Carrier 30GN040-420 Factory Conguration Keystrokes, Adjustable Field Congurations

Page 45

Table 13 Ð Factory Con®guration Keystrokes

To change a con®guration enter the new con®guration

and press while on the correct con®guration.

 

SUB-

KEYPAD

DISPLAY

COMMENTS

FUNCTION

ENTRY

 

 

 

 

 

 

 

3 FACTORY

 

 

FACTORY

 

FACT CFG

CONFIGURATION

 

CFG

 

 

 

 

CODES

 

 

 

 

 

 

 

XXXXXXXX

Con®guration

 

 

 

Code 1

 

 

 

 

 

 

 

XXXXXXXX

Con®guration

 

 

 

Code 2

 

 

 

 

 

 

 

XXXXXXXX

Con®guration

 

 

 

Code 3

 

 

 

 

 

 

 

XXXXXXXX

Con®guration

 

 

 

Code 4

 

 

 

 

 

 

 

XXXXXXXX

Con®guration

 

 

 

Code 5

 

 

 

 

 

 

 

XXXXXXXX

Con®guration

 

 

 

Code 6

 

 

 

 

 

 

 

XXXXXXXX

Con®guration

 

 

 

Code 7

 

 

 

 

 

 

 

 

 

5 SERVICE

 

 

SERVICE

 

SRV CFG

CONFIGURATION

 

CFG

 

 

 

 

CODES

 

 

 

 

 

 

 

XXXXXXXX

Con®guration

 

 

 

Code 8

 

 

 

 

 

 

 

XXXXXXXX

Con®guration

 

 

 

Code 9

 

 

 

 

 

 

 

REFRIG X

Refrigerant Type

 

 

 

TDTYPE X

Pressure Transducer Select

 

 

 

OPS X

Oil Pressure Set Point

 

 

 

LPS X

Low Pressure Set Point

 

 

 

FANTYP X

Fan Staging Select

 

 

 

SH X

EXV Superheat Set Point

 

 

 

MOP X

EXV MOP Superheat

 

 

 

ZM X

Z Multiplier

 

 

 

 

 

 

LEGEND

 

 

MOP

Ð Maximum Operating Pressure

 

EXV

Ð Electronic Expansion Valve

 

When unit is con®gured for dual set point, chilled liquid pump relay is energized continuously, in both occupied and unoccupied modes. Occupied mode places occupied chilled water set point into effect; unoccupied mode places unoc- cupied chilled water set point into effect.

Scheduling Ð

is used to override any current sched-

ule in effect (for 0-4 hours). is used to activate a

clock for the scheduling function. - are used

to program schedules for speci®c occupied and unoccupied periods.

The schedule consists of from one to 8 occupied time pe- riods, set by the operator. These time periods can be ¯agged to be in effect or not in effect on each day of the week. The day begins at 00.00 and ends at 24.00. The machine is in unoccupied mode unless a scheduled time period is in effect. If an occupied period is to extend past midnight, it must be programmed in the following manner: occupied period must end at 24:00 hours (midnight); a new occupied period must be programmed to begin at 00:00 hours.

Table 14 Ð Adjustable Field Con®gurations

 

 

FIELD CONFIGURATION

 

 

FACTORY

SERVICE

 

 

 

CONFIGURATION

REPLACEMENT

 

 

ITEM AND CODES

 

 

 

 

 

CODE

CODE

 

 

 

 

 

 

 

 

 

 

CCN element address

 

 

001

001

(Entered by CCN Technician)

 

 

 

 

 

 

CCN Bus Number

 

 

000

000

(Entered by CCN Technician)

 

 

 

 

 

 

CCN Baud Rate

 

 

9600

9600

(Entered by CCN Technician)

 

 

 

 

 

 

Cooler Fluid Select

 

 

 

 

1

= Water (38 to 70 F

 

1 = Standard Models

1

 

 

[3.3 to 21 C] Set Point)

 

 

 

 

 

 

 

 

 

2

= Medium Brine (15 to 70 F

 

2 = Brine Models

 

 

 

[±9 to 21 C] Set Point)

 

 

 

 

Display Unit Select

 

 

 

 

0

= English

 

 

0

0

1

= Metric SI

 

 

 

 

Delay at Power Up

 

 

0

0

No. Circuit A Unloaders

 

 

 

 

0

= No Unloaders

 

0 = 30GN190-210*

0

1

= One Unloader

 

1 = 30GN040-170*

 

 

2

= Two Unloaders

 

 

 

 

No. Circuit B Unloaders

 

0 = 30GN040-070,

 

0

= No Unloaders

 

 

 

 

190-210*

0

1

= One Unloader

 

 

 

1 = 30GN080-170*

 

2

= Two Unloaders

 

 

 

 

 

 

Hot Gas Bypass Select

 

 

0

0

0

= No Valve

 

 

 

 

 

 

Loading Sequence Select

 

 

 

 

1

= Equal Circuit Loading

 

 

1

1

2

= Staged Circuit Loading

 

 

 

 

