Lifebreath RNC95, RNC5-TPD, RNC200, RNC10, RNC120D, RNC155 Troubleshooting Symptom Cause Solution

Page 32

Troubleshooting

Symptom

Cause

Solution

Poor Air Flow

1/4” (6mm) mesh on the outside hoods is plugged

• clean exterior hoods or vents

 

filters plugged

• remove and clean filter

 

core obstructed

• remove and clean core

 

house grilles closed or blocked

• check and open grilles

 

dampers are closed if installed

• open and adjust dampers

 

poor power supply at site

• have electrician check supply voltage at house

 

duct is restricting HRV

• check duct installation

 

improper speed control setting

• increase the speed of the HRV

 

HRV air flow improperly balanced

• have contractor balance HRV

 

 

 

 

 

Supply air feels cold

poor location of supply grilles, the air flow may irritate

locate the grilles high on the walls or under the baseboards,

 

 

the occupant

 

install ceiling mounted diffuser or grilles so as not to directly

 

 

 

 

spill the supply air on the occupant (eg. over a sofa)

 

outdoor temperature extremely cold

turn down the HRV supply speed. A small duct heater (1kw)

 

 

 

 

could be used to temper the supply air

 

 

 

placement of furniture or closed doors is restricting the

 

 

 

 

movement of air in the home

 

 

 

if supply air is ducted into air handler return, the air handler fan

 

 

 

 

may need to run continuously to distribute ventilation air

 

 

 

 

comfortably

Dehumidistat is not Operating

improper connection to ventilator

check that the correct terminals have been used

 

external low voltage is shortened out by a staple or nail

check external wiring for a short

 

check dehumidistat setting it may be on OFF

set the dehumidistat at the desired setting

 

 

 

 

 

Humidity Levels are too High in Winter Condensation is appearing on the windows

dehumidistat is set too high

.• lifestyle of the occupants

moisture coming into the home from an unvented or unheated crawl space

moisture is remaining in the washroom/bathroom and kitchen areas

condensation seems to form in the spring and fall

HRV is set at too low a speed

set dehumidistat lower

avoid hanging clothes to dry, storing wood and venting clothes dryer inside. Heating wood may have to be moved outside

vent crawl space and place a vapor barrier on the floor of the crawl space

ducts from the washroom/bathroom should be sized to remove moist air as effectively as possible, use of a washroom/bathroom fan for short periods will remove additional moisture

timer or fan can be added to washroom/bathroom exhaust

on humid days, as the seasons change, some condensation may appear but the home’s air quality will remain high with some HRV use

increase speed of the HRV

Humidity Levels are too Low

dehumidistat control set too low

set dehumidistat higher

 

blower speed of HRV is too high

decrease HRV blower speed

 

lifestyle of occupants

humidity may have to be added through the use of humidifiers

 

HRV air flow may be improperly balanced

have a contractor balance HRV air flow

 

 

 

 

HRV and / or Ducts Frosting up

 

 

• Note: minimal frost build-up is expected on cores before

 

 

 

 

unit initiates defrost cycle functions

 

HRV air flow is improperly balanced

• have HVAC contractor balance the HRV

 

malfunction of the HRV defrost system

• ensure working properly.

 

 

 

 

Condensation or Ice Build Up in

incomplete vapor barrier around insulated duct

• tape and seal all joints

Insulated Duct to the Outside

a hole or tear in outer duct covering

• tape any holes or tears made in the outer duct covering

 

 

 

• ensure that the vapor barrier is completely sealed

 

 

 

 

Water in the bottom of the HRV

drain pans plugged

• ensure O-Ring on drain nozzle sits properly

 

improper connection of HRV drain lines

• look for kinks in line

 

HRV is not level

• check water drain connections

 

drain lines are obstructed

• make sure water drains properly from pan

 

HRV heat exchange core is not properly installed

 

 

 

 

 

 

 

20 Minute Timer Not Working

Wiring

disconnect external controls and run unit through self test. If

 

Faulty control

 

the unit runs through self test successfully, then the circuit

 

Faulty circuit board

 

board is okay.

 

 

 

check wiring connection.

 

 

 

make sure wires are connected to proper terminals.

 

 

 

test 20 Minute Timer, press and hold the button for 10 seconds

 

 

 

 

then release. The unit should run on high speed and then return

 

 

 

 

to normal operation when the button is released.

