Cornelius IWCS227, IAC 322, IAC227, CR800, CR1200, CR1400, IWC530, IWC330, IWC322 Status Indicator

Page 24

 

 

 

 

 

STATUS INDICATOR

 

 

D6

Green LED

Condenser Fan

 

 

D10

Yellow LED

Left Water Curtain

 

 

D11

Green LED

Hot Gas Valve

 

 

D12

Green LED

Water Pump

 

 

D13

Yellow LED

Right Water Curtain

 

 

D14

Green LED

Compressor Contactor

 

 

D5

Red LED

Error

 

 

D15

Green LED

Dump Valve

 

 

 

 

 

Curtain Open

 

 

 

 

 

D13

Yellow LED

off

 

Right evaporator curtain open.

D10

Yellow LED

off

 

Left evaporator curtain open.

 

 

 

 

 

 

 

 

 

 

 

Pre-Chill Mode

 

 

 

 

 

D6

Green LED

(on or off)

 

Condenser fan cycles on & off depending upon condenser temperature.

D14

Green LED

(on)

 

Compressor contactor active - Compressor running.

D13

Yellow LED

(on)

 

Right evaporator curtain closed.

D10

Yellow LED

(on)

 

Left evaporator curtain closed (only if unit has two evaporators).

 

 

 

 

 

 

 

 

 

 

 

Ice-Making Mode

 

 

 

 

 

D6

Green LED

(on or off)

 

Condenser fan cycles on and off depending upon condenser temperature.

D12

Green LED

(on)

 

Water pump active.

D14

Green LED

(on)

 

Compressor contactor active - compressor running.

D13

Yellow LED

(on)

 

Right evaporator curtain closed.

D10

Yellow LED

(on)

 

Left evaporator curtain closed (only if unit has two evaporators).

 

 

 

 

 

 

 

 

 

 

 

Harvest Mode

 

 

 

 

 

D11

Green LED

(on)

 

Three seconds after water dump valve becomes active, the hot gas valve becomes active.

D12

Green LED

(on) 15 sec.

 

Fifteen seconds after water dump valve becomes active, the water pump deactivates.

D14

Green LED

(on)

 

Compressor contactor active - compressor running.

D15

Green LED

(on) 15 sec.

 

Water dump valve becomes active at the start of harvest. Water dump valve is active for

 

 

 

 

15 seconds.

D13

Yellow LED

(on)

 

Right evaporator curtain closed. When the ice falls and the curtain opens, the LED will turn off.

D10

Yellow LED

(on)

 

Same as D13 if there is a second (left) evaporator.

 

 

 

 

 

 

 

 

 

 

 

Error LED

 

 

 

 

 

D5

Red LED

(on)

 

EVAPORATOR OPEN THERMISTOR CIRCUIT 8 thermistor open / broken wire / poor connection.

 

 

 

 

Ice maker is SHUT DOWN. Consult service manual (Diagnostic Section) for troubleshooting

 

 

 

 

guide.

 

D5

Red LED

(on)

 

EVAPORATOR HIGH TEMP. ERROR: Six minutes into the Freeze cycle the suction line tempera8

 

 

 

 

ture failed to reach 40°F or below. Ice Maker is SHUT DOWN. Consult service manual (Diagnostic

 

 

 

 

Section) for troubleshooting guide.

D5

Red LED

(on)

 

TWO REPEATED FAILED HARVEST CYCLES 8 No ice drop.

D5

Red LED

Flashing, 1/sec

CONDENSER OPEN THERMISTOR CIRCUIT (Air Cooled only) 8 Thermistor open / broken wire /

 

 

 

 

poor connection. Ice Maker is SHUT DOWN. Consult service manual (Diagnostic Section) for

 

 

 

 

troubleshooting guide.

D5

Red LED

Flashing, 1/sec

CONDENSER LOW TEMPERATURE CONDITION. 8 Condenser midpoint reaches 36°F 8 Ice

 

 

 

 

Maker is SHUT DOWN.

D5

Red LED

Flashing, 1/sec

CONDENSER HIGH TEMPERATURE SAFETY SHUT DOWN.

 

 

 

 

 

 

12/1/94

21

166240004

Rev 3/4/96

 

 

