Carrier 30GN040-420 Example 4 Ð Reading and Changing Chilled Fluid Set Point, Reset Amounts

Page 39

Example 4 Ð Reading and Changing

Chilled Fluid Set Point

KEYPAD

DISPLAY

COMMENTS

ENTRY

RESPONSE

 

 

 

SET POINT

System set points

 

 

CSP1 44.0

Present occupied chilled ¯uid

 

 

set point is 44.0 F

 

 

CSP1 42.0

Press the

.

 

 

 

 

Display shows new occupied

 

 

chilled ¯uid set point is 42.0 F

 

CSP2 44.0

Present unoccupied chilled ¯uid

 

set point is 44.0 F

 

 

 

 

 

CSP2 50.0

Press the

. Display

 

 

 

 

shows new unoccupied chilled

 

 

¯uid set point is 50.0 F

 

RESET

Displays the maximum reset

 

 

set point. The minimum and

 

 

maximum reference reset

 

 

set points can also be displayed.

 

 

These set points are not

 

 

accessible when reset type has

 

 

been con®gured for NONE in

 

 

the service function.

 

 

 

 

 

Subfunction displays temperature reset set points.

Temperature Reset Based on Return Fluid Temperature Ð The control system is capable of providing leaving ¯uid tem- perature reset based on return ¯uid temperature. Because the temperature difference between leaving and return tempera- ture is a measure of the building load, return ¯uid tempera- ture reset is essentially an average building load reset method.

Under normal operation, the chiller maintains a constant leaving ¯uid temperature approximately equal to chilled fluid set point. As building load drops from 100% down to 0%, entering cooler ¯uid temperature drops in proportion to load. Thus, temperature drop across the cooler drops from a typi- cal 10 F (5.5 C) at full load to a theoretical 0° F (0° C) at no load. See Fig. 5.

At partial load, leaving chilled ¯uid temperature may be lower than required. If this is allowed to increase (reset), the efficiency of the chiller increases. Amount of reset can be de®ned as a function of cooler temperature drop, as shown in Fig. 5. This is a simple linear function that requires 3 pieces of input data for the set function that will vary de- pending on measurement method used as follows (see Table 11):

NOTE: Reset set points are not accessible unless the reset function is enabled ®rst. This is done as a ®eld

con®guration. Select one of the 4 choices for type of reset: Return Fluid Reset, External Temperature Reset, 4-20 mA External Signal Reset, or 4-20 mA Internal Signal Reset.

If dual set point control is enabled (see Field Wiring sec- tion on page 69), the amount of reset is applied to whichever set point is in effect at the time.

Examples 5A-5C demonstrate how to activate reset. Ex- ample 6 demonstrates how to change the type of reset. As- sume that reset is to be based on return ¯uid temperature, the desired reset range is to be 0° to 10° F (0° to 5.5° C) and full load is a 10° F (5.5° C) drop across the cooler. See Fig. 5.

Activating reset based on external temperature or 4-20 mA signal is done the same way, except the reference set point range is ±40° to 240° F (±40° to 115° C), or 4 to 20 mA depending on which method was selected at the ®eld con®guration step.

Example 5A Ð External Reset

In this example, the unit set point is reset from full load at 90 F (32 C) to a maximum reset value of 10 F (5.5 C) at 20 F (±6.7 C) outdoor ambient.

NOTE: All temperatures given in this example are in F.

