Carrier 30GN040-420 Keypad and Display Module Also Called Hsio, Stop, Local/Enable

Page 4

also controls the EXV driver module (as appropriate), com- manding it to open or close each EXV in order to maintain the proper superheat entering the cylinders of each lead com- pressor. Information is transmitted between the processor mod- ule and relay module, the EXV driver module, and the key- pad and display module through a 3-wire communications bus. The options module is also connected to the commu- nications bus.

For the Flotronic™ II chillers, the processor monitors sys- tem pressure by means of 6 transducers, 3 in each lead com- pressor. Compressor suction pressure, discharge pressure, and oil pressure are sensed. If the processor senses high dis- charge pressure or low suction pressure, it immediately shuts down all compressors in the affected circuit. During opera- tion, if low oil pressure is sensed for longer than one minute, all compressors in the affected circuit are shut down. At start- up, the oil pressure signal is ignored for 2 minutes. If shut- down occurs due to any of these pressure faults, the circuit is locked out and the appropriate fault code is displayed.

Low-Voltage Relay Module Ð This module closes contacts to energize compressor unloaders and/or compres- sors. It also senses the status of the safeties for all compres- sors and transmits this information to the processor.

Electronic Expansion Valve Module (If So Equipped) Ð This module receives signals from the pro- cessor and operates the electronic expansion valves.

Options Module Ð This module allows the use of Flo- tronic II features such as dual set point, remote reset, de- mand limit, hot gas bypass, and accessory unloaders. The options module also allows for reset and demand limit to be activated from a remote 4-20 mA signal. The options mod- ule is installed at the factory.

Keypad and Display Module (Also Called HSIO

or LID) Ð This device consists of a keypad with 6 func- tion keys, 5 operative keys, 12 numeric keys, and an alpha- numeric 8-character LCD (liquid crystal display). Key us- age is explained in Accessing Functions and Subfunctions section on page 24.

Control Switch Ð Control of the chiller is de®ned by the position of the LOCAL/ENABLE-STOP-CCN switch. This is a 3-position manual switch that allows the chiller to be put under the control of its own Flotronic II controls, manu- ally stopped, or put under the control of a Carrier Comfort Network (CCN). Switch allows unit operation as shown in Table 2.

In the LOCAL/ENABLE position, the chiller is under lo- cal control and responds to the scheduling con®guration and set point data input at its own local interface device (keypad and display module).

Table 2 Ð LOCAL/ENABLE-STOP-CCN

Switch Positions and Operation

SWITCH

UNIT

CONFIGURATION AND

SET POINT CONTROL

POSITION

OPERATION

 

 

Keypad Control

CCN Control

 

 

STOP

Unit Cannot Run

Read/Write

Read Only

LOCAL/ENABLE

Unit Can Run

Read/Limited Write

Read Only

CCN Stop Ð

Unit Cannot Run

Read Only

Read/Write

Run Ð

Unit Can Run

Read Only

Read/Limited

Write

 

 

 

 

 

 

 

In the CCN position, the chiller is under remote control and responds only to CCN network commands. The occupied/ unoccupied conditions are de®ned by the network. All key- pad and display functions can be read at the chiller regard- less of position of the switch.

CCN run or stop condition is established by a command from the CCN network. It is not possible to force outputs from the CCN network, except that an emergency stop com- mand shuts down the chiller immediately and causes ``ALARM 52'' to be displayed.

Electronic Expansion Valve (EXV) Ð The micro- processor controls the EXV (if so equipped) through the EXV driver module. Inside the expansion valve is a linear actua- tor stepper motor.

The lead compressor in each circuit has a thermistor and a pressure transducer located in the suction manifold after the compressor motor. The thermistor measures the tem- perature of the superheated gas entering the compressor cyl- inders. The pressure transducer measures the refrigerant pressure in the suction manifold. The microprocessor converts the pres- sure reading to a saturated temperature. The difference be- tween the temperature of the superheated gas and the satu- ration temperature is the superheat. The microprocessor controls the position of the electronic expansion valve stepper motor to maintain 30 F (17 C) superheat.

At initial unit start-up, the EXV position is at zero. After that, the microprocessor keeps accurate track of the valve position in order to use this information as input for the other control functions. The control monitors the superheat and the rate of change of superheat to control the position of the valve. The valve stroke is very large, which results in very accurate control of the superheat.

Thermostatic Expansion Valves (TXV) Ð Model 30GN040 and 045 units with factory-installed brine option are equipped with conventional thermostatic expansion valves with liquid line solenoids. The liquid line solenoid valves are not intended to be a mechanical shut-off. When service is required, use the liquid line service valve to pump down the system.

