44Cyclades PM IPDU Installer/Administrator/User Guide

Arguments

<IPDU#> IPDU number in a daisy chain

<IPDU_ID> Identification string previously set by the id command

reset Resets the maximum humidity registered

Examples

To get the humidity for all units in a daisy chain, enter the following.

pm> humidity

IPDU #1: humidity: 42.3%. Maximum: 58.7%

IPDU #2: humidity: 44.0% Maximum: 72.6%

IPDU #3: Does not have humidity sensor.

To get the humidity for specific unit, provide the unit number as an argument, enter the following.

pm> humidity 2

IPDU #2: humidity: 44.0% Maximum: 72.6%

To reset the maximum humidity registered, use reset as a argument, enter the following.

pm>humidity reset

IPDU #1: Clearing maximum recorded humidity to zero.

IPDU #2: Clearing maximum recorded humidity to zero.

hwocp

The hwocp command checks the status of the hardware overcurrent protection. When overcurrent protection is on, the power is shut off. When the overcurrent protection is off or reset, the power is on and the PM IPDU is running in normal mode. If no string identifying the IPDU is given, all PM IPDUs in the daisy chain are affected by this command. This command is available to the admin user only.

Syntax

hwocp [<IPDU#><IPDU_ID> [reset]]

Arguments

<IPDU#> IPDU number in a daisy chain

<IPDU_ID> Identification string previously set by the id command

reset turn overcurrent protection off (normal operation)

Page 56