32

Image 32
Contents RNC Series RNC Electronics Table of ContentsIntroduction Dimensions RNC95 Engineering Data HRV Model RNC95Variable Port Location / Installation Model RNC95 only RNC95 Air FlowDimensions RNC155 Engineering Data HRV Model RNC155Dimensions RNC200 Engineering Data HRV Model RNC200RNC10 DimensionsEngineering Data HRV Model RNC10 Engineering Data HRV Model RNC20 RNC20Engineering Data HRV Model RNC5-TPD RNC5-TPDEngineering Data HRV Model RNC120D RNC120DOption 1 Horizontal Duct Configuration Dimensions inches Remote Control Devices Optional Main Control Features ON/OFF SwitchOptional Timers Minute TimerSuspending the HRV Suspending the HRV using Provided Hanging StrapsLocating and Suspending the HRV Location Selection Horizontal Installation Suspending the RNC120DDrain Connections Drain Connection HRV Only Trap HRV onlyInstallation Methods Three Methods of Installation Simplified InstallationsPartially Dedicated Installations Fully Dedicated InstallationsSimplified Installation Return/Return Method Four Port ModelsPartially Dedicated Installation Installation manualFully Dedicated Installation Four Port Models Models RNC155/RNC200Weatherhood Installation Grilles and WeatherhoodsLifebreath Kitchen Grille Lifebreath TechgrilleRemote Control Connections ElectricalChanging OFF to Standby Increasing Low Speed to Medium LowDigital Electronic Timer DET Green LEDDefrost Cycle DIP Switch Settings Increasing the Run Time Factory Setting OptionDamper Defrost 5 port models OFF DFR3Prior to balancing, ensure that Balancing ProcedureAir Flow Balancing Air Flow Balancing Pitot Tube and Gauge DuctPitot Tube Air Flow Balancing Kit Balancing Collar InstructionsProcedure StepStale Air Magnehelic Door Port Balancing KitInterlocking HRV Operation to an Airhandler/Furnace Blower Wiring Diagrams Model RNC5-TPD Defrost DetailsWiring Diagrams RNC120D HRV Control Box Wiring Diagrams RNC95/RNC10/RNC20/RNC155/RNC200 RNC3Troubleshooting Symptom Cause Solution HRV Page

RNC155, RNC20, RNC95, RNC120D, RNC10 specifications

Lifebreath is renowned for its commitment to providing high-quality air ventilation products that enhance indoor air quality. Among its popular models are the RNC95, RNC5-TPD, RNC155, RNC10, and RNC200, each offering unique features and technologies tailored to different ventilation needs.

The Lifebreath RNC95 is known for its efficient performance, featuring a high-efficiency heat exchanger that recovers up to 95% of the energy from outgoing air. This model is perfect for residential use, where energy efficiency is paramount. The compact design allows for easy installation, and it is equipped with advanced controls that enable smart operation, ensuring optimal air quality with minimal energy consumption.

On the other hand, the RNC5-TPD is designed for tight spaces without compromising on performance. It provides a versatile solution with a variable speed motor that adjusts airflow to match the specific requirements of the environment. This model also features a quick-change filter system, making maintenance a breeze. Its energy recovery capabilities help reduce heating and cooling costs, appealing to eco-conscious consumers.

The RNC155 stands out due to its robust capacity, catering to larger living spaces or commercial environments. This unit integrates advanced airflow management technology, allowing users to balance air distribution effectively throughout the building. The unit's energy-efficient operation is complemented by integrated controls that can be programmed for optimal performance based on occupancy and air quality levels.

The RNC10 offers a budget-friendly option while maintaining effective ventilation. It is compact and lightweight, making it ideal for smaller rooms or apartments. Despite its size, it features a reliable heat recovery system that significantly lowers energy costs and enhances comfort.

Finally, the RNC200 is a powerhouse model designed for larger commercial spaces. It boasts an impressive airflow capacity, making it suitable for demanding environments. This unit includes sophisticated monitoring systems that provide real-time data on air quality and system performance, ensuring that the air remains fresh and healthy. Additionally, its customizable setup allows for integration with other HVAC systems, further enhancing its functionality.

In summary, Lifebreath models like RNC95, RNC5-TPD, RNC155, RNC10, and RNC200 exemplify cutting-edge ventilation technology. Their distinct features cater to various needs, from residential to commercial applications, ensuring that users enjoy optimal indoor air quality while minimizing energy expenditure.