TOA Electronics 600 installation instructions Lhp

Page 28

Step 5. Millivolt Appliances -

Honeywell Systems

a. Convert the gas valve as follows (see Figure 67): Remove the plastic protecting cap. Remove the gas type setting screw by turning it counter- clockwise. Obtain the replacement gas type setting screw from the kit and screw it into place (red for propane and blue for natural gas). Tighten the gas type setting screw by turning it clockwise. Replace the plastic protecting cap.

Honeywell Millivolt Gas Valve

Step 6. Electronic Appliances -

Honeywell Systems

See Figure 68 and the instructions provided with the kit. Remove the slotted cap screw, o- ring, pressure-regulating adjusting screw and spring. Retain all parts for possible later use. Install new components from the kit. Black cap and red spring for propane gas units. Silver cap and stainless steel spring for natural gas units. Before installing the cap, attach manometer to the manifold side pressure test fitting and adjust screw until pressure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.

Pilot

PilotAssembly

Orifice

Ignitor

Assembly

 

Retaining

Flare Nut

Clip

Note: If the ignitor is damaged, a replacement kit is available - order Catalog Number 87L54.

Adjusting Knob

Regulator Cap

Conversion screw

(blue natural gas; red LP/propane gas)

Figure 67

b. Attach manometer to the manifold side pressure test fitting and verify manifold pres- sure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column

CONTROL

OFF ON

IGNITE

Manifold

Pressure

Test Port

Slotted Cap

Inlet Pressure Test Port

I

IS

P

Spring

Adjusting

Screw

Figure 69

All Models

Step 7. Remove the orifice from the mani- fold and replace it with the one provided with the kit. See the following table for orifice sizes for natural and propane models. Figure 70 illustrates the orifice.

D, DT,

Orifice Size

DR Series

 

 

Natural

Propane

 

 

 

 

500

0.090 in.

#54

(2.49 kPa) for propane gas.

c. Convert the pilot orifice as follows (refer to Figures 64, 65 and 66 ):

Note - Use extra care not to engage the orifice strip with the 7/16" open end wrench (contact- ing the orifice strip could cause strip distortion rendering the pilot inoperative). Also avoid wrench contact to any of the other pilot parts.

Use a 7/16" open end wrench and turn the pilot hex fitting counter-clockwise 1/4 turn. (refer to Figure 64 ).

Note - The orifice strip tab may be randomly located on any side of the hex fitting.

d.Push the orifice strip tab all the way against the hex fitting to align the appropriate gas type orifice (refer to Figures 65 and 66). The type of gas for which the pilot is set, is, the gas type shown on the tab.

e.Retighten, clockwise, the pilot hex fitting until the pilot hood aligns with the thermo- couple and thermopile as indicated by the arrows shown in Figure 64.

Figure 68

See Figure 69 and replace the pilot orifice as follows: Remove the ignitor assembly retainer clip, and carefully remove the ignitor assem- bly. Exercise extreme care to prevent dam- age to or breakage of the ignitor assembly. Remove the screw securing the pilot assembly to its mounting bracket. Back off the flare nut at the end of the pilot gas line to free the pilot assembly from the gas line.

Remove the pilot orifice and replace it with the one provided with the conversion kit. Reinstall the pilot assembly by reversing the steps de- tailed here.

When reinstalling the ignitor assembly, use extreme care to prevent damage and break- age. Do not apply any leverage to the ignitor assembly while restoring the retainer clip to its original position.

600

#36

#52

 

 

 

800

#33

0.065 in.

Figure 70

Step 8. Reassemble all removed components by reversing the procedures outlined in the preceding steps. Use pipe joint compound or Teflon tape on all pipe fittings before installing (ensure propane resistant compounds are used in propane applications, do not use pipe joint compounds on flare fittings).

Step 9. Attach the conversion label provided in the conversion kit to the rating plate on the appliance.

Step 10. Turn on gas supply and test for gas leaks.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.

