Step 2: Two screws installed in the top frame.
Open the doors and fasten the refrigerator with two screws through the holes underneath the top decoration panel. See FIG. 7.
FIG. 7
STEP 3: Two screws installed in the rear base.
See FIG. 8.
FIG. 8
Hole for drain water hose
TESTING LP GAS SAFETY
SHUT OFF
The gas safety shut off must be tested after the re- frigerator is connected to LP gas supply.
To test the gas safety shut off, proceed as follows:
1.Start the refrigerator according to the instructions, and switch to GAS mode. (See start up instructions “Select energy mode of operation”).
2.Check that the dot for GAS mode on the LED is on, check that the gas flame is lit.
3.Close the manual gas shut off valve at the back of the refrigerator. (See FIG. 1).
4.Wait until “ch LP” is flashing on the LED panel approximately 6 to 7 minutes.
5.Remove protection cover (see FIG. 1) and open the manual gas shut off valve. Do not change any button positions on the control panel. Apply a non- corrosive commercial bubble solution to the burner jet orifice.
6.No bubbles should appear at the opening of the burner jet orifice. The presence of bubbles indi- cates a defective gas safety shut off, and service is required.
7.If no bubbles were present at the burner jet orifice, it should be rinsed with fresh water. Be careful not to damage the burner jet orifice. Replace cover and press the main power ON/OFF button (1) OFF and back ON. Normal operation of the burner should return. Allow the burner to operate for a minimum of five minutes.
Failure to follow the sequence in securing refrigerator in enclosure can cause leakage between the frame and cabinet.
Any space between the counter, storage area or ceiling and top of the refrigerator greater den
Drain water hose
A hole must be drilled through flooring see FIG. 8.
The hole must be drilled in the cut out opening of the base plate at the rear of the refrigerator. The installer MUST make sure that the hose does not kink when run through the floor. Seal around the hose that goes through the drilled hole. If a longer hose than supplied is required to get the water to drain outside of the vehicle, the in- staller will have to supply the extra length of hose.
7