Cover roof opening if installation of the ERV unit will not be immediate. Failure to cover roof opening could result in water damage and/or serious personal injury.

Assemble the Roof Curb — Connect the curb side and the curb end. See Fig. 1. Insert the tabs on the curb end into the slots on the curb sides. Press firmly until the pieces lock into place. It may be necessary to exert additional force to the top of the curb to lock the pieces in place. Ensure the curb pieces are locked together prior to proceeding.

Repeat for all corners of the roof curb.

Prepare Roof Curb Location — Cut a hole in the roof for duct openings. See Fig. 2-5 for duct opening dimensions. Frame the opening to provide adequate structural support.

Install Deck Pans and Duct Supports — The roof curb may have a duct support and deck pans, depending on the model and application. Determine which end of the roof curb will be the duct end.

Install the deck pans on the roof curb with the insulation side facing up toward the ERV base. Install the duct support between the supply and return openings.

Set the Roof Curb — Fit the roof curb assembly by measuring across the corners of the curb to ensure a square fit. Set the roof curb over the roof opening. Level the curb by placing shims under the bottom flange of the curb. Secure the curb in place by welding or fastening the curb to the roof.

Cover the roof curb if installation of the ERV unit will not be immediate. Failure to cover the roof curb could result in water damage and/or serious personal injury.

Install Ductwork — Ductwork will be installed in the roof curb for vertical discharge and stand-alone applications. The duct will hang from the top of the curb. See Fig. 45 for stand- alone application airflow.

NOTE: Ductwork must be installed before the ERV unit is set in place.

Refer to Fig. 2-5 to determine the duct size required. Provide field manufactured duct and place into the supply and return openings in the curb.

Install Gaskets — The ERV roof curbs come with a gasketing package to provide a seal between the ERV unit and the top perimeter of the roof curb. Install the gasket around the top perimeter of the curb and around the supply and return opening.

NOTE: Some stand-alone curbs will not have duct openings). Gasket strips must fit tightly together, leaving no gaps for leakage.

IMPORTANT: Gasket installation is critical for water integrity. Improperly installed gaskets can result in air or water leaks, leading to poor unit performance.

Install Roofing Materials — Insulate and add a cant strip to the roof curb. Follow suggested and acceptable roofing practices

END

SIDE

Fig. 1 — Assembling the Roof Curb

for applying roofing materials. The roofing material should extend up to the wood nailer and be secured under the counter- flashing. Follow all local, national, and industry roofing standards. Refer to Fig. 6 for roofing recommendations.

COUPLED APPLICATIONS — The ERV unit can be in- stalled directly coupled to a Carrier rooftop unit. The connec- tion between the ERV and HVAC (Heating, Ventilation, and Air Conditioning) unit is made with the use of a transition. In a coupled rooftop application there is a separate roof curb for the HVAC curb and a separate roof curb for the ERV unit. See Fig. 4 and 5 for roof curb dimensions.

Locate the Roof Curb — Prior to locating the roof curb con- sider the structural support required for the rooftop system and, the duct drop location in relation to the joists. Allow sufficient space for service, clearance, and locations of vents or other sources of air. Refer to the rooftop installation instructions for more information regarding location considerations.

Assemble the Roof Curb — Connect the curb side and the curb end. Insert the tabs on the curb end into the slots on the curb sides. Press firmly until the pieces lock in to place. It may be necessary to exert additional force to the top of the curb to lock the pieces in place. Ensure the curb pieces are locked to- gether prior to proceeding.

Repeat for other corners of the roof curb.

NOTE: If lifting or moving the roof curb assembly hammer the tabs over 90 degrees.

Install Deck Pans and Duct Supports — The roof curb may have a duct support and deck pans, depending on the model and application. Refer to Fig. 2-5. Determine which end of the roof curb will be the duct end.

Install the deck pans on the roof curb with the insulation side facing up toward the ERV base. Install the duct support between the supply and return openings.

Install Locator Pieces — Some ERV roof curbs (62MA-CRB- 14MC and 62MB-CRB-14MC) will include locator pieces, which are to be attached to the ERV roof curb section. The locator pieces will help the installer ensure that the ERV and HVAC unit roof curbs are positioned properly. Attach the 2 side locator pieces to the ERV roof curb. Install the cover panel over the 2 sides and fasten in place.

