48 Cyclades PM IPDU Installer/Administrator/User Guide
lock
The lock command locks an outlet or group of outlets in the current state. The response to this
command is a list of status lines, one per power port. This command works on all PM IPDUs in a
daisy chain.
Syntax
lock all|<outlet_string>
Arguments
<outlet_string> Outlet number, such as “5”, outlet name such as “sunfire”, or group of
outlets such as “1, 3-5”
Examples
To lock outlets 1, 2, and 6, enter the following.
name
The name command names an outlet. A maximum of 16 alphabetic and numeric characters (not
case sensitive) is allowed with these exceptions:
The hyphen (-), percent (%), and comma (,) characters are not allowed.
Numeric characters are not allowed as the first character of a name.
This command is available to the administrator user only.
Syntax
name <outlet_number> <name>
Arguments
<outlet number> Outlet number, such as “5”
<name> Desired outlet name
Examples
To name outlet 4 as nowhere, enter the following.
pm>lock 1,2,6
1: Outlet locked.
2: Outlet locked.
6: Outlet locked.
pm>name 4 nowhere
4: Outlet now named nowhere