Carrier 62MC, 62ME, 62MD, 62MB specifications High Voltage Low Voltage

Page 57

Before performing service or maintenance operations on 62M unit, turn off power switches to unit. Multiple switches may exist. Electrical shock could cause personal injury or death.

See Note

57

 

LEGEND

COM

Common

DPDT

Dual Pole, Dual Throw Relay

ERV

Energy Recovery Ventilator

GRD

Ground

NC

Normally Closed

NO

Normally Open

WIRING LEGEND

High Voltage

Low Voltage

See Note

See Note

See Note

See Note

See Note

(OPTIONAL)

(OPTIONAL)

See Note

See Note

See Note

NOTES:

4.

Variable frequency drives are sensitive to the polarity of a 0 to 10 volt DC control signal. If the control

1.

When the 62M unit is used in a stand-alone application, the solid-state relay will be added to activate

 

source is acting properly and the voltage variance can be detected on the proper leads of the VFD,

 

ERV at approximately 2 volts. CO2 sensor output signal is sent to relay. Coupled units are activated

 

reverse the leads and the controller will respond.

 

through HVAC unit.

5.

Three-phase motor on all 62M750,950 units.

2.

Supply and Exhaust Variable Frequency Drive (VFD) terminals no. 25 and no. 2 can be used as a

6.

Color determined by primary voltage: Red — 200 vac, Orange — 230 vac, Black — 460 vac.

 

4 to 20 mA power control source, if desired.

7.

0 to 10 volt and 4 to 20 mA inputs are polarity sensitive. Reverse leads if signal fails to update controller.

3.

Transformer not necessary on all 62M750,950 units.

8.

DPDT relay may be substituted. If so, pins 2, 5 and 8 will not exist.

Fig. 52 — Typical Wiring Schematic, High/Low Voltage with Variable Air Volume Option

