Chapter 4: Command Line Interface

37

 

 

Examples

To display current protection status for all units, enter the following.

pm>currentprotection status

IPDU #1: Overcurrent protection is OFF.

IPDU #2: Overcurrent protection is OFF.

To enable current protection status for all units, enter the following.

pm>currentprotection ON

IPDU #1: Overcurrent protection turned ON.

IPDU #2: Overcurrent protection turned ON.

To disable current protection status for all units, enter the following.

pm>currentprotection off

IPDU #1: Overcurrent protection turned OFF.

IPDU #2: Overcurrent protection turned OFF.

currseg

The currseg command lets you view the current for the lower or upper segment of outlets. This command is only useful for IPDUs with dual current sensors (30A and 32A models). The lower segment (segment A) would be outlets 1-5 on a PM 10 series IPDU, and the upper segment (segment B) would be outlets 6-10 on a PM 10 series IPDU.

Syntax

currseg AB [reset]

Arguments

AB segment A or segment B

reset Clears the max recorded current for A & B.

Example

To view the current load of segment A, enter the following.

pm>currseg A

IPDU #1: True RMS current for segment A: 0.4A. Maximum current for

segment A: 0.

4A

Page 49
Image 49
Cyclades PM IPDU manual Currseg, Example, To view the current load of segment A, enter the following