Carrier 62MB, 62ME, 62MC, 62MD specifications Start-Up

Page 59

START-UP

Do not operate the ERV unit without the filters and bird- screens installed, which prevent foreign objects from enter- ing the unit.

Use the following information and the Start-Up Checklist on page CL-1 to check unit PRIOR to start-up.

Unit Preparation — Check that the unit has been in- stalled in accordance with these installation instructions and all applicable codes.

Check all fasteners and set screws for tightness. This is critical for bearings and fan wheels. Also, if dampers are not motorized, check that they open and close without binding.

Internal Wiring — Check all electrical connections in the control box. Tighten as required.

Rain Hoods — Some ERV units will require the outside air and/or exhaust hood to be field installed. Caulk coupled flanges and screw to ERV unit.

NOTE: Units for indoor applications will not have rain hoods.

The outside air hood will include aluminum water entrain- ment filters, which should be in place prior to starting the unit.

Energy Recovery Wheel

DRIVE BELT — Turn the energy recovery wheel by hand to verify free operation. Inspect the belt, which drives the energy wheel rotation. Make sure the belt rides smoothly through the pulley and over the wheel rim.

AIR SEALS — Check that the air seals, located around the outside of the wheel and across the center, on both sides of wheel, are secure and in good condition. Air seals which are too tight will prevent proper rotation of the energy recovery wheel. Re-check the air seals for tightness.

Air seal clearance may be checked by placing a sheet of paper, like a feeler gage, against the wheel face. To adjust the air seals, loosen all eight seal retaining screws. These screws are located on the bearing support that spans the length of the cassette through the wheel center. Tighten the screws so the air seals tug slightly on the sheet of paper as the wheel is turned.

Replace the access door and apply power. Observe that the wheel rotates freely. If the wheel does not rotate or is binding, remove the cassette and adjust.

Blower Rotation — First, hand-rotate the blower to en- sure that the wheel is not rubbing against the scroll. If the blower is rotating in the wrong direction, the ERV unit will move some air, but will not perform properly.

To change the rotation, turn the power off and use the following procedure:

Single-phase units — Rewire the motor per the instruc- tions located on the motor.

Three-phase units — Interchange any two power leads. This can be done at the motor starter.

Airflow Settings and Adjustments — Most ERV units have factory-installed airflow test ports, which allow the balancer of the job to easily measure the static pressure across the ERV wheel, and thus the system airflow cfm levels. The static is measured on both the supply and return sides of the wheel. See Fig. 54-56.

To achieve the highest level of effectiveness, the airflow across the supply and return should be equal.

FACTORY SETTING — The ERV unit is factory set to achieve the maximum airflow cfm within the cabinet’s range. For example, a 62M170 unit has a range of 1,400 to 2,000 cfm airflow, and when shipped will be setup to achieve the 2,000 cfm airflow level. See Fig. 57-80.

CURVE SELECTION — Refer to the fan curve for the ERV unit being used for the application. See Fig. 57-80. Knowing the outside air intake cfm required and the external static pressure on the application, select the fan curve desired. The fan curve will indicate how to set the blower motor pulley to achieve the desired cfm level. If the job requirements are the same as the maximum ERV unit setup, then no blower adjust- ments are required.

ADJUST THE ERV BLOWER SPEED — If jobsite condi- tions require blower speeds other than the factory setting, then the ERV blower(s) will have to be adjusted. The fan curve will specify the number of turns to be made to the adjustable pulley on the blower motor. See Fig. 57-80.

Belt Drive Motors — Check pulley alignment and belt tension prior to set up. To change the speeds of the blowers:

1.Shut off power supply and tag disconnect.

2.Loosen belt tension.

3.Loosen adjustable (movable) pulley flange set screw. See Fig. 81.

4.Screw adjustable pulley side toward the fixed side to increase speed or away from fixed side to decrease speed. Increasing speed increases load on motor. Do not exceed maximum load for motor.