2

Image 2
Contents Installation, Start-Up Service Instructions Assembling the Roof Curb All dimensions are in inches Roof curb shipped unassembled Roof Curb 62M040 for Stand-Alone ApplicationsDuct Sizes DimensionsDimensions 075,120 170-285†Field provided Dimensions 075,120 62M-A-CRB-14MC 30.562M-B-CRB-14MC 49.63 45.5 Required Service Clearances Front Rear Left Right62MD,ME040 Outdoor Unit Dimensions Front 27.5 Rear Left Right62MB,MC075,120 Indoor Unit Dimensions 39 in. service clearance required for ERV wheel removal62MD,ME075,120 Outdoor Unit Dimensions 55 in. service clearance required for ERV wheel removal View A-A62MD,ME170-285 Outdoor Unit Dimensions Required Service Clearances View A-A 62 in. service clearance required for ERV wheel removal62MD,ME330-640 Outdoor Unit Dimensions Rear Left 72 in. service clearance required for ERV wheel removalFront 62MD,ME750,950 Outdoor Unit Dimensions Top View RooftopUnit Curb 004-007Roof Curb Location Detail Unit Curb Support48/50PG 03-07 ReturnERV TOP View 67 3/848/50HJ,TF,TJ,TM Cannot be used. Use the 62M economizer instead 008,009 62M-ATR-HJ78-H 62M-A-CRB-14MC48/50PG Supply ReturnRooftop Unit Curb 62M-ATR-PG26-H Unit Curb Rooftop Unit CurbSide View A-A 62M-ATR-PG712-H78 1 012,014 62M-BTR-HJ1012-D 62M-B-CRB-14MC 62M-BTR-HJ36-D 62M-B-CRB-14MC008,009 62M-BTR-HJ78-D 62M-B-CRB-14MC 62M-BTR-HJ1012-H 62M-B-CRB-14MC 62M-BTR-HJ36-H 62M-B-CRB-14MC62M-BTR-HJ78-H 62M-B-CRB-14MC 48/50HJ Length is 891/16″ for 48/50TM028 units62M-BTR-HJ1525-D 62M-B-CRB-14S 015,017 62M-BTR-HJ1525-D 62M-B-CRB-14S62M-BTR-PG26-D 62M-A-CRB-14MC 62M-BTR-PG712-D 62M-A-CRB-14MCUnit 38 3/4 Curb Rooftop Unit Curb 38 3/4 49 5/8 ERV CurbCurb Detail 62M-BTR-PG26-H 62M-B-CRB-14MC 80 5 44 1120-28 62M-BTR-HG1525-H 62M-B-CRB-14MC 114.4 78.6 020-028 62M-BTR-HG1525-H 62M-B-CRB-14MC 114.4 78.648/50PG 20-28 62M-BTR-HG1525-D 62M-B-CRB-14MC 114.4 48/50HJ 020-028 62M-BTR-HG1525-D 62M-B-CRB-14MC 114.4Supply 012,014 62M-CTR-HJ1012-D 62M-C-CRB-14M62M-CTR-HJ1012-H 62M-C-CRB-14M 62M-CTR-HJ1012-HEC 62M-C-CRB-14MOptional Economizer Hood Exhaust hood Rooftop Unit AccessoryTransition Rooftop Unit Accessory 62M ERV Unit 62M330-640 74 1/448/50PG 08-14 62M-CTR-PG712-D 62M-C-CRB-14M 923/4 5315/16 62M ERV Unit ERV Curb ERV Energy Recovery Ventilator 60 11/32 ERV Curb48/50PG 20-28 62M-CTR-HG1525-H 62M-C-CRB-14M 114.4 48/50HJ 020-028 62M-CTR-HG1525-H 62M-B-CRB-14M 114.448/50PG 20-28 62M-CTR-HG1525-D 62M-C-CRB-14M 114.4 Hood rather than the bottom. The newHood will use the filters from the original 48/50HJ 020-028 62M-CTR-HG1525-D 62M-B-CRB-14M 114.4Rooftop Unit Economizer See Note Standard Rooftop Unit Curb 58 3/4 ERV Curb Rooftop Unit Curb 77 3/4 Outside airHood 62M Unit ERV Wheel ERV Curb 48/50A 020-060 62M-CTR-AJ2060-D 62M-C-CRB-14MERV Wheel Hood Used when coupled with 62M750,950 units62M ERV Unit Rooftop Standard factory economizer cannot be48/50PG 20-28 62M-DTR-HG1525-H 62M-D-CRB-14M 114.4 48/50HJ 020-028 62M-DTR-HG1525-H 62M-D-CRB-14M 114.4Relief Hood 62M750,950 ERV ERV CurbHood O/A Outdoor Air 48/50PG 20-28 62M-DTR-HG1525-D 62M-D-CRB-14M 114.4Unit 57 9/16 Curb 95.7 Rooftop Unit 62M ERV Unit86.25 Rooftop See curb Detail 77 3/4Side View Rigging Details Physical Data Make Electrical Connections Electrical Data Without VAV Option Size ERV Electrical Data With VAV Option NEC FLA MCA VFD Exhaust and Supply Power Supply PRE Disconnect Economizer End Switch Wiring Typical Wiring Schematic, High Voltage Secondary Energy Recovery VentilatorPrimary MCA Minimum Circuit AmpsHigh Voltage Low Voltage Disconnect Fiop START-UP 62M040-120 ERV Wheel Pressure Drop 62M550-950 ERV Wheel Pressure Drop* 62M550,640 62M750,95062M040 Supply Air Fan Performance Curves 62M075 Supply Air Fan Performance Curves 62M120 Supply Air Fan Performance Curves 2400 28002600 220062M225 Supply Air Fan Performance Curves 62M285 Supply Air Fan Performance Curves 4500 4000 4000 5500 50004500 3500 3000 2500500 000 000 50062M640 Supply Air Fan Performance Curves 62M750 Supply Air Fan Performance Curves 9000 8500 8000 7500 7000 6500 11500 11000 1050010000 9500 Blower Motor Pulley Adjustment Service Installing Wheel Segments 62M170-950 Units Motor WheelDrive Series wheelMaintenance Diameter Seal Adjustment Copyright 2006 Carrier Corporation Page START-UP Checklist