Chapter 4: Command Line Interface

47

 

 

To set the interval of outlets 2, 4, 5, and 6 to a value of 2.4, enter the following.

pm>interval 2,4-6 2.4

2:Outlet power on interval set to 2.4 sec.

4:Outlet power on interval set to 2.4 sec.

5:Outlet power on interval set to 2.4 sec.

6:Outlet power on interval set to 2.4 sec.

list

The list command lists users created and outlets assigned to each user (for the administrator), or just the outlets assigned to the user logged in at the moment (for the regular user).

Syntax

list

Arguments

none

Examples

As admin, to list usernames and associated outlets in the internal database, enter the following.

pm>list

----------------------------------------------------------------

UserOutlets

----------------------------------------------------------------

gregg

1-3

george

4,

6-7, 9

mila

5,

8

sarah

4-9

----------------------------------------------------------------

As mila, to list mila’s name and associated outlets in the internal database, enter the following.

pm>list

----------------------------------------------------------------

UserOutlets

----------------------------------------------------------------

mila

5, 8

----------------------------------------------------------------