4

Image 4
Contents Controls, Operation, Troubleshooting Unit Model Nominal Section a Section B Unit Sizes and Modular CombinationsTons Unit 30GN 30GN Control Panel 040-110 Unit Shown LOCAL/ENABLE-STOP-CCN Switch Positions and Operation LOCAL/ENABLEKeypad and Display Module Also Called Hsio StopCompressor Protection Control Module Cpcs Thermistor and Transducer LocationsThermistors Pressure TransducersLoading Sequence a Loading Sequence B Unit Control Ð Capacity Control StepsSteps Ð Capacity Control Steps, 040-070 Ð Capacity Control Steps, 040-070 Displacement Compressors Approx 080, 230B 60 Hz A1²,B1²A1²**, B1² A1²**,B1²090, 245B 60 Hz Compressors Displacement090, 245B 50 Hz 100, 255B 270B 60 HzUnit Control Loading Sequence a Loading Sequence B 270B 50 Hz315B 60 Hz 110, 290B315B 50 Hz A1*,A2,B1 A1,A2,B1 A1²²,A2,B1,B2 A1*,A2,B1,B2 130 60 Hz 130 50 Hz 150, 230A, 245AA1,kB1 170, 270A 330A/B 60 Hz330A/B,360B 50 Hz 330A/B, 360B 50 Hz Approx 190, 290A, 360A/B 390B 60 HzA1,B1 A1**,B1210, 315A, 390A 420A/B 60 Hz420A/B 50 Hz Head Pressure Control PumpoutCondenser Fan Sequence FAN Arrangement FAN Numbers FAN Contactor Controlled byKeypad and Display Module Usage Functions and SubfunctionsFunction USE Keys Operative USE KeysAccessing Functions and Subfunctions Keypad DirectoryTemperature Keypad Directory StatusSubfunction Keypad Entry Display Comment Stage SET PointSubfunction Keypad Entry Display Comment Pressure AnalogInputs OutputsSubfunction Keypad Entry Display Comment Subfunction Keypad Entry Display Comment OutputsSubfunction Keypad Entry Display Comment Compressors Unloaders CPA1Keypad Directory Test Keypad Directory Schedule Keypad Directory Service ConfigurationService Subfunction Keypad Entry Display Comment FactoryALARM/ALERT Subfunction Keypad Entry Display Comment RUN TimeStarts HISTORY²²Reset SET Points Subfunction Keypad Entry Display Comment SET PointsDemand SET Points Date and TimeExample 2 Ð Reading Current Operating Modes Example 1 Ð Reading Alarm CodesKeypad Display Comments Entry Response Operational and Mode Display Codes Example 3 Ð Using Test Function Reset Set PointsExample 5A Ð External Reset Reset AmountsExample 4 Ð Reading and Changing Chilled Fluid Set Point Measurement Method Input Data DescriptionExample 5C Ð Using Return Fluid Temperature Reset Keypad Display Comments Entry ResponsePower SwitchComm Ð Communications Bus PWRService Functions PasswordSUB Keypad Display Comment LoggedonTo Disable Demand Limit Example 8 Ð Setting Time of Day Day of Week4-20 mA Demand Limiting Adjustable Field Congurations Factory Conguration KeystrokesExample 9 Ð Using the Schedule Function Keypad Display Comment EntryProgramming Period Keypad Display Comment Entry Programming PeriodExample 10 Ð Holiday Schedule Function Enter DisplayTypical Stoppage Faults and Reset Types Stop position. Unit cannot start if these contacts areAlarm and Alert Codes LOCAL/ENABLE-STOP-CCNFSM CpcsWSM COM, Comm DGTDsio HPSComm CGF Subfunction. Groups Electronic Expansion Valve EXV EXV Cable Connections to EXV Driver Module, Dsio EXV Thermistor Replacement T1, T2, T7, T8 Temperature Voltage Resistance Drop Ohms Temperature Voltage Resistance Drop Thermistor and Pressure Transducer Locations Thermistor Locations Circuits a and B, Lead Compressor Only Lead Compressor Transducer and Thermistor Locations Module Address Selector Switch Locations Control ModulesAccessory Unloader Installation Installation 4 In/4 Out Module SIOTroubleshooting Standard and Accessory UnloadersPage Or HGBPR-A ²Or HGBPR-BHgbpr Ð COMExternally Powered Outdoor-Air TemperatureCWP Ð Chilled Water Fluid Pump TB Ð Terminal BlockRemote Alarm InterlocksPage Copyright 1995 Carrier Corporation

30GN040-420 specifications

The Carrier 30GN040-420 is a well-regarded model within the industry of chillers, designed to deliver efficient cooling solutions for a variety of commercial applications. Its compact design and advanced technology make it an ideal choice for businesses looking to optimize their HVAC systems.

One of the standout features of the Carrier 30GN series is its flexibility. This chiller model is available in a range of capacities, specifically from 40 to 420 tons, allowing for customized solutions based on specific cooling demands. Such versatility enables this unit to cater to a broad array of installations, from small commercial spaces to larger industrial facilities.

The Carrier 30GN040-420 utilizes a scroll compressor design, known for its reliability and efficiency. The scroll technology allows for a reduction in the number of moving parts, resulting in lower maintenance costs and increased durability. Additionally, the unit operates with environmentally friendly refrigerants such as R-410A, promoting sustainability without compromising performance.

Energy efficiency is another significant aspect of this model. The 30GN series is designed to provide high energy efficiency ratios (EER), which translates to lower operational costs for users over the lifespan of the unit. This is particularly beneficial in an era where energy costs are consistently rising.

The advanced controls found within the Carrier 30GN040-420 further enhance its performance and ease of use. The unit is equipped with a microprocessor-based control system that allows for precise temperature management while providing valuable diagnostic information. This feature not only improves the overall reliability of the system but also facilitates proactive maintenance, reducing the risk of unscheduled downtime.

Moreover, the design of the Carrier 30GN040-420 emphasizes quiet operation, making it suitable for environments where noise levels must be minimized. This characteristic is critical for applications in hospitals, schools, or office buildings, where a peaceful atmosphere is essential.

In summary, the Carrier 30GN040-420 chiller provides a robust solution for businesses requiring dependable and efficient cooling. Its features, including flexible capacity options, reliable scroll compressors, energy-efficient performance, advanced controls, and quiet operation, position it as a top choice for various commercial and industrial applications. As technology continues to evolve, models such as the 30GN series remain at the forefront, meeting the demands of modern HVAC needs while ensuring sustainability and efficiency.