Carrier 62MD, 62ME, 62MC, 62MB specifications START-UP Checklist

Page 82

 

 

 

 

 

 

 

 

START-UP CHECKLIST

 

 

 

 

 

A. Project Information:

 

 

 

 

Start-Up Performed By ____________________________

 

 

 

 

Name __________________________________________________

 

 

 

 

 

 

 

 

Job Name

______________________________________________

 

 

 

 

 

 

 

 

ERV Unit Designation ____________________________________

 

 

 

 

 

 

 

 

Phone Number __________________________________________

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Design Information

 

 

 

 

 

 

 

 

 

 

Application

 

 

 

 

 

Coupled to rooftop unit or stand-alone.

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure

 

 

 

 

 

 

 

 

 

 

Supply Discharge

 

 

 

 

Down or horizontal (use horizontal for mated application)

 

 

 

Return Discharge

 

 

 

 

Down or horizontal (use horizontal for mated application)

 

 

 

Voltage/Phase

 

 

 

 

 

 

 

 

 

 

 

ERV Unit Part Number

 

 

 

 

 

 

 

 

 

 

Specify Rooftop Unit.

 

 

 

 

NOTE: Complete This Section for Coupled Applications Only

 

Model Number

 

 

 

 

 

 

 

 

 

 

 

HVAC Unit Discharge Type

 

 

 

 

Down discharge or horizontal discharge.

 

 

 

 

Roof Curb (Option)

Yes

No

 

 

 

 

 

 

 

14-in. Tall Roof Curb

 

 

Field install

 

 

 

 

 

 

 

Vibration Isolation Curb

 

 

Field install

 

 

 

 

 

 

 

Transition (Option)

 

 

 

 

NOTE: Complete This Section for Coupled Applications Only.

 

Rooftop Unit Discharge

 

 

 

 

Down or horizontal discharge rooftop unit.

 

 

 

 

Percent Outside Air

 

 

 

 

Outside air thru ERV unit as a percent of total rooftop unit cfm.

 

Transition Part Number

 

 

Field install

 

 

 

 

 

 

 

Inside Mounting Kit (Option)

Yes

No

 

NOTE: Complete This Section for Indoor Applications Only.

 

 

 

 

 

 

 

 

 

Factory installed

 

Removes rainhoods and adds duct flanges.

 

 

 

Electrical Disconnect (Option)

Yes

No

 

 

 

 

 

 

 

Fused

 

 

 

Factory installed

 

 

 

 

 

 

 

Switched

 

 

 

Factory installed

 

 

 

 

 

 

 

Two-Position Motorized Dampers (Option)

Yes

No

 

 

 

 

 

 

 

Outside Air Damper

 

 

Factory installed

 

 

 

 

 

 

 

Exhaust Air Damper

 

 

Factory installed

 

 

 

 

 

 

 

Economizer (Accessory for Rooftop Unit)

Yes

No

 

NOTE: Do Not Use With Wheel Bypass Option.

 

 

 

 

 

 

 

 

 

 

 

Field install

 

Special economizers required for some rooftop units. See the price pages.

 

Wheel Bypass With Stop Jog Control (Option)

Yes

No

 

NOTE: Do Not Use With Economizer Option.

 

 

 

 

 

 

 

 

 

 

 

Factory installed

 

Stops the ERV wheel rotation for free-cooling.

 

 

 

Stop Jog Control (Option)

Yes

No

 

NOTE: Use With Economizer Option.

 

 

 

 

 

 

 

 

 

 

 

 

Factory installed

 

Jogs the wheel during economizer mode to expel contaminants.

 

Pre-Heater (Option)

Yes

No

 

 

 

 

 

 

 

kW

 

 

 

 

 

 

 

Factory installed

 

 

 

 

 

 

 

Temp Control

 

 

 

 

 

 

 

 

 

 

 

Temp and Static Pressure Control

 

 

 

 

 

 

 

 

 

 

Frost Protection (Option)

Yes

No

 

NOTE: Do Not Use With Pre-Heater.

 

 

 

 

 

 

 

 

 

 

 

 

Factory installed

 

Defrosts wheel with exhaust air, by shutting down OA blower.

 

Low Temperature Lock Out (Option)

Yes

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory installed

 

Shut down ERV unit at low temperature set point.

