STEP 6: ELECTRICAL REQUIREMENTS, CONNECTION & GROUNDING
Dual Fuel models PRDS304, PRDS36 and PRDS48 must be connected to the power supply utilizing one ofthe following methods. For all methods of connection, the length ofthe cord or conduit/wiring must allow the unit to be slid completely out of the cabinet without having to unplug or disconnect the unit from the power supply. Recommended minimum free length of cord or conduit is four feet. Electrical installations and grounding must be in accordance with all local codes and ordinances, and/or the National Electric Code, as applicable.
•
Locate the junction box on the rear of the unit and remove cover. Refer to Fig. 16 for PRDS304 range and Fig. 16a for PRDS36 and PRDS48 ranges. Remove the knock out ring in the junction box to provide a 1 - 3/8" diameter hole. Install the cord to the junction box, and make the connections to the terminal block provided. Refer to Figures 17 and 17a. The cord kit must be plugged into a mating NEMA
•
ends of the individual conduc tors, preferably soldered in place.
Locate the junction box on the rear of the unit and remove cover. Refer to Fig. 16 for PRDS304 range and Fig. 16a for PRDS36 and PRDS48 ranges. Remove the knock out ring in the junction box to provide a 1
PERMANENT CONNECTION (HARD WIRING)- Units may be hard wired to the power supply. The installer must provide approved flexible aluminum conduit, 3/4" trade size, maxi mum 6 feet long. Locate the junction box on the rear of the
unit and remove cover. Refer to
Fig. 16 for P*RDS304 range and
Fig. 16a for PRDS36 and PRDS48 ranges. Remove the ground strap retaining screw and bend the ground strap up. Refer to Fig. 18. The conduit must be installed to the junction box using an approved conduit connector.
Wiring for the unit is to be brought into thejunction box through the conduit. Refer to Chart D on Page 16 for rating of wiring and sizing of individual
conductors. The ends of the wiring must have #10 closed- loop lugs attached, preferably soldered in place. Make the connections to the terminal block provided. Secure the ground lead to thejunction box with the screw previously used to secure the ground strap. Refer to Fig. 18a. The frSe end of the conduit must be con nected to ajunction box pro vided in the gas and electrical supply zone, as shown in Figures 3b and 3c on Page 6.
FIG. 16 Location of Junction Box on PRDS304 Range
Hole for
Width Connection of Cord 67 Conduit
of
FIG. 16a Location of Junction Box on PRDS36, 48.
Hole for Con nection of Coed or Conduit
MODEL DIM "A"
PRDS36
PRDS48 19"
Page 17