connection(s), compressor and fan motor start contactors, current overloads, and factory wiring.

2.Field power supply wiring connections shall be to a single power center on the chiller, shall be 3 phase of scheduled voltage, and shall connect to terminal blocks per each of the two motor control panels. Separate disconnecting means and/or ex- ternal branch circuit protection (by Contractor) re- quired per applicable local or national codes.

3.Provide two electrically separate, adjacent motor control center cabinets, with independent doors and separated by a steel panel, for compressor and fan motor power distribution components.

B.Exposed compressor and fan motor power wiring shall be routed through liquid tight conduit.

2.07ACCESSORIES and OPTIONS

Some accessories and options supercede standard product features. Your YORK representative will be pleased to provide assistance.

A. Microprocessor controlled, Factory installed Wye- Delta compressor motor starters for reduced com- pressor inrush start current. Two-compressor ma- chines with Single-Point Power connection and equipped with Star-Delta compressor motor start must also include factory provided circuit breakers in each motor control center. All 3 & 4 compressor machines equipped with Star-Delta compressor mo- tor start must also include factory provided circuit breakers in each motor control center.

B. Power Supply Connections:

1.Two Compressor Machines –

a.Multiple Point with Individual System Circuit Breakers or Non-Fused Disconnect Switches: Two Field provided branch circuits shall con- nect to Individual System Circuit Breakers or Non-Fused Disconnects per compressor on each of the two motor control centers, with lockable external handles on doors in compli- ance with Article 440-14 of the N.E.C.

b.Single-Point Terminal Block or Non-fused Dis- connect Switch: Field provided branch circuit shall connect to single-point Terminal Block or Non-Fused Disconnect with lockable exter- nal handle in compliance with N.E.C. Article 440-14, with Factory provided interconnect- ing wiring to (optional Individual System Cir- cuit Breakers, and) compressor motor start components in each of two motor control cen- ter cabinets.

c.Single-Point Circuit Breaker: Field provided branch circuit shall connect to Single-Point Cir- cuit Breaker with Lockable External Handle (in compliance with Article 440-14 of N.E.C.)

YORK INTERNATIONAL

99

Image 99
Contents Millennium Table of Contents York Millennium Air Cooled Screw Liquid Chillers IntroductionCondenser Section SpecificationsComplete Factory Package SEMI-HERMETIC York Screw CompressorsMicroprocessor Controls Refrigerant CircuitPower Panel Accessories and Options Vibration Isolation DX Cooler OptionsSound Reduction Options High Static FansTemperature and Flows Temperatures and FlowsSI Units English Units Water Pressure DropPressure Drop kPa SI UnitsModel YCAS0110EC Iplv = Ratings English Units100 105 110 115 120 125 Model YCAS0090ECModel YCAS0100EC Model YCAS0110ECModel YCAS0120EC Iplv = Model YCAS0120EC Model YCAS0130ECModel YCAS0140EC Model YCAS0150EC Iplv = Model YCAS0150EC Model YCAS0160ECModel YCAS0170EC Model YCAS0180EC Iplv = Model YCAS0180EC Model YCAS0200ECModel YCAS0210EC Model YCAS0230EC Iplv = Model YCAS0230EC Model YCAS0250ECModel YCAS0270EC Model YCAS0300EC Iplv = Model YCAS0300EC Model YCAS0330ECModel YCAS0360EC Model YCAS0400EC Iplv = Model YCAS0440EC Model YCAS0400ECRatings SI Units Model YCAS0120EC YCAS0170EC YCAS0160ECModel YCAS0200EC YCAS0180ECModel YCAS0230EC Model YCAS0300EC Model YCAS0400EC Model YCAS0440EC English Units Physical DataCondenser Fans SI Units Refrig. Charge, R-22,Ckt.-1 / Ckt.-2, kg View A-A Dimensions YCAS0090 0100EC English0090 73.7 41.9 38.4 0100 73.8 41.7 30.01 Center of Gravity AlumDimensions YCAS0090 0100EC SI 0100 1875.4 1059.8 0090 1872.9 1063.3Dimensions YCAS0110 0120EC English 82.8 43.2 38.9 0120Dimensions YCAS0110 0120EC SI 0120 1837.0 1093.8 1834.7 1095.7130 150 Dimensions YCAS0130 0180 English0160 01300140 0150130 150 438 457 Dimensions YCAS0130 0180 SI2573.0 1127.8 960.1 Dimensions YCAS0200 0230 English 0200 02100230 Dimensions YCAS0200 0230 SI 0230 3032.8 0200 3032.8965.2 0210 3032.816 Egde of Unit to Cooler Connection Dimensions YCAS0250 0270 English144.5 42.0 40.3 0250 141.6 33.8 0270 140.6 41.7 33.7All dimensions are Mm unless otherwise noted Dimensions YCAS0250 0270 SI0250 1063 1030 02701066 1023 16 Edge of Unit to Cooler Connection Dimensions YCAS0300 0330 English0330 0300Dimensions YCAS0300 0330 SI 3842 1058 876 0330 3911 1057 883 0300View A-A View C-C Dimensions YCAS0360 English0360 200.7 44.0 39.6 0360 197.3 44.0 33.2Dimensions YCAS0360 SI 0360 5011 1117 844 5097 1005 Dimensions YCAS0400 0440 English 218.7 44.0 34.1 Dimensions YCAS0400 0440 SI 0440 0400Lbs Operating Weights Aluminum Fin CoilsIsolator Selection Aluminum Fin Coils Copper FIN Coil Weight Distribution by Model LBS Ycas Total Operating Weights Copper Fin CoilsIsolator Selection Copper Fin Coils Isolator Details Or RD-3Or RD-4 CP-2-XX AWMR-1-XXXAWMR-2-XXX Electrical Data System #1 FIELD-SUPPLIED WiringOPT. NF FLA See page 89 for Electrical Data footnotes MIN NF OVER-CURRENT Wire Range Data Ycas Chiller FIELD-SUPPLIED Wiring System #1 System #2 Model Volts Compressor Data Field Supplied Wiring LRA RLA Standard Optional NF FLA LRA RLA RLA LRA QTY Electrical Notes20A 30A Style F 2 Compressor Power Wiring Connections Power Connection OptionsLD05550 Control Power Wiring As Shown On Two Compressor DiagramsSee Note CB1 CB3 CB2 CB4 Typical Control Wiring 2-Compressor Units For Legend Refer to Bottom Chilled Liquid Piping Application DataUnit Location FoundationGuide Specifications Refrigerant Circuit Components Heat ExchangersControls Power Connection and Distribution 100 Part 3 Execution Installation 102 103 Proud Sponsor