 

 

 

Filter Maintenance Indicator (Option)

Yes

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory installed

 

Senses static pressure across OA filters (can be set for return filters).

 

ERV Blower Maintenance Indicator (Option)

Yes

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory installed

 

Monitors OA and EA blowers and sends signal on electrical spike.

 

ERV Wheel Maintenance Indicator (Option)

Yes

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory installed

 

Monitors ERV wheel and sends signal on electrical spike.

 

 

 

Airflow Monitor (Option)

Yes

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory installed

 

Gages display static pressure across wheel for OA and exhaust air.

 

ERV Control Timer (Option)

Yes

No

 

 

 

 

 

 

 

24 Volt Mounted in ERV

 

 

Factory installed

 

24 hour / 7 day timer mounted in ERV unit.

 

 

 

 

115 Volt Remote Mount

 

 

Field install

 

24 hour / 7 day timer field mounted in remote location.

 

 

 

VAV Control (Option)

Yes

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory installed

 

Provides independent VFD control for both OA and exhaust air.

 

CO2 Sensor (Option)

Yes

No

 

 

 

 

 

 

 

Wall Mount or Duct Mount

 

 

Field install

 

 

 

 

 

 

 

Duct Mount With External View

 

 

Field install

 

 

 

 

 

 

 

For 62M040 Cabinet Only

Yes

No

 

 

 

 

 

 

 

Equipment Support

 

 

Field installed

 

Use for coupled applications.

 

 

 

 

Base Rail Option

 

 

Factory installed

 

Must be ordered when 62M040 sits on a roof curb.

 

 

 

Hinged Door Option

 

 

Factory installed

 

Provides hinges and latches on both access doors.

 

 

 

2-in. Filters Option

 

 

Factory installed

 

Replaces the standard 1-in. filters with 2-in. high efficiency, pleated.

 

Door Interlock Safety Switches

 

 

Factory installed

 

Cuts power to ERV unit when access doors are opened during operation.

 

Test Port Option

 

 

 

Factory installed

 

Allows for convenient monitoring of static / airflow across ERV wheel.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

 

Book

 

1

4

 

Catalog No. 536-220

Printed in U.S.A.

Form 62M-1SI

Pg CL-1

1-06

Replaces: New

 

Tab

 