Image 24
Contents Series Ice Cube Machine Table of Contents Table of Contents cont’d Model and Serial Location Series CuberSerial Number Explanation Remote Condenser Specification ICE Cuber SpecificationCR800 CR1200 CR1400 IAC322/330 IAC227 IWC322/330Specifications 60 HZ LRAIAC630 IWC630 IRC630 IAC830 IWC830 IRC830 IAC1030 IWC1030 IRC1030 IAC1030L IWC1030L IRC1030L IAC1230 IWC1230 IRC1230 IAC1448 IWC1448 IRC1448 Specifications 50 HZ Volts 220 Phase Hertz No. Wires +ground 220 12.5 75.9 Specifications 50 HZ, Remote Condenser CR800E50 CR1200E50 CR1400E50Freight Damage Claims Procedure GeneralInstallation Instructions Dispenser InstallationLocation of Equipment Equipment SET-UPIACS/IWCS Installation Check Points Plumbing ConnectionsElectrical START-UP and Check OUT Cleaning Procedures Prep CleaningOwner -OPERATOR Discard the ICESanitizing Procedures Dump CycleRH Evap Adjusting Bridge Thickness Total ICE CapacityICE Production Check LED Indicators Status Indicator Circuit Board Diagnostic Procedure Green Contactor Fan Dump ValveRestoring ICE Thickness Potentiometer to Factory Setting Making AdjustmentsReset Operation Component Function Circuit Board ETCTest Plug SensorsVoltage Selector Switch Stacking CableCondenser FAN Cycling Control Thermostatic Expansion ValvesStarving TXV Product Symptoms Water Regulating ValveService Stem Valves Moisture ContaminationCompressor Contactor Compressor & Starting Component CHECK-OUT Procedure RelayLeak Detection System Evacuation & RechargingSELF-CONTAINED Products Recovery AshraeRecycling ReclaimHigh Pressure Safety Switch Compressor RUN-ONAverage Operating Characteristics IACS227/IAC322/IAC330Freeze Cycle Harvest Cycle AverageIWCS227/IWC322/IWC330 IAC522/IAC530 IWC522/IWC530 IAC630 IWC630 IRC630 IAC830 IWC830 IRC830 IAC1030 IWC1030 IRC1030 IAC1230 IWC1230 IRC1230 IAC1448 IWC1448 IRC1448 Troubleshooting Compressor does not RUN, Circuit Board Indicator Lights onCuber not Operating Does not COOL, Circuit Board Indicator Lights Proximity Switch Light OUTProximity Switch Light on Compressor Runs butLong Freeze Cycle Water Flow AssociatedGeneral Long Harvest CyclesICE Weight Light AT TOP Plate and Heavy AT BottomSoft White ICE or Water a Pump not PumpingWater Dump Switch Condenser FAN Motor Only IAC 322 & IWC IAC 330 & IWCIacs 227 & Iwcs Volts 60 HZ IACS227E60, IWCS227E60 208/230V 60HZ IAC 522 & IWC IAC 530 & IWCIAC 830, IWC 830 & IRC IAC 630, IWC 630 & IRCIAC 1230, IWC 1230 & IRC IAC 1030, IWC 1030 & IRCIAC 1448, IWC 1448 & IRC Heat Shrink Tape Capacitor CR800, CR1200, & CR1400 Remote CondensersRefrigeration and Water Systems Refrigeration and water system Refrigeration and Water Systems Vavle Water Dump Valve Water Pump Refrigeration and Water System Remote Condenser Series Remote Ice Machine Installation Instructions Remote Condensers Liquid Refrigerant Line Discharge Correct Remote Condenser Location Physical Line-Set Length 55 Ft. Maximum 16.764 metersExamples Lengthening or Reducing the Line-Set Lengths Connection of Line-SetFinal Installation Start UpICE Cuber Specification Head Pressure Control Headmaster Remote System EVACUATION/RE-CHARGE EvacuationThis page Left Blank Intentionally One Cornelius Place Anoka, Minnesota 763 800

IAC530, IWCS227, IWC522, IAC522, IAC330 specifications

Cornelius has established itself as a leader in the field of beverage dispensing systems, and its range of machines, including the IAC 322, IAC 227, CR800, CR1200, and CR1400, showcases advanced technology and user-friendly designs tailored for various commercial environments.

The Cornelius IAC 322 is a compact and versatile air-cooled unit designed for high-volume beverage dispensing. It features an efficient refrigeration system that ensures optimal temperature control, providing beverages that are always served at the perfect temperature. Its user-friendly interface allows operators to manage settings easily, and its durable construction ensures longevity in busy environments.

The IAC 227 model is similar in design but is specifically optimized for lower volume settings. With a smaller footprint, it is ideal for cafes and small bars. This model also incorporates energy-efficient technology, minimizing power consumption without compromising performance. The IAC 227 maintains the same commitment to temperature control, ensuring each cup served enhances the customer experience.

Turning to the CR series, the CR800 stands out with its robust build and larger capacity. This unit is designed for establishments needing a reliable dispenser for a variety of carbonated beverages. The CR800's carbonation technology ensures each drink maintains the right level of fizz, contributing to a consistent taste. Its modular design facilitates easy maintenance and upgrades, making it a favorite among operators.

The CR1200 increases capacity, making it suitable for larger venues, including stadiums and large restaurants. This model incorporates advanced monitoring systems that track beverage levels and alert operators when supplies are low. The CR1200 also supports multiple beverage types, allowing for customization based on customer preference while maintaining ease of use.

Lastly, the CR1400 takes it a step further, combining high-capacity dispensing with cutting-edge technology. It features touchscreen controls for intuitive operation and automated cleaning systems that reduce downtime. The CR1400 is designed with a focus on sustainability, using recyclable materials and energy-efficient components to lessen its environmental impact while maintaining premium performance.

Together, the Cornelius IAC and CR series models represent the forefront of beverage dispensing technology, emphasizing efficiency, durability, and customer satisfaction. Whether for a small café or a large arena, these machines provide businesses with the tools they need to serve quality beverages consistently.