Blodgett KLT-G Series manual Installation, To Install

Page 6

INSTALLATION (Continued)

All units must be installed in such a manner that the flow of combustion and ventilation air are not obstructed. Provisions for an adequate air supply must also be provided. Do not obstruct side of the unit, as combustion air enters through this area.

Information on the construction and installation of ventilating hoods may be obtained from the standard for “Vapor Removal from Cooking Equipment”, NFPA No. 96 (latest edition), available from the National Fire Protection Association, Batterymarch Park, Quincy, MA, USA, 02269.

TO INSTALL

1.Uncrate carefully. Report any hidden freight damage to the freight company immediately.

2.The pressure relief valve is located at the right rear of the unit. This area should be kept clear and should not be in an area where operators will normally stand. The elbow on the relief valve should be turned toward the floor. A maximum 3 foot, 3/4" diameter pipe may be used to extend to the floor, but must not be piped directly to a drain. It must vent to the atmosphere.

3.Set the unit in place. Be certain to maintain minimum clearances as stated above.

4.To level the unit use a spirit level in all directions on the top of the kettle (lid up). Adjust the bottom foot on each leg to overcome an uneven floor.

5.Mark hole locations on floor through anchoring holes provided in flanged adjustable feet.

6.Remove appliance and drill holes in locations marked on floor and insert proper anchoring devices.

7.Set unit back in position and re-level left to right and front to back.

8.Bolt and anchor appliances securely to the floor.

9.Seal bolts and flanged feet with silastic or equivalent compound.

10.Appliance location must allow air supply to unit and obstruction free clearance for air opening into the combustion chamber.

11.Make service connections as indicated.

12.Check the pressure gauge on the front panel before operating. If the pressure gauge does not indicate green vacuum zone (below 0 psi), see “Re-establishing Vacuum” section under SERVICE, after completing installation instructions.

6

Image 6
Contents Important Notes for Installation and Operation KLT-G SeriesPage Table of Contents Description Service Connections Model GAS SupplyInstallation Installation Codes and Standards Sides Inches BackFloors NON-COMBUSTIBLE Installation To InstallGAS Connection Water Connection Electrical ConnectionPerformance Check Operation GAS Control InstructionsLighting Daily Shutdown Complete ShutdownRED Cooking Light Front Panel Controls Power SwitchGreen Ignition Light Amber LOW Water LightPressure Gauge Dial SettingThermostat Sight GlassPressure Relief Valve Daily OperationEND USE Tips GAS Saving Tips Cleaning Instructions Cleaning Instructions DRAW-OFF Valve CleaningDairy DRAW-OFF Valve Cleaning What to do if Surface Rust Appears Stainless SteelCleaning Instructions Monthly MaintenanceDaily Twice a Year minimumService General AdjustmentsManifold Pressure Pressure Switch To Adjust Pressure Switch Adding Water Low water light comes on For ReferenceRE-ESTABLISHING Vacuum Troubleshooting Problem AdjustmentsLook for Shutter Settings Kettle Size/Gas Type Natural PropaneShutter setting at Chemical Product and Company Identification Material Safety Data Sheet Preparation InformationMaterial Safety Data Sheet ProductHazards Identification Emergency Overview Product DOWFROST* HD Heat Transfer FLUID, DyedFirst AID Fire Fighting Measures Flammable PropertiesFlammability Limits Material Safety Data Sheet Handling and Storage Exposure CONTROLS/PERSONAL ProtectionPersonal Protective Equipment Physical and Chemical Properties Stability and ReactivityMutagenicity Environmental FateTransport Information Chemical Name CAS Number List RegulationsToxic Substances Control ACT Tsca PA1Canadian Regulations Canadian Environmental Protection ACT CepaOther Information