Lifebreath RNC120D manual Air Flow Balancing, Prior to balancing, ensure that, Balancing Procedure

Page 24

Air Flow Balancing

It is necessary to have balanced air flow in an HRV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit. If the air flow is not properly balanced, then:

The HRV may not operate at its maximum efficiency

A negative or positive air pressure may occur in the house

The unit may not defrost properly

Failure to balance HRV properly may void warranty

CAUTION

Ensure balanced air flow in HRV. Excessive positive pressure may drive moist indoor air into the external walls of the building where it may condense (in cold weather) and degrade structural components. May also cause key holes to freeze up.

Excessive negative pressure may have several undesirable effects. In some geographic locations, soil gases such as methane and radon gas may be drawn into the home through basement/ground contact areas.

Read the Application Warning in Clearances & Requirements section of this manual!

WARNING

Ensure balanced air flow in HRV/ERV. Excessive negative pressure may also cause the back- drafting of vented combustion equipment.

Prior to balancing, ensure that:

1.All sealing of the duct system has been completed.

2.All of the HRV’s components are in place and functioning properly.

3.Balancing dampers are fully open.

4.Unit is on HIGH speed.

5.Air flow in branch lines to specific areas of the house should be adjusted first prior to balancing the unit. A smoke pencil used at the grilles is a good indicator of each branch line's relative air flow.

6.After taking readings of both the stale air to the HRV duct and fresh air to the house duct, the duct with the lower CFM ([L/s] velocity) reading should be left alone, while the duct with the higher reading should be dampered back to match the lower reading.

7.Return unit to appropriate fan speed for normal operation

8.A field-supplied balancing damper for the stale air side is required for system balancing.

Balancing Procedure

The following is a method of field balancing an HRV using a Pitot tube, which is advantageous in situations when flow stations are not installed in the duct system. Procedure should be performed with the HRV on high speed.

The first step is to operate all mechanical systems on high speed, which have an influence on the ventilation system, i.e. the HRV itself and the air handler, if applicable. This will provide the maximum pressure that the HRV will need to overcome, and allow for a more accurate balance of the unit.

Drill a small hole in the duct (about 3/16"), three feet downstream of any elbows or bends, and one foot upstream of any elbows or bends. These are recommended distances but the actual installation may limit the amount of straight duct.

The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0.25 in. (0-62 Pa) of water, preferably to 3 digits of resolution. The tube coming out of the end of the Pitot is connected to the high pressure side of the gauge. The tube coming out of the branch of the Pitot is connected to the low pressure or reference side of the gauge.

Insert the Pitot tube into the duct; pointing the tip into the air flow.

For general balancing it is sufficient to move the Pitot tube around in the duct and take an average or typical reading. Repeat this procedure in the other (supply or return) duct. Determine which duct has the highest air flow (highest reading on the gauge). Then damper that air flow back to match the lower reading from the other duct. The flow should now be balanced.

Actual air flow can be determined from the gauge reading. The value read on the gauge is called the velocity pressure. The Pitot tube comes with a chart that will give the air flow velocity based on the velocity pressure indicated by the gauge. This velocity will be in either feet per minute or meters per second. To determine the actual air flow, the velocity is multiplied by the cross sectional area of the duct being measured.

This is an example for determining the air flow in a 6" duct.

The Pitot tube reading was 0.025 inches of water.

From the chart, this is 640 feet per minute.

The 6" duct has a cross sectional area of

= [3.14 x (6"÷12)2]÷4

= 0.2 square feet

The air flow is then:

640 ft./min. x 0.2 square feet = 128 cfm

For your convenience, the cross sectional area of some common round duct is listed below:

DUCT DIAM. (inches)

CROSS SECTION AREA (sq. ft.)

5

0.14

6

0.20

7

0.27

The accuracy of the air flow reading will be affected by how close to any elbows or bends the readings are taken. Accuracy can be increased by taking an average of multiple readings as outlined in the literature supplied with the Pitot tube.

