STEP 6: ELECTRICAL REQUIREMENTS, CONNECTION & GROUNDING

A 3 or 4 conductor supply may be connected to the terminal block. A 4 conductor supply shall be used only when the range is installed in a mobile home or where local codes do not permit grounding through the neutral.

3 WIRE LEAD CONNECTION

1.Remove upper nuts only from the terminal block studs. Do not remove nuts which secure range internal wiring leads.

2.Secure the neutral, grounded wire of the supply circuit, to the center stud of the terminal block with nut. (See Fig. 17a).

3.Secure the LI (black) and L2 (red) power leads to the outside terminal block studs (brass colored) with nuts.

4.Tighten nuts securely.

4 WIRE CONNECTION

1.Remove upper nuts only from the terminal block studs. Do not remove lower nuts which secure range internal wiring leads.

2.Remove ground strap screw and bend the strap up as shown in Fig. 18)

3.Secure the neutral wire to the center stud of the terminal block with nut. Tape neutral wire and connector, as shown in Fig. 18a to insure strap does not contact a grounded surface.

4.Secure the LI (black) and L2 (red) power leads to the outside terminal studs (brass colored) with nuts.

5.Secure the bare copper ground lead to the range chassis using the ground screw previ ously used for the ground strap.

FIG.17 Conductor Securement

Upper Nut

^-Cupped Washer

*"- Supply Wire

lat Washer

FIG. 17a 3 Wire Connection

L2Red

Neutral White

FIG. 18 Ground Strap

Bend Ground Strap Up

FIG. 18a Secure Neutral Wire

6.Tighten all connections securely.

L1 Black

Ground Wire

Page 18

Image 20
Contents Corporation Gas SupplyWhat to do If YOU Smell GAS Do not try to light any applianceIf you cannot reach your gas supplier, call Fire department Small electric oven with a breadCE QUI Faire SI Vous Avertissements EN FrancaisAvertissement Danger DE Renversement LES Degats DE LA Protriete AvertissementTouteslescuisinieres Risques D* ElectrocutionWall Installation Island InstallationVentilation Requirements VTrim. See Steps 2Cabinet Clearances WanCabinet Preparation Side View 30, 36 and 48 RangesModel GAS and Electric Supply ZonesGrounding plug. IT Must be Plugged Power Cord & Receptacle Junction Box & Conduit Electrical SUPPLY, Dual Fuel RangesUNPACKING, Moving and Placing the Range All Ranges RemovalUNPACKING, Moving and Placing the Range ALL Ranges can TIP Installing ANTI-TIP DeviceRange Tipping Hazard Prepare holes at fastener locations as identified below Important Installation InformationPRG36 All-Gas Ranges Side View Step B Set the bracket on the floor and turn itPlan View PRDS304 and PRDS36 Dual-Fuel Ranges Figures 11, 14 Prds Wall Mount Prds Floor Mount Manifold Pressure 10 water column 24.9 mb GAS Requirements and Hookup Hook UP Phase For P*RDS304 range Unit and remove cover. Refer toWire Lead Connection Ground WireWire Connection Cupped WasherGrounding Method PRG48Under ANY CIRCUMSTANCES, be CUT or Removed PROS36 and PRDS48Backguard Installation Case 2 Electrical Connections and GroundingBackguard must be attached PRDS36/PRG36Test and Adjustment To Clean and Protect Exterior Surfaces Griddle 3/4 4to Grill 1/4 1/2Final Check List GAS SupplyPage Page Thermador Corporation