Carrier 30GN040-420 operating instructions Cpcs, Fsm, Wsm

Page 50

Table 16 Ð Alarm and Alert Codes (cont)

 

ALARM

 

ACTION TAKEN

CIRCUIT

RESET

 

 

DISPLAY

OR

DESCRIPTION

BY CONTROL

PUMPDOWN

METHOD

PROBABLE CAUSE

 

ALERT

 

 

 

 

 

 

63

Alarm

Complete unit shutdown

Alarm only

Ð

Auto.

 

Check individual alarms

 

 

 

 

 

 

 

 

64

Alert

Loss of charge, circuit A

Circuit cannot start

Ð

Auto.

 

Refrigerant leak or transducer

65

Loss of charge, circuit B

Circuit cannot start

Ð

Auto.

 

failure

 

 

66

Alarm

FSM communication loss

FSM forces removed

Ð

Auto.

 

Wiring faulty or module failure

 

 

 

 

 

 

 

 

67

Alarm

Transducer calibration date code failure

Unit cannot start

Ð

Auto.

 

Incorrect date code entered

 

 

 

 

 

 

 

 

68,69

Ð

Not used

Ð

Ð

Ð

Ð

 

 

 

 

 

 

 

 

 

70

Alert

High leaving chilled ¯uid temperature

Alarm only

Ð

Auto.

 

Building load greater than unit capacity,

 

 

 

 

 

 

 

low water/brine ¯ow, or compressor

 

 

 

 

 

 

 

fault. Check for other alarms or alerts.

 

LEGEND

*Reset automatic ®rst time, manual if repeated same day.

CPCS

Ð Compressor Protection Control Module

 

FSM

Ð Flotronic™ System Manager

 

PS

Ð Power Supply

 

WSM

Ð Water System Manager

 

Possible causes of failure:

1.High-Pressure Switch Open Ð High-pressure switch for each compressor is wired in series with 24-v power that energizes compressor control relay. If high-pressure switch opens during operation, compressor stops. This is detected by microprocessor through the feedback terminals.

2.DSIO-LV or DSIO-EXV Module Failure Ð If a DSIO-LV relay module relay fails open or closed, microprocessor detects this, locks compressor off, and indicates an error.

3.Wiring Errors Ð If a wiring error exists causing CPCS, CR, or feedback switch to not function properly, micro- processor indicates an error.

4.Processor (PSIO) Failure Ð If hardware that monitors feedback switch fails, or processor fails to energize relay module relay to on, an error may be indicated.

NOTE: The control does not detect circuit breaker fail- ures. If a circuit breaker trips on lead compressor in a circuit, a low oil pressure failure is indicated. On the other compressors, no failure is indicated.

5.Ground Fault Module on 130-210 and associated modu- lar units (CGFA or CGFB) Open Ð Module contacts are in lead compressor circuits, but ground fault could be in any compressor in affected circuit.

Ground fault of any 040-110 and associated modular unit compressor (®eld-supplied accessory on 040-060 and 070, 60 Hz units; standard on 070, 50 Hz and 80-110 and as- sociated modular units) will cause a trip.

6.Checkout Procedure Ð Shut off main power to unit. Turn

on control power, then step through subfunc-

tion to proper compressor number (i.e., failure

code 5 is compressor B1). Next, energize the step. If step works correctly, then failure code is caused by:

·HPS (high-pressure switch) open

·Misplaced feedback wire from J4 and J5 terminals

·Ground wire and 24-v feeds reversed on one or more points on J3

Compressor Alarm/Alert Circuit Ð For compres- sor A1 circuit, processor closes contacts between J4 termi- nals 2 and 3 to start compressor. See Fig. 11A-11C. Safeties shown to left of J4 must be closed in order for power to reach compressor control relay, and the feedback input ter- minals on J3.

Failure of power to terminal 1 on J3, when contacts be- tween 2 and 3 on J4 should be closed, causes a code 1 alert.

Terminal 2 on J3 is the other leg of the compressor A1 feedback channel. It is connected to the 24-v common.