Image 57
Contents Installation, Start-Up Service Instructions Assembling the Roof Curb Roof Curb 62M040 for Stand-Alone Applications All dimensions are in inches Roof curb shipped unassembledDimensions 075,120 DimensionsDuct Sizes 170-285†Dimensions 075,120 62M-A-CRB-14MC 30.5 62M-B-CRB-14MC 49.63 45.5Field provided Front Rear Left Right Required Service ClearancesFront 27.5 Rear Left Right 62MD,ME040 Outdoor Unit Dimensions39 in. service clearance required for ERV wheel removal 62MB,MC075,120 Indoor Unit Dimensions62MD,ME075,120 Outdoor Unit Dimensions View A-A 55 in. service clearance required for ERV wheel removal62MD,ME170-285 Outdoor Unit Dimensions 62 in. service clearance required for ERV wheel removal Required Service Clearances View A-A62MD,ME330-640 Outdoor Unit Dimensions 72 in. service clearance required for ERV wheel removal FrontRear Left 62MD,ME750,950 Outdoor Unit Dimensions Unit Curb RooftopTop View 004-007Unit Curb Support Roof Curb Location DetailReturn 48/50PG 03-07ERV 67 3/8 TOP View48/50HJ,TF,TJ,TM 008,009 62M-ATR-HJ78-H 62M-A-CRB-14MC Cannot be used. Use the 62M economizer insteadSupply Return Rooftop Unit Curb48/50PG Side View A-A Unit Curb Rooftop Unit Curb62M-ATR-PG26-H 62M-ATR-PG712-H62M-BTR-HJ36-D 62M-B-CRB-14MC 008,009 62M-BTR-HJ78-D 62M-B-CRB-14MC78 1 012,014 62M-BTR-HJ1012-D 62M-B-CRB-14MC 62M-BTR-HJ36-H 62M-B-CRB-14MC 62M-BTR-HJ78-H 62M-B-CRB-14MC62M-BTR-HJ1012-H 62M-B-CRB-14MC 62M-BTR-HJ1525-D 62M-B-CRB-14S Length is 891/16″ for 48/50TM028 units48/50HJ 015,017 62M-BTR-HJ1525-D 62M-B-CRB-14S62M-BTR-PG712-D 62M-A-CRB-14MC 62M-BTR-PG26-D 62M-A-CRB-14MCCurb Detail Rooftop Unit Curb 38 3/4 49 5/8 ERV CurbUnit 38 3/4 Curb 62M-BTR-PG26-H 62M-B-CRB-14MC 80 5 44 11020-028 62M-BTR-HG1525-H 62M-B-CRB-14MC 114.4 78.6 20-28 62M-BTR-HG1525-H 62M-B-CRB-14MC 114.4 78.648/50HJ 020-028 62M-BTR-HG1525-D 62M-B-CRB-14MC 114.4 48/50PG 20-28 62M-BTR-HG1525-D 62M-B-CRB-14MC 114.4012,014 62M-CTR-HJ1012-D 62M-C-CRB-14M Supply62M-CTR-HJ1012-HEC 62M-C-CRB-14M 62M-CTR-HJ1012-H 62M-C-CRB-14MTransition Rooftop Unit Accessory 62M ERV Unit 62M330-640 Rooftop Unit AccessoryOptional Economizer Hood Exhaust hood 74 1/448/50PG 08-14 62M-CTR-PG712-D 62M-C-CRB-14M 923/4 5315/16 60 11/32 ERV Curb 62M ERV Unit ERV Curb ERV Energy Recovery Ventilator48/50HJ 020-028 62M-CTR-HG1525-H 62M-B-CRB-14M 114.4 48/50PG 20-28 62M-CTR-HG1525-H 62M-C-CRB-14M 114.4Hood will use the filters from the original Hood rather than the bottom. The new48/50PG 20-28 62M-CTR-HG1525-D 62M-C-CRB-14M 114.4 48/50HJ 020-028 62M-CTR-HG1525-D 62M-B-CRB-14M 114.4Hood 62M Unit ERV Wheel ERV Curb 58 3/4 ERV Curb Rooftop Unit Curb 77 3/4 Outside airRooftop Unit Economizer See Note Standard Rooftop Unit Curb 48/50A 020-060 62M-CTR-AJ2060-D 62M-C-CRB-14M62M ERV Unit Rooftop Used when coupled with 62M750,950 unitsERV Wheel Hood Standard factory economizer cannot be48/50HJ 020-028 62M-DTR-HG1525-H 62M-D-CRB-14M 114.4 48/50PG 20-28 62M-DTR-HG1525-H 62M-D-CRB-14M 114.4Hood O/A Outdoor Air 62M750,950 ERV ERV CurbRelief Hood 48/50PG 20-28 62M-DTR-HG1525-D 62M-D-CRB-14M 114.486.25 Rooftop Rooftop Unit 62M ERV UnitUnit 57 9/16 Curb 95.7 See curb Detail 77 3/4Side View Rigging Details Physical Data Make Electrical Connections Electrical Data Without VAV Option Size ERV Electrical Data With VAV Option NEC FLA MCA VFD Exhaust and Supply Power Supply PRE Disconnect Economizer End Switch Wiring Typical Wiring Schematic, High Voltage Primary Energy Recovery VentilatorSecondary MCA Minimum Circuit AmpsHigh Voltage Low Voltage Disconnect Fiop START-UP 62M040-120 ERV Wheel Pressure Drop 62M550,640 62M750,950 62M550-950 ERV Wheel Pressure Drop*62M040 Supply Air Fan Performance Curves 62M075 Supply Air Fan Performance Curves 62M120 Supply Air Fan Performance Curves 2600 28002400 220062M225 Supply Air Fan Performance Curves 62M285 Supply Air Fan Performance Curves 4500 4000 4500 5500 50004000 3500 3000 2500000 500 500 00062M640 Supply Air Fan Performance Curves 62M750 Supply Air Fan Performance Curves 11500 11000 10500 10000 95009000 8500 8000 7500 7000 6500 Blower Motor Pulley Adjustment Service Installing Wheel Segments 62M170-950 Units Drive WheelMotor Series wheelMaintenance Diameter Seal Adjustment Copyright 2006 Carrier Corporation Page START-UP Checklist