24

Image 24
Contents RNC Series Table of Contents IntroductionRNC Electronics Dimensions RNC95 Engineering Data HRV Model RNC95Variable Port Location / Installation Model RNC95 only RNC95 Air FlowDimensions RNC155 Engineering Data HRV Model RNC155Dimensions RNC200 Engineering Data HRV Model RNC200Dimensions Engineering Data HRV Model RNC10RNC10 Engineering Data HRV Model RNC20 RNC20Engineering Data HRV Model RNC5-TPD RNC5-TPDEngineering Data HRV Model RNC120D RNC120DOption 1 Horizontal Duct Configuration Dimensions inches Remote Control Devices Optional Main Control Features ON/OFF SwitchOptional Timers Minute TimerSuspending the HRV using Provided Hanging Straps Locating and Suspending the HRV Location SelectionSuspending the HRV Horizontal Installation Suspending the RNC120DDrain Connections Drain Connection HRV Only Trap HRV onlyInstallation Methods Three Methods of Installation Simplified InstallationsPartially Dedicated Installations Fully Dedicated InstallationsSimplified Installation Return/Return Method Four Port ModelsPartially Dedicated Installation Installation manualFully Dedicated Installation Four Port Models Models RNC155/RNC200Weatherhood Installation Grilles and WeatherhoodsLifebreath Kitchen Grille Lifebreath TechgrilleRemote Control Connections ElectricalChanging OFF to Standby Increasing Low Speed to Medium LowDigital Electronic Timer DET Green LEDDefrost Cycle DIP Switch Settings Increasing the Run Time Factory Setting OptionDamper Defrost 5 port models OFF DFR3Balancing Procedure Air Flow BalancingPrior to balancing, ensure that Air Flow Balancing Pitot Tube and Gauge DuctPitot Tube Air Flow Balancing Kit Balancing Collar InstructionsProcedure StepStale Air Magnehelic Door Port Balancing KitInterlocking HRV Operation to an Airhandler/Furnace Blower Wiring Diagrams Model RNC5-TPD Defrost DetailsWiring Diagrams RNC120D HRV Control Box Wiring Diagrams RNC95/RNC10/RNC20/RNC155/RNC200 RNC3Troubleshooting Symptom Cause Solution HRV Page

RNC155, RNC20, RNC95, RNC120D, RNC10 specifications

Lifebreath is renowned for its commitment to providing high-quality air ventilation products that enhance indoor air quality. Among its popular models are the RNC95, RNC5-TPD, RNC155, RNC10, and RNC200, each offering unique features and technologies tailored to different ventilation needs.

The Lifebreath RNC95 is known for its efficient performance, featuring a high-efficiency heat exchanger that recovers up to 95% of the energy from outgoing air. This model is perfect for residential use, where energy efficiency is paramount. The compact design allows for easy installation, and it is equipped with advanced controls that enable smart operation, ensuring optimal air quality with minimal energy consumption.

On the other hand, the RNC5-TPD is designed for tight spaces without compromising on performance. It provides a versatile solution with a variable speed motor that adjusts airflow to match the specific requirements of the environment. This model also features a quick-change filter system, making maintenance a breeze. Its energy recovery capabilities help reduce heating and cooling costs, appealing to eco-conscious consumers.

The RNC155 stands out due to its robust capacity, catering to larger living spaces or commercial environments. This unit integrates advanced airflow management technology, allowing users to balance air distribution effectively throughout the building. The unit's energy-efficient operation is complemented by integrated controls that can be programmed for optimal performance based on occupancy and air quality levels.

The RNC10 offers a budget-friendly option while maintaining effective ventilation. It is compact and lightweight, making it ideal for smaller rooms or apartments. Despite its size, it features a reliable heat recovery system that significantly lowers energy costs and enhances comfort.

Finally, the RNC200 is a powerhouse model designed for larger commercial spaces. It boasts an impressive airflow capacity, making it suitable for demanding environments. This unit includes sophisticated monitoring systems that provide real-time data on air quality and system performance, ensuring that the air remains fresh and healthy. Additionally, its customizable setup allows for integration with other HVAC systems, further enhancing its functionality.

In summary, Lifebreath models like RNC95, RNC5-TPD, RNC155, RNC10, and RNC200 exemplify cutting-edge ventilation technology. Their distinct features cater to various needs, from residential to commercial applications, ensuring that users enjoy optimal indoor air quality while minimizing energy expenditure.