5.Set adjustable pulley side at nearest keyway of pulley hub and tighten set screw. See fan curves for speed change for each turn of the adjustable pulley.

Aligning Blower and Motor Pulleys — It is important that the pulleys be exactly in line with one another. See Fig. 82.

1.Loosen blower pulley set screw.

2.Align pulleys per illustration. Motor and blower shafts must be parallel.

3.Tighten pulley set screws.

Adjust Belt Tension — Loosen blower motor mounting nuts. and slide motor mounting plate away from fan scroll for proper belt tension (1/2-in. deflection with 7 to 10 lb of force.)

MEASURE MOTOR VOLTAGE, AMPERAGE AND FAN RPM — Measure and record the input voltage and motor amperage(s). To measure the fan rpm, the blower door will need to be opened. Minimize measurement time because the motor may over-amp with the door removed. Do not operate units with access doors/panels open as the motors will over- load. With the blower door closed, compare measured amps to the motor nameplate full load amps and correct if the ERV unit is over-amping.

BELT MAINTENANCE — Premature belt failures are fre- quently caused by improper belt tension (either too tight or too loose), or misaligned pulleys. The proper tension for operating a V-belt is the lowest tension at which the belts will not slip at peak load conditions. Check belt tension two weeks after start- up and periodically thereafter. It is very important that the drive pulleys remain in proper alignment after adjustments are made. Misalignment of pulleys will result in premature belt wear, noise, vibration, and power loss. Maintain belts and motors through the provided access panels. Refer to Fig. 82.

Text continued on page 74.