KEYPAD

DISPLAY

COMMENTS

ENTRY

RESPONSE

 

 

 

 

 

FLD CFG

 

 

CRTYP 0

Scroll past to reset type

 

CRTYP 2

External reset selected

 

ERTYP 0

Scroll past to space

 

thermistor sensor selected

 

 

 

ERTYP 1

OAT selected

 

RESET

 

 

CRT2N 0

Temperature for no

 

reset is 0

 

 

 

CRT2N 90

Temperature for no

 

reset is 90

 

 

 

CRT2F 0

Temperature for maximum

 

reset is 0

 

 

 

CRT2F 20

Temperature for maximum

 

reset is 20

 

 

 

CRT2D 0

Maximum reset is 0

 

CRT2D 10

Maximum reset is 10

 

 

 

Table 11 Ð Reset Amounts

 

 

 

MEASUREMENT METHOD

 

 

INPUT DATA DESCRIPTION

4-20 mA

OAT/Occupied Space

Return Water

or Internal/External

 

 

 

 

 

 

Variable

Limits (F)

Variable

Limits (F)

Variable

Limits (F)

Maximum Reset Amount Ð Allowable range for

CRT1

±30 to 30

CRT2D

±30 to 30

CRT3D

±30 to 30

maximum amount which LWT is to be reset.

 

 

 

 

 

 

Maximum Reset Reference Ð Temperature at

Ð

Ð

CRT2F

±40 to 240

CRT3F

0 to 15

which maximum reset occurs.

 

 

 

 

 

 

Minimum Reset Reference Ð Temperature at

Ð

Ð

CRT2N

±40 to 240

CRT3N

0 to 15

which no reset occurs.

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

OAT Ð Outdoor-Air Temperature

 

 

 

 

 

 

LWT Ð Leaving Fluid Temperature

 

 

 

 

 

 

39

Image 39
Contents Controls, Operation, Troubleshooting Unit Sizes and Modular Combinations Unit Model Nominal Section a Section BTons Unit 30GN 30GN Control Panel 040-110 Unit Shown Stop LOCAL/ENABLE-STOP-CCN Switch Positions and OperationLOCAL/ENABLE Keypad and Display Module Also Called HsioPressure Transducers Compressor Protection Control Module CpcsThermistor and Transducer Locations ThermistorsÐ Capacity Control Steps Loading Sequence a Loading Sequence B Unit ControlSteps Ð Capacity Control Steps, 040-070 Ð Capacity Control Steps, 040-070 A1²**,B1² Displacement Compressors Approx 080, 230B 60 HzA1²,B1² A1²**, B1²Compressors Displacement 090, 245B 60 Hz090, 245B 50 Hz 270B 60 Hz 100, 255B270B 50 Hz Unit Control Loading Sequence a Loading Sequence B110, 290B 315B 60 Hz315B 50 Hz A1*,A2,B1 A1,A2,B1 A1²²,A2,B1,B2 A1*,A2,B1,B2 130 60 Hz 150, 230A, 245A 130 50 HzA1,kB1 330A/B 60 Hz 170, 270A330A/B,360B 50 Hz 330A/B, 360B 50 Hz A1**,B1 Approx 190, 290A, 360A/B390B 60 Hz A1,B1420A/B 60 Hz 210, 315A, 390A420A/B 50 Hz Pumpout Head Pressure ControlFAN Arrangement FAN Numbers FAN Contactor Controlled by Condenser Fan SequenceOperative USE Keys Keypad and Display Module UsageFunctions and Subfunctions Function USE KeysKeypad Directory Accessing Functions and SubfunctionsSET Point TemperatureKeypad Directory Status Subfunction Keypad Entry Display Comment StageOutputs Subfunction Keypad Entry Display Comment PressureAnalog InputsUnloaders CPA1 Subfunction Keypad Entry Display CommentSubfunction Keypad Entry Display Comment Outputs Subfunction Keypad Entry Display Comment CompressorsKeypad Directory Test Keypad Directory Schedule Subfunction Keypad Entry Display Comment Factory Keypad Directory ServiceConfiguration ServiceHISTORY²² ALARM/ALERTSubfunction Keypad Entry Display Comment RUN Time StartsDate and Time Reset SET PointsSubfunction Keypad Entry Display Comment SET Points Demand SET PointsExample 1 Ð Reading Alarm Codes Example 2 Ð Reading Current Operating ModesKeypad Display Comments Entry Response Operational and Mode Display Codes Reset Set Points Example 3 Ð Using Test FunctionMeasurement Method Input Data Description Example 5A Ð External ResetReset Amounts Example 4 Ð Reading and Changing Chilled Fluid Set PointKeypad Display Comments Entry Response Example 5C Ð Using Return Fluid Temperature ResetPWR PowerSwitch Comm Ð Communications BusLoggedon Service FunctionsPassword SUB Keypad Display CommentExample 8 Ð Setting Time of Day Day of Week To Disable Demand Limit4-20 mA Demand Limiting Factory Conguration Keystrokes Adjustable Field CongurationsKeypad Display Comment Entry Programming Period Example 9 Ð Using the Schedule FunctionKeypad Display Comment Entry Programming PeriodEnter Display Example 10 Ð Holiday Schedule FunctionStop position. Unit cannot start if these contacts are Typical Stoppage Faults and Reset TypesLOCAL/ENABLE-STOP-CCN Alarm and Alert CodesCpcs FSMWSM HPS COM, CommDGT DsioComm CGF Subfunction. Groups Electronic Expansion Valve EXV EXV Cable Connections to EXV Driver Module, Dsio EXV Thermistor Replacement T1, T2, T7, T8 Temperature Voltage Resistance Drop Ohms Temperature Voltage Resistance Drop Thermistor and Pressure Transducer Locations Thermistor Locations Circuits a and B, Lead Compressor Only Lead Compressor Transducer and Thermistor Locations Control Modules Module Address Selector Switch LocationsAccessory Unloader Installation 4 In/4 Out Module SIO InstallationStandard and Accessory Unloaders TroubleshootingPage COM Or HGBPR-A²Or HGBPR-B Hgbpr ÐTB Ð Terminal Block Externally PoweredOutdoor-Air Temperature CWP Ð Chilled Water Fluid PumpInterlocks Remote AlarmPage Copyright 1995 Carrier Corporation

