36 Cyclades PM IPDU Installer/Administrator/User Guide
Syntax
current [<IPDU#>|<IPDU_ID>]|reset
Arguments
<IPDU#> IPDU number in a daisy chain
<IPDU_ID> Identification string previously set by the id command
reset Clears the saved peak current value
Examples
To get the current status for all units, enter the following.
To get the current status for a specific unit, enter the following.
To reset maximum current drawn, enter the following:
currentprotection
The currentprotection command turns on and off the over current protection feature. The
overcurrent protection does not let any outlet be turned on if the current drawn by the unit is greater
than the current threshold configured with the command alarm. This command may also be used to
display the current protection status. This command is available to the admin user only.
Syntax
currentprotection <on|off|status>
Arguments
on Enables over current protection
off Disables over current protection
status Displays the current protection status
pm> current
IPDU #1: True RMS current: 2.2A. Maximum current: 9.4A
IPDU #2: True RMS current: 2.0A. Maximum current: 10.2A
pm> current 2
IPDU #2: True RMS current: 2.4A. Maximum current: 10.2A
pm>current reset
IPDU #1: Clearing maximum recorded current to zero.
IPDU #2: Clearing maximum recorded current to zero.