80Cyclades PM IPDU Installer/Administrator/User Guide

Figure C.1: PM10-L30A IPDU Circuit Breakers

PM10i-L30A IPDU

The PM10i-L30A IPDU has two 15-amp circuit breakers. The first circuit breaker controls outlets 6 through 10; the second controls outlets 1 through 5. In the event that the total current flow to outlets 6 through 10 exceeds 15 amps due to equipment connected to these outlets, the first circuit breaker will trip causing outlets 6 through 10 to shutdown. This does not affect outlets 1 through 5, which are controlled by the second circuit breaker.

As the PM10i-L30A IPDU has the controller (see Control Board in the figure below) powered from the line side of one of the circuit breakers, the whole unit will be inoperative only if both circuit breakers trip, but the controller will still function.

When either circuit breaker trips, only the power outlets of that segment will be affected, and half of the outlets remain operative.

Figure C.2: PM10i-L30A IPDU Circuit Breakers

PM10i-32A IPDU and PM10i-32Au IPDU

The PM10i-32A has two 16-amp circuit breakers. The first circuit breaker controls outlets 6 through 10; the second controls outlets 1 through 5. In the event that the total current flow to outlets 6 through 10 exceeds 16 amps due to equipment connected to these outlets, the first circuit breaker

Page 92
Image 92
Cyclades PM IPDU manual PM10i-L30A Ipdu, PM10i-32A Ipdu and PM10i-32Au Ipdu