59

Image 59
Contents Installation, Start-Up Service Instructions Assembling the Roof Curb Roof Curb 62M040 for Stand-Alone Applications All dimensions are in inches Roof curb shipped unassembled170-285† DimensionsDimensions 075,120 Duct SizesField provided Dimensions 075,120 62M-A-CRB-14MC 30.562M-B-CRB-14MC 49.63 45.5 Front Rear Left Right Required Service ClearancesFront 27.5 Rear Left Right 62MD,ME040 Outdoor Unit Dimensions39 in. service clearance required for ERV wheel removal 62MB,MC075,120 Indoor Unit Dimensions62MD,ME075,120 Outdoor Unit Dimensions View A-A 55 in. service clearance required for ERV wheel removal62MD,ME170-285 Outdoor Unit Dimensions 62 in. service clearance required for ERV wheel removal Required Service Clearances View A-A62MD,ME330-640 Outdoor Unit Dimensions Rear Left 72 in. service clearance required for ERV wheel removalFront 62MD,ME750,950 Outdoor Unit Dimensions 004-007 RooftopUnit Curb Top ViewUnit Curb Support Roof Curb Location DetailReturn 48/50PG 03-07ERV 67 3/8 TOP View48/50HJ,TF,TJ,TM 008,009 62M-ATR-HJ78-H 62M-A-CRB-14MC Cannot be used. Use the 62M economizer instead48/50PG Supply ReturnRooftop Unit Curb 62M-ATR-PG712-H Unit Curb Rooftop Unit CurbSide View A-A 62M-ATR-PG26-H78 1 012,014 62M-BTR-HJ1012-D 62M-B-CRB-14MC 62M-BTR-HJ36-D 62M-B-CRB-14MC008,009 62M-BTR-HJ78-D 62M-B-CRB-14MC 62M-BTR-HJ1012-H 62M-B-CRB-14MC 62M-BTR-HJ36-H 62M-B-CRB-14MC62M-BTR-HJ78-H 62M-B-CRB-14MC 015,017 62M-BTR-HJ1525-D 62M-B-CRB-14S Length is 891/16″ for 48/50TM028 units62M-BTR-HJ1525-D 62M-B-CRB-14S 48/50HJ62M-BTR-PG712-D 62M-A-CRB-14MC 62M-BTR-PG26-D 62M-A-CRB-14MC62M-BTR-PG26-H 62M-B-CRB-14MC 80 5 44 11 Rooftop Unit Curb 38 3/4 49 5/8 ERV CurbCurb Detail Unit 38 3/4 Curb020-028 62M-BTR-HG1525-H 62M-B-CRB-14MC 114.4 78.6 20-28 62M-BTR-HG1525-H 62M-B-CRB-14MC 114.4 78.648/50HJ 020-028 62M-BTR-HG1525-D 62M-B-CRB-14MC 114.4 48/50PG 20-28 62M-BTR-HG1525-D 62M-B-CRB-14MC 114.4012,014 62M-CTR-HJ1012-D 62M-C-CRB-14M Supply62M-CTR-HJ1012-HEC 62M-C-CRB-14M 62M-CTR-HJ1012-H 62M-C-CRB-14M74 1/4 Rooftop Unit AccessoryTransition Rooftop Unit Accessory 62M ERV Unit 62M330-640 Optional Economizer Hood Exhaust hood48/50PG 08-14 62M-CTR-PG712-D 62M-C-CRB-14M 923/4 5315/16 60 11/32 ERV Curb 62M ERV Unit ERV Curb ERV Energy Recovery Ventilator48/50HJ 020-028 62M-CTR-HG1525-H 62M-B-CRB-14M 114.4 48/50PG 20-28 62M-CTR-HG1525-H 62M-C-CRB-14M 114.448/50HJ 020-028 62M-CTR-HG1525-D 62M-B-CRB-14M 114.4 Hood rather than the bottom. The newHood will use the filters from the original 48/50PG 20-28 62M-CTR-HG1525-D 62M-C-CRB-14M 114.448/50A 020-060 62M-CTR-AJ2060-D 62M-C-CRB-14M 58 3/4 ERV Curb Rooftop Unit Curb 77 3/4 Outside airHood 62M Unit ERV Wheel ERV Curb Rooftop Unit Economizer See Note Standard Rooftop Unit CurbStandard factory economizer cannot be Used when coupled with 62M750,950 units62M ERV Unit Rooftop ERV Wheel Hood48/50HJ 020-028 62M-DTR-HG1525-H 62M-D-CRB-14M 114.4 48/50PG 20-28 62M-DTR-HG1525-H 62M-D-CRB-14M 114.448/50PG 20-28 62M-DTR-HG1525-D 62M-D-CRB-14M 114.4 62M750,950 ERV ERV CurbHood O/A Outdoor Air Relief HoodSee curb Detail 77 3/4 Rooftop Unit 62M ERV Unit86.25 Rooftop Unit 57 9/16 Curb 95.7Side View Rigging Details Physical Data Make Electrical Connections Electrical Data Without VAV Option Size ERV Electrical Data With VAV Option NEC FLA MCA VFD Exhaust and Supply Power Supply PRE Disconnect Economizer End Switch Wiring Typical Wiring Schematic, High Voltage MCA Minimum Circuit Amps Energy Recovery VentilatorPrimary SecondaryHigh Voltage Low Voltage Disconnect Fiop START-UP 62M040-120 ERV Wheel Pressure Drop 62M550,640 62M750,950 62M550-950 ERV Wheel Pressure Drop*62M040 Supply Air Fan Performance Curves 62M075 Supply Air Fan Performance Curves 62M120 Supply Air Fan Performance Curves 2200 28002600 240062M225 Supply Air Fan Performance Curves 62M285 Supply Air Fan Performance Curves 4500 4000 3500 3000 2500 5500 50004500 4000000 500 500 00062M640 Supply Air Fan Performance Curves 62M750 Supply Air Fan Performance Curves 9000 8500 8000 7500 7000 6500 11500 11000 1050010000 9500 Blower Motor Pulley Adjustment Service Installing Wheel Segments 62M170-950 Units Series wheel WheelDrive MotorMaintenance Diameter Seal Adjustment Copyright 2006 Carrier Corporation Page START-UP Checklist