NOTE: Similar connections for each compressor can be fol- lowed on the unit wiring diagrams located on the unit.

Code 9 Leaving ¯uid thermistor failure (alarm) Code 10 Entering ¯uid thermistor failure (alarm)

If temperature measured by these thermistors is outside range of ±40 to 240 F (±40 to 116 C), unit shuts down after going through a normal pumpout. Reset is automatic if tem- perature returns to the acceptable range, and unit start-up fol- lows normal sequence. The cause of the fault is usually a bad thermistor, wiring error, or loose connection.

Code 19 Compressor A1 suction sensor failure (alert)

Code 20 Compressor B1 suction sensor failure (alert)

On units with thermistors, if temperature measured by these thermistors is outside the range of ±40 to 240 F (±40 to 116 C), affected circuit shuts down after going through a nor- mal pumpout. Other circuit continues to run. Reset is auto- matic if temperature returns to the acceptable range, and cir- cuit start-up follows normal sequence. The cause of this fault is usually a bad thermistor, wiring error, or loose connection.

On units with transducers, if the saturated suction tem- perature is greater than the leaving ¯uid temperature plus 10° F (5.5 C) for more than 5 minutes, the affected circuit shuts down (after going through normal pumpout). The reset is automatic if the saturated suction temperature returns to the acceptable range and start-up follows the normal se- quence. The cause of this fault is usually a bad transducer, a wiring error, or a loose connection.

50

Image 50
Contents Controls, Operation, Troubleshooting Tons Unit 30GN Unit Sizes and Modular CombinationsUnit Model Nominal Section a Section B 30GN Control Panel 040-110 Unit Shown Keypad and Display Module Also Called Hsio LOCAL/ENABLE-STOP-CCN Switch Positions and OperationLOCAL/ENABLE StopThermistors Compressor Protection Control Module CpcsThermistor and Transducer Locations Pressure TransducersSteps Ð Capacity Control StepsLoading Sequence a Loading Sequence B Unit Control Ð Capacity Control Steps, 040-070 Ð Capacity Control Steps, 040-070 A1²**, B1² Displacement Compressors Approx 080, 230B 60 HzA1²,B1² A1²**,B1²090, 245B 50 Hz Compressors Displacement090, 245B 60 Hz 100, 255B 270B 60 HzUnit Control Loading Sequence a Loading Sequence B 270B 50 Hz315B 50 Hz 110, 290B315B 60 Hz A1*,A2,B1 A1,A2,B1 A1²²,A2,B1,B2 A1*,A2,B1,B2 130 60 Hz 130 50 Hz 150, 230A, 245AA1,kB1 170, 270A 330A/B 60 Hz330A/B,360B 50 Hz 330A/B, 360B 50 Hz A1,B1 Approx 190, 290A, 360A/B390B 60 Hz A1**,B1210, 315A, 390A 420A/B 60 Hz420A/B 50 Hz Head Pressure Control PumpoutCondenser Fan Sequence FAN Arrangement FAN Numbers FAN Contactor Controlled byFunction USE Keys Keypad and Display Module UsageFunctions and Subfunctions Operative USE KeysAccessing Functions and Subfunctions Keypad DirectorySubfunction Keypad Entry Display Comment Stage TemperatureKeypad Directory Status SET PointInputs Subfunction Keypad Entry Display Comment PressureAnalog OutputsSubfunction Keypad Entry Display Comment Compressors Subfunction Keypad Entry Display CommentSubfunction Keypad Entry Display Comment Outputs Unloaders CPA1Keypad Directory Test Keypad Directory Schedule Service Keypad Directory ServiceConfiguration Subfunction Keypad Entry Display Comment FactoryStarts ALARM/ALERTSubfunction Keypad Entry Display Comment RUN Time HISTORY²²Demand SET Points Reset SET PointsSubfunction Keypad Entry Display Comment SET Points Date and TimeKeypad Display Comments Entry Response Example 1 Ð Reading Alarm CodesExample 2 Ð Reading Current Operating Modes Operational and Mode Display Codes Example 3 Ð Using Test Function Reset Set PointsExample 4 Ð Reading and Changing Chilled Fluid Set Point Example 5A Ð External ResetReset Amounts Measurement Method Input Data DescriptionExample 5C Ð Using Return Fluid Temperature Reset Keypad Display Comments Entry ResponseComm Ð Communications Bus PowerSwitch PWRSUB Keypad Display Comment Service FunctionsPassword LoggedonTo Disable Demand Limit Example 8 Ð Setting Time of Day Day of Week4-20 mA Demand Limiting Adjustable Field Congurations Factory Conguration KeystrokesProgramming Period Example 9 Ð Using the Schedule FunctionKeypad Display Comment Entry Keypad Display Comment Entry Programming PeriodExample 10 Ð Holiday Schedule Function Enter DisplayTypical Stoppage Faults and Reset Types Stop position. Unit cannot start if these contacts areAlarm and Alert Codes LOCAL/ENABLE-STOP-CCNWSM CpcsFSM Dsio COM, CommDGT HPSComm CGF Subfunction. Groups Electronic Expansion Valve EXV EXV Cable Connections to EXV Driver Module, Dsio EXV Thermistor Replacement T1, T2, T7, T8 Temperature Voltage Resistance Drop Ohms Temperature Voltage Resistance Drop Thermistor and Pressure Transducer Locations Thermistor Locations Circuits a and B, Lead Compressor Only Lead Compressor Transducer and Thermistor Locations Module Address Selector Switch Locations Control ModulesAccessory Unloader Installation Installation 4 In/4 Out Module SIOTroubleshooting Standard and Accessory UnloadersPage Hgbpr Ð Or HGBPR-A²Or HGBPR-B COMCWP Ð Chilled Water Fluid Pump Externally PoweredOutdoor-Air Temperature TB Ð Terminal BlockRemote Alarm InterlocksPage Copyright 1995 Carrier Corporation