1a

12a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 82
Contents Installation, Start-Up Service Instructions Assembling the Roof Curb All dimensions are in inches Roof curb shipped unassembled Roof Curb 62M040 for Stand-Alone ApplicationsDuct Sizes DimensionsDimensions 075,120 170-285†62M-B-CRB-14MC 49.63 45.5 Dimensions 075,120 62M-A-CRB-14MC 30.5Field provided Required Service Clearances Front Rear Left Right62MD,ME040 Outdoor Unit Dimensions Front 27.5 Rear Left Right62MB,MC075,120 Indoor Unit Dimensions 39 in. service clearance required for ERV wheel removal62MD,ME075,120 Outdoor Unit Dimensions 55 in. service clearance required for ERV wheel removal View A-A62MD,ME170-285 Outdoor Unit Dimensions Required Service Clearances View A-A 62 in. service clearance required for ERV wheel removal62MD,ME330-640 Outdoor Unit Dimensions Front 72 in. service clearance required for ERV wheel removalRear Left 62MD,ME750,950 Outdoor Unit Dimensions Top View RooftopUnit Curb 004-007Roof Curb Location Detail Unit Curb Support48/50PG 03-07 ReturnERV TOP View 67 3/848/50HJ,TF,TJ,TM Cannot be used. Use the 62M economizer instead 008,009 62M-ATR-HJ78-H 62M-A-CRB-14MCRooftop Unit Curb Supply Return48/50PG 62M-ATR-PG26-H Unit Curb Rooftop Unit CurbSide View A-A 62M-ATR-PG712-H008,009 62M-BTR-HJ78-D 62M-B-CRB-14MC 62M-BTR-HJ36-D 62M-B-CRB-14MC78 1 012,014 62M-BTR-HJ1012-D 62M-B-CRB-14MC 62M-BTR-HJ78-H 62M-B-CRB-14MC 62M-BTR-HJ36-H 62M-B-CRB-14MC62M-BTR-HJ1012-H 62M-B-CRB-14MC 48/50HJ Length is 891/16″ for 48/50TM028 units62M-BTR-HJ1525-D 62M-B-CRB-14S 015,017 62M-BTR-HJ1525-D 62M-B-CRB-14S62M-BTR-PG26-D 62M-A-CRB-14MC 62M-BTR-PG712-D 62M-A-CRB-14MCUnit 38 3/4 Curb Rooftop Unit Curb 38 3/4 49 5/8 ERV CurbCurb Detail 62M-BTR-PG26-H 62M-B-CRB-14MC 80 5 44 1120-28 62M-BTR-HG1525-H 62M-B-CRB-14MC 114.4 78.6 020-028 62M-BTR-HG1525-H 62M-B-CRB-14MC 114.4 78.648/50PG 20-28 62M-BTR-HG1525-D 62M-B-CRB-14MC 114.4 48/50HJ 020-028 62M-BTR-HG1525-D 62M-B-CRB-14MC 114.4Supply 012,014 62M-CTR-HJ1012-D 62M-C-CRB-14M62M-CTR-HJ1012-H 62M-C-CRB-14M 62M-CTR-HJ1012-HEC 62M-C-CRB-14MOptional Economizer Hood Exhaust hood Rooftop Unit AccessoryTransition Rooftop Unit Accessory 62M ERV Unit 62M330-640 74 1/448/50PG 08-14 62M-CTR-PG712-D 62M-C-CRB-14M 923/4 5315/16 62M ERV Unit ERV Curb ERV Energy Recovery Ventilator 60 11/32 ERV Curb48/50PG 20-28 62M-CTR-HG1525-H 62M-C-CRB-14M 114.4 48/50HJ 020-028 62M-CTR-HG1525-H 62M-B-CRB-14M 114.448/50PG 20-28 62M-CTR-HG1525-D 62M-C-CRB-14M 114.4 Hood rather than the bottom. The newHood will use the filters from the original 48/50HJ 020-028 62M-CTR-HG1525-D 62M-B-CRB-14M 114.4Rooftop Unit Economizer See Note Standard Rooftop Unit Curb 58 3/4 ERV Curb Rooftop Unit Curb 77 3/4 Outside airHood 62M Unit ERV Wheel ERV Curb 48/50A 020-060 62M-CTR-AJ2060-D 62M-C-CRB-14MERV Wheel Hood Used when coupled with 62M750,950 units62M ERV Unit Rooftop Standard factory economizer cannot be48/50PG 20-28 62M-DTR-HG1525-H 62M-D-CRB-14M 114.4 48/50HJ 020-028 62M-DTR-HG1525-H 62M-D-CRB-14M 114.4Relief Hood 62M750,950 ERV ERV CurbHood O/A Outdoor Air 48/50PG 20-28 62M-DTR-HG1525-D 62M-D-CRB-14M 114.4Unit 57 9/16 Curb 95.7 Rooftop Unit 62M ERV Unit86.25 Rooftop See curb Detail 77 3/4Side View Rigging Details Physical Data Make Electrical Connections Electrical Data Without VAV Option Size ERV Electrical Data With VAV Option NEC FLA MCA VFD Exhaust and Supply Power Supply PRE Disconnect Economizer End Switch Wiring Typical Wiring Schematic, High Voltage Secondary Energy Recovery VentilatorPrimary MCA Minimum Circuit AmpsHigh Voltage Low Voltage Disconnect Fiop START-UP 62M040-120 ERV Wheel Pressure Drop 62M550-950 ERV Wheel Pressure Drop* 62M550,640 62M750,95062M040 Supply Air Fan Performance Curves 62M075 Supply Air Fan Performance Curves 62M120 Supply Air Fan Performance Curves 2400 28002600 220062M225 Supply Air Fan Performance Curves 62M285 Supply Air Fan Performance Curves 4500 4000 4000 5500 50004500 3500 3000 2500500 000 000 50062M640 Supply Air Fan Performance Curves 62M750 Supply Air Fan Performance Curves 10000 9500 11500 11000 105009000 8500 8000 7500 7000 6500 Blower Motor Pulley Adjustment Service Installing Wheel Segments 62M170-950 Units Motor WheelDrive Series wheelMaintenance Diameter Seal Adjustment Copyright 2006 Carrier Corporation Page START-UP Checklist