30GN040-420 specifications

The Carrier 30GN040-420 is a well-regarded model within the industry of chillers, designed to deliver efficient cooling solutions for a variety of commercial applications. Its compact design and advanced technology make it an ideal choice for businesses looking to optimize their HVAC systems.

One of the standout features of the Carrier 30GN series is its flexibility. This chiller model is available in a range of capacities, specifically from 40 to 420 tons, allowing for customized solutions based on specific cooling demands. Such versatility enables this unit to cater to a broad array of installations, from small commercial spaces to larger industrial facilities.

The Carrier 30GN040-420 utilizes a scroll compressor design, known for its reliability and efficiency. The scroll technology allows for a reduction in the number of moving parts, resulting in lower maintenance costs and increased durability. Additionally, the unit operates with environmentally friendly refrigerants such as R-410A, promoting sustainability without compromising performance.

Energy efficiency is another significant aspect of this model. The 30GN series is designed to provide high energy efficiency ratios (EER), which translates to lower operational costs for users over the lifespan of the unit. This is particularly beneficial in an era where energy costs are consistently rising.

The advanced controls found within the Carrier 30GN040-420 further enhance its performance and ease of use. The unit is equipped with a microprocessor-based control system that allows for precise temperature management while providing valuable diagnostic information. This feature not only improves the overall reliability of the system but also facilitates proactive maintenance, reducing the risk of unscheduled downtime.

Moreover, the design of the Carrier 30GN040-420 emphasizes quiet operation, making it suitable for environments where noise levels must be minimized. This characteristic is critical for applications in hospitals, schools, or office buildings, where a peaceful atmosphere is essential.

In summary, the Carrier 30GN040-420 chiller provides a robust solution for businesses requiring dependable and efficient cooling. Its features, including flexible capacity options, reliable scroll compressors, energy-efficient performance, advanced controls, and quiet operation, position it as a top choice for various commercial and industrial applications. As technology continues to evolve, models such as the 30GN series remain at the forefront, meeting the demands of modern HVAC needs while ensuring sustainability and efficiency.