36Cyclades PM IPDU Installer/Administrator/User Guide

Syntax

current [<IPDU#><IPDU_ID>]reset

Arguments

<IPDU#> IPDU number in a daisy chain

<IPDU_ID> Identification string previously set by the id command reset Clears the saved peak current value

Examples

To get the current status for all units, enter the following.

pm> current

IPDU #1: True RMS current: 2.2A. Maximum current: 9.4A

IPDU #2: True RMS current: 2.0A. Maximum current: 10.2A

To get the current status for a specific unit, enter the following.

pm> current 2

IPDU #2: True RMS current: 2.4A. Maximum current: 10.2A

To reset maximum current drawn, enter the following:

pm>current reset

IPDU #1: Clearing maximum recorded current to zero.

IPDU #2: Clearing maximum recorded current to zero.

currentprotection

The currentprotection command turns on and off the over current protection feature. The overcurrent protection does not let any outlet be turned on if the current drawn by the unit is greater than the current threshold configured with the command alarm. This command may also be used to display the current protection status. This command is available to the admin user only.

Syntax

currentprotection <onoffstatus>

Arguments

on Enables over current protection

off Disables over current protection

status Displays the current protection status