TROUBLE DIAGNOSIS
3. Cooling Cycle Heavy Repair
NO. | Items | Unit | Standards | Purposes | Remarks | ||
1 | Pipe and piping | Min. | Pipe:within 1 hour. | To protect | The opening time should be reduced to a | ||
| system opening time. |
| Comp:within | Moisture | half of the standards during rain and | ||
|
|
|
|
| 10 minutes. | Penetration. | rainy seasons (the penetration of water |
|
|
|
|
| Drier:within |
| into the pipe is dangerous). |
|
|
|
|
| 20 minutes. |
|
|
2 | Welding. |
| Nitrogen | Weld under | To protect | - Refet to repair note in each part. | |
|
|
|
| Pressure. | Nitrogen | oxide scale | - R134a refrigerant is more susceptible to |
|
|
|
|
| atmosphere | formation. | leaks than R12 and requires more care |
|
|
|
|
| (N2 pressure: |
| during welding. |
|
|
|
|
| 0.1~0.2 kg/cm2) |
| - Do not apply force to pipes before and |
|
|
|
|
|
|
| after welding to protect pipe from |
|
|
|
|
|
|
| cracking. |
3 | N2 sealed parts. | Confirm N2 | Confirm air leaking | To protect | - In case of evaporator parts, if it doesn't | ||
|
|
|
| leak. | sounds when | moisture | noise when removing rubber cap blow |
|
|
|
|
| removing rubber | penetration. | dry air or N2 gas for more than 1 min |
|
|
|
|
| cap. |
| use the parts. |
|
|
|
|
| Sound:usable |
|
|
|
|
|
|
| No sound:not usable |
|
|
4 | Refrigeration |
| Evacuation | Min. | More than | To remove |
|
| Cycle. |
| time |
| 40 minutes. | moisture. |
|
|
|
| Vacuum | Torr | Below 0.03(ref) |
| Note:Only applicable to the model |
|
|
| degree |
|
|
| equipped with reverse flow protect |
|
|
|
|
|
|
| plate. |
|
|
| Vacuum | EA | High and low |
| Vaccum efficiency can be improved by |
|
|
|
|
| Pressure sides are |
| operating compressor during evacuation. |
|
|
|
|
| evacuated at the |
|
|
|
|
|
|
| same time for |
|
|
|
|
|
|
| models above 200L |
|
|
|
|
| Vacuum | EA | Use R134a | To protect | The rubber pipes for R12 refrigerant shall |
|
|
| piping |
| exclusive | mixing of | be melted when they are used for R134a |
|
|
|
|
| manifold. | mineral and | refrigerant(causes of leak). |
|
|
|
|
|
| ester oils. |
|
|
|
| Pipe | EA | Use R134a | To protect |
|
|
|
| coupler |
| cxclusive. | R12 Refri- |
|
|
|
|
|
|
| gerant mixing. |
|
|
|
| Outlet |
| R134a exclusive. |
|
|
|
|
| (Socket) |
|
|
|
|
|
|
| Plug |
| R134a exclusive |
|
|
5 | Refrigerant weighing. | EA | Use R134a | Do not mix | - Do not weight the refrigerant at too hot or | ||
|
|
|
|
| exclusively. | with R12 | too cold an area.(25°C is adequate.) |
|
|
|
|
| Weighing | refrigerant. | - Use copper bombe |
|
|
|
|
| allowance:±5g |
| Socket:2SV Plug: 2PV R134a |
|
|
|
|
|
| Note:Do not burn | |
|
|
|
|
| Summer:+5g |
| welding. |
6 | Drier replacement. |
| To remove |
| |||
|
|
|
|
| for R134a refrigerator | the moisture |
|
|
|
|
|
| from pipe. |
| |
|
|
|
|
| for R12 refrigerator |
|
|
|
|
|
|
|
|
| |
|
|
|
|
| repairing refrigerator |
|
|
|
|
|
|
| cycle piping. |
|
|
7 | Leak check. |
|
| Detect | |||
|
|
|
|
| water for check. | refrigerant | Use electronic leak detector if oil leak is |
|
|
|
|
| it may be sucked | leak area. | not found. |
|
|
|
|
| into the pipe by. |
| |
|
|
|
|
|
|
| sensitive to halogen gas in the air. It also |
|
|
|
|
|
|
| can detect R141b in urethane. Please |
|
|
|
|
|
|
| practice, therfore, many times before use. |
|
|
|
|
|
|
|
|
NOTE) Please contact Songso company on