36Cyclades PM IPDU Installer/Administrator/User Guide
Syntax
current [<IPDU#><IPDU_ID>]reset
Arguments
<IPDU#> IPDU number in a daisy chain
<IPDU_ID> Identification string previously set by the id command reset Clears the saved peak current value
Examples
To get the current status for all units, enter the following.
pm> current
IPDU #1: True RMS current: 2.2A. Maximum current: 9.4A
IPDU #2: True RMS current: 2.0A. Maximum current: 10.2A
To get the current status for a specific unit, enter the following.
pm> current 2
IPDU #2: True RMS current: 2.4A. Maximum current: 10.2A
To reset maximum current drawn, enter the following:
pm>current reset
IPDU #1: Clearing maximum recorded current to zero.
IPDU #2: Clearing maximum recorded current to zero.
currentprotection
The currentprotection command turns on and off the over current protection feature. The overcurrent protection does not let any outlet be turned on if the current drawn by the unit is greater than the current threshold configured with the command alarm. This command may also be used to display the current protection status. This command is available to the admin user only.
Syntax
currentprotection <onoffstatus>
Arguments
on Enables over current protection
off Disables over current protection
status Displays the current protection status