Lead/Lag Sequence Select

 

 

 

 

1

= Automatic

 

 

1

1

2

= Manual, Circuit A Leads

 

 

 

 

 

 

3

= Manual, Circuit B Leads

 

 

 

 

Oil Pressure Switch Select

 

 

 

 

0

= Not Used

 

 

0

0

1

= Air Cooled

 

 

 

 

Head Pressure Control Type

 

 

 

 

0

= Not Used

 

 

1

0

1

= Air Cooled

 

 

 

 

Head Pressure Control Method

 

 

 

 

1

= EXV Controlled

 

 

 

 

2

= Set Point Control for

 

 

 

 

 

 

Both Circuits

 

 

1

 

3

= Set Point Control for

 

 

 

 

 

2 = 040,045

1

 

 

Circuit A; EXV Control

 

 

 

 

 

 

Brine Units

 

 

 

for Circuit B

 

 

 

 

 

 

 

 

 

4

= Set Point Control for

 

 

 

 

 

 

Circuit B; EXV Control

 

 

 

 

 

 

for Circuit A

 

 

 

 

Motormaster Select

 

 

 

 

0

= None

 

 

0

0

2

= Indirect Control

 

 

 

 

Cooling Set Point

 

 

 

 

Control Select

 

 

 

 

0

= Single Set Point Control

 

 

 

 

1

= External Switch

 

 

0

0

 

 

Controlled Set Point

 

 

 

 

2

= Clock Controlled

 

 

 

 

 

 

Set Point

 

 

 

 

Cooling Reset Control Select

 

 

 

 

0

= No Reset

 

 

0

0

1

= 4-20 mA, Internally Powered

 

 

 

 

2

= External Temperature

 

 

 

 

 

 

Reset

 

 

 

 

3

= Return Fluid Reset

 

 

 

 

4

= 4-20 mA, Externally Powered

 

 

 

 

External Reset Sensor Select

 

 

 

 

0

= Thermistor Connected to

 

 

0

0

 

 

Options Module

 

 

 

 

 

 

 

 

1

= Obtained Through CCN

 

 

 

 

Outdoor-Air Sensor Select

 

 

 

 

0

= Not Selected

 

 

0

0

1

= Selected

 

 

 

 

Demand Limit Control Select

 

 

 

 

0

= No Demand Limiting

 

 

 

 

1

= Two External Switch Inputs

 

 

0

0

2

= Internal 4-20 mA Input

 

 

 

 

 

 

3

= CCN Loadshed

 

 

 

 

4

= External 4-20 mA Input

 

 

 

 

Ramp Load Select

 

 

 

 

(Pulldown Control)

 

 

1

0

0

= Disabled

 

 

 

 

 

 

1

= Enabled

 

 

 

 

Cooler Pump Interlock Select

 

 

 

 

0

= No Interlock

 

 

1

0

1

= With Interlock

 

 

 

 

Cooler Pump Control Select

 

 

 

 

0

= Not Controlled

 

 

1

0

1

= ON/OFF Controlled

 

 

 

 

Remote Alarm Option Select

 

 

 

 

0

= Not Selected

 

 

0

0

1

= Selected

 

 

 

 

Local/Enable-Stop-CCN

 

 

 

 

Switch Usage²

 

 

1

1

0

= Not Allowed

 

 

 

 

 

 

1

= Allowed

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

CCN

Ð Carrier Comfort Network

 

*And associated modular units.

EXV

Ð Electronic Expansion Valve

²For reset of alarms.