Printed in U.S.A. © 2001 by Lennox Hearth Products

 

LHP

P/N 700,005M REV. X 11/2004

 

1110 West Taft Avenue • Orange, CA 92865

 

 

 

 

Image 28
Contents Retain These Instructions For Future Reference DT-500CEN DR-600CEPDR-500CEP DT-800CEN DT-600CEN DR-800CEPTable of Contents Cote DE Lappareil Location Millivolt ModelsElectronic Models All ModelsTypical Locations Appliance and Vent ClearancesArea above it. See . Model No Shelf Height inches mmDetailed Installation Steps Typical Installation SequenceVent Termination Clearances Exterior Horizontal Vent Termination Clearance Requirements Fireplace Framing Specifications Framing DimensionsDR-800 DR-600mm 1019 1554Fireplace Framing Specifications Fireplace SpecificationsFor D-500, DT-500 and DR- 500 Models only Install the Vent System Combined TOP and Rear Vent UnitsVertical Straight Installation Vertical Offset Installation Vent / Appliance Collar ConnectionFraming Dimensions for Roof Pitch 12/1210¹⁄₂ 267 mm 305 mm 10¹⁄₂ 17 ³⁄₄ 267 mm 451 mmTable a Vertical Vent FIGURES/TABLESTable B MaximumTable E Minimum+H 1 Maximum + H 1 = 20 feet 6.2 m MaxTypical Horizontal Vent Installation Install firestop/spacer at ceilingHorizontal Outside Wall Termination System Plan the vent runInstall Firestop/Spacer at exterior wall Install the desired termination¹⁄₄ 32 mm as shown in Figure SV4.5HTRTable F Table GHorizontal Vent FIGURES/TABLES Elbow Connection AT ApplianceSF4.5HF Table JSF4.5BF +H 1+H +H+H 1+H 2 = 40 feet 12.4 m Max+H 1+H 2= 20 feet 6.2 m Max 610 914Route Flex Vent Install the Outer Flex PipeAttach Adapter to Appliance Collar, or Secure Vent Sections Field Wiring Wiring Optional Forced AIR Blower KITSIT and Honeywell Millivolt Wiring Electronic Wiring See orConnecting GAS Line Burner Adjustments Hood InstallationFinishing Requirements Wall DetailsCold Climate Insulation Installation Accessories .2 Installation Code GAS Conversion KitsPilot for SIT Millivolt Gas Valve Millivolt Appliances SIT SystemsSide Of The Hex Fitting LHP

600 specifications

TOA Electronics, a leading manufacturer in the audio and communication equipment industry, has built a reputation for delivering high-quality products designed for commercial and professional applications. One of their standout offerings is the TOA 600 series of amplifiers, which combines power, clarity, and reliability, catering to a diverse range of sound reinforcement needs.

The TOA 600 series amplifiers are engineered with a wide power range, accommodating various installations from small venues to large auditoriums. This versatility is complemented by advanced technologies that enhance audio performance. The amplifiers boast a compact design, making them easy to integrate into existing sound systems without occupying excessive space.

One of the key features of the TOA 600 series is its high efficiency. Utilizing Class D amplification technology, these amplifiers deliver clear and powerful audio while consuming less energy than traditional analog amplifiers. This not only reduces operational costs but also minimizes heat generation, enhancing the long-term reliability of the equipment.

Another notable characteristic of the TOA 600 series is its built-in digital signal processing (DSP) capabilities. This technology allows users to optimize sound quality in real-time by adjusting parameters such as equalization, compression, and limiting. Users can create tailored sound profiles that suit specific environments or applications, ensuring optimal audio clarity and consistency.

The TOA 600 series also includes extensive protection circuits that safeguard the amplifier against common faults like overcurrent, overload, and overheating. This ensures durability and serviceability, making it a preferred choice for professionals who require dependable audio solutions.

Additionally, the amplifiers support multiple input options, including balanced XLR inputs and unbalanced RCA connectors, allowing for seamless integration with a variety of audio sources such as microphones, mixers, and playback devices. The built-in network capability also facilitates remote control and monitoring, providing users with greater flexibility and convenience.

Overall, the TOA 600 series amplifiers are a testament to TOA Electronics' commitment to quality and innovation in the audio industry. With their advanced features, robust construction, and user-friendly interface, these amplifiers are ideal for anyone seeking reliable and high-performance audio solutions for commercial or professional applications. Whether in schools, venues, or corporate environments, the TOA 600 series amplifiers deliver unparalleled sound quality and reliability.