30GN040-420 specifications

The Carrier 30GN040-420 is a well-regarded model within the industry of chillers, designed to deliver efficient cooling solutions for a variety of commercial applications. Its compact design and advanced technology make it an ideal choice for businesses looking to optimize their HVAC systems.

One of the standout features of the Carrier 30GN series is its flexibility. This chiller model is available in a range of capacities, specifically from 40 to 420 tons, allowing for customized solutions based on specific cooling demands. Such versatility enables this unit to cater to a broad array of installations, from small commercial spaces to larger industrial facilities.

The Carrier 30GN040-420 utilizes a scroll compressor design, known for its reliability and efficiency. The scroll technology allows for a reduction in the number of moving parts, resulting in lower maintenance costs and increased durability. Additionally, the unit operates with environmentally friendly refrigerants such as R-410A, promoting sustainability without compromising performance.

Energy efficiency is another significant aspect of this model. The 30GN series is designed to provide high energy efficiency ratios (EER), which translates to lower operational costs for users over the lifespan of the unit. This is particularly beneficial in an era where energy costs are consistently rising.

The advanced controls found within the Carrier 30GN040-420 further enhance its performance and ease of use. The unit is equipped with a microprocessor-based control system that allows for precise temperature management while providing valuable diagnostic information. This feature not only improves the overall reliability of the system but also facilitates proactive maintenance, reducing the risk of unscheduled downtime.

Moreover, the design of the Carrier 30GN040-420 emphasizes quiet operation, making it suitable for environments where noise levels must be minimized. This characteristic is critical for applications in hospitals, schools, or office buildings, where a peaceful atmosphere is essential.

In summary, the Carrier 30GN040-420 chiller provides a robust solution for businesses requiring dependable and efficient cooling. Its features, including flexible capacity options, reliable scroll compressors, energy-efficient performance, advanced controls, and quiet operation, position it as a top choice for various commercial and industrial applications. As technology continues to evolve, models such as the 30GN series remain at the forefront, meeting the demands of modern HVAC needs while ensuring sustainability and efficiency.