45

Image 45
Contents Controls, Operation, Troubleshooting Unit Sizes and Modular Combinations Unit Model Nominal Section a Section BTons Unit 30GN 30GN Control Panel 040-110 Unit Shown LOCAL/ENABLE LOCAL/ENABLE-STOP-CCN Switch Positions and OperationKeypad and Display Module Also Called Hsio StopThermistor and Transducer Locations Compressor Protection Control Module CpcsThermistors Pressure TransducersÐ Capacity Control Steps Loading Sequence a Loading Sequence B Unit ControlSteps Ð Capacity Control Steps, 040-070 Ð Capacity Control Steps, 040-070 A1²,B1² Displacement Compressors Approx 080, 230B 60 HzA1²**, B1² A1²**,B1²Compressors Displacement 090, 245B 60 Hz090, 245B 50 Hz 270B 60 Hz 100, 255B270B 50 Hz Unit Control Loading Sequence a Loading Sequence B110, 290B 315B 60 Hz315B 50 Hz A1*,A2,B1 A1,A2,B1 A1²²,A2,B1,B2 A1*,A2,B1,B2 130 60 Hz 150, 230A, 245A 130 50 HzA1,kB1 330A/B 60 Hz 170, 270A330A/B,360B 50 Hz 330A/B, 360B 50 Hz 390B 60 Hz Approx 190, 290A, 360A/BA1,B1 A1**,B1420A/B 60 Hz 210, 315A, 390A420A/B 50 Hz Pumpout Head Pressure ControlFAN Arrangement FAN Numbers FAN Contactor Controlled by Condenser Fan SequenceFunctions and Subfunctions Keypad and Display Module UsageFunction USE Keys Operative USE KeysKeypad Directory Accessing Functions and SubfunctionsKeypad Directory Status TemperatureSubfunction Keypad Entry Display Comment Stage SET PointAnalog Subfunction Keypad Entry Display Comment PressureInputs OutputsSubfunction Keypad Entry Display Comment Outputs Subfunction Keypad Entry Display CommentSubfunction Keypad Entry Display Comment Compressors Unloaders CPA1Keypad Directory Test Keypad Directory Schedule Configuration Keypad Directory ServiceService Subfunction Keypad Entry Display Comment FactorySubfunction Keypad Entry Display Comment RUN Time ALARM/ALERTStarts HISTORY²²Subfunction Keypad Entry Display Comment SET Points Reset SET PointsDemand SET Points Date and TimeExample 1 Ð Reading Alarm Codes Example 2 Ð Reading Current Operating ModesKeypad Display Comments Entry Response Operational and Mode Display Codes Reset Set Points Example 3 Ð Using Test FunctionReset Amounts Example 5A Ð External ResetExample 4 Ð Reading and Changing Chilled Fluid Set Point Measurement Method Input Data DescriptionKeypad Display Comments Entry Response Example 5C Ð Using Return Fluid Temperature ResetSwitch PowerComm Ð Communications Bus PWRPassword Service FunctionsSUB Keypad Display Comment LoggedonExample 8 Ð Setting Time of Day Day of Week To Disable Demand Limit4-20 mA Demand Limiting Factory Conguration Keystrokes Adjustable Field CongurationsKeypad Display Comment Entry Example 9 Ð Using the Schedule FunctionProgramming Period Keypad Display Comment Entry Programming PeriodEnter Display Example 10 Ð Holiday Schedule FunctionStop position. Unit cannot start if these contacts are Typical Stoppage Faults and Reset TypesLOCAL/ENABLE-STOP-CCN Alarm and Alert CodesCpcs FSMWSM DGT COM, CommDsio HPSComm CGF Subfunction. Groups Electronic Expansion Valve EXV EXV Cable Connections to EXV Driver Module, Dsio EXV Thermistor Replacement T1, T2, T7, T8 Temperature Voltage Resistance Drop Ohms Temperature Voltage Resistance Drop Thermistor and Pressure Transducer Locations Thermistor Locations Circuits a and B, Lead Compressor Only Lead Compressor Transducer and Thermistor Locations Control Modules Module Address Selector Switch LocationsAccessory Unloader Installation 4 In/4 Out Module SIO InstallationStandard and Accessory Unloaders TroubleshootingPage ²Or HGBPR-B Or HGBPR-AHgbpr Ð COMOutdoor-Air Temperature Externally PoweredCWP Ð Chilled Water Fluid Pump TB Ð Terminal BlockInterlocks Remote AlarmPage Copyright 1995 Carrier Corporation

30GN040-420 specifications

The Carrier 30GN040-420 is a well-regarded model within the industry of chillers, designed to deliver efficient cooling solutions for a variety of commercial applications. Its compact design and advanced technology make it an ideal choice for businesses looking to optimize their HVAC systems.

One of the standout features of the Carrier 30GN series is its flexibility. This chiller model is available in a range of capacities, specifically from 40 to 420 tons, allowing for customized solutions based on specific cooling demands. Such versatility enables this unit to cater to a broad array of installations, from small commercial spaces to larger industrial facilities.

The Carrier 30GN040-420 utilizes a scroll compressor design, known for its reliability and efficiency. The scroll technology allows for a reduction in the number of moving parts, resulting in lower maintenance costs and increased durability. Additionally, the unit operates with environmentally friendly refrigerants such as R-410A, promoting sustainability without compromising performance.

Energy efficiency is another significant aspect of this model. The 30GN series is designed to provide high energy efficiency ratios (EER), which translates to lower operational costs for users over the lifespan of the unit. This is particularly beneficial in an era where energy costs are consistently rising.

The advanced controls found within the Carrier 30GN040-420 further enhance its performance and ease of use. The unit is equipped with a microprocessor-based control system that allows for precise temperature management while providing valuable diagnostic information. This feature not only improves the overall reliability of the system but also facilitates proactive maintenance, reducing the risk of unscheduled downtime.

Moreover, the design of the Carrier 30GN040-420 emphasizes quiet operation, making it suitable for environments where noise levels must be minimized. This characteristic is critical for applications in hospitals, schools, or office buildings, where a peaceful atmosphere is essential.

In summary, the Carrier 30GN040-420 chiller provides a robust solution for businesses requiring dependable and efficient cooling. Its features, including flexible capacity options, reliable scroll compressors, energy-efficient performance, advanced controls, and quiet operation, position it as a top choice for various commercial and industrial applications. As technology continues to evolve, models such as the 30GN series remain at the forefront, meeting the demands of modern HVAC needs while ensuring sustainability and efficiency.