Hearth and Home Technologies BE-36-C manual Installing the Horizontal Termination Cap

Page 31

C. Installing Heat Shield and Horizontal Termination Cap (DVP Pipe ONLY)

WARNING

Fire Hazard

Impaired performance of appliance

Telescoping flue section of termination cap MUST be used when connecting pipe section to termination cap.

Maintain a 1-1/2 inch minimum overlap on telescoping flue section of termination cap.

Installing the Horizontal Termination Cap

Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base.

Flash and seal as appropriate for siding material at outside edges of cap.

When installing a horizontal termination cap, follow the cap location guidelines as prescribed by current ANSI Z223.1 and CAN/CGA-B149installation codes.

WARNING

Fire Risk

Exhaust Fumes Risk

Impaired Performance of Appliance

Overlap pipe slip sections at least 1-1/2 inches.

Use pilot holes for screws.

Screws must not exceed 1 inch long.

Pipe may separate if not properly joined.

Heat Shield Requirements for Horizontal Termination

For all horizontally vented appliances, a heat shield MUST be placed one inch above the top of the vent between the wall shield firestop and the base of the termination cap.

There are two sections of the heat shield. One section attaches to the wall shield firestop with two screws. The remaining section is attached to the cap in the same manner.

If the wall thickness does not allow the required 1-1/2 inch heat shield overlap, an extended heat shield must be used.

The extended heat shield will need to be cut to the thick- ness of the wall and be attached to the wall shield firestop. The small leg on the extended heat shield should rest on the top of the vent (pipe section) to properly space it from the pipe section (see Figure 8.12).

WARNING

Burn Risk

Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap.

Figure 8.12 Venting through the Wall

NOTE: Where required, an exterior wall flashing is available.

When penetrating a brick wall, a brick extension kit is available for framing the brick.

Hearth & Home Technologies • BE-36-C, BE-36-CIPI397-981 Rev. V 1/07

31

Image 31
Contents What to do if you smell gas BE-36-CIPIHomeowner Reference Information CongratulationsTable of Contents Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Tools and Supplies Needed Design and Installation ConsiderationsGetting Started Inspect Appliance and ComponentsSelecting Appliance Location Framing and ClearancesModels Clearances Constructing the Appliance ChaseClearances to Mantels or other Combustibles above Appliance Mantel ProjectionsVent Termination Minimum Clearances Termination LocationsSee .4 for specific clearances Minimum Clearances for Termination Alcove ApplicationsMeasuring Standards Vent Information and DiagramsVent Table Key Use of ElbowsUse of Flex Vent Top Vent Horizontal Termination One Elbow Vent DiagramsTwo Elbows Top Vent Horizontal Termination Three Elbows Baffle Instruction Top Vent Vertical Termination No Elbows V1 = 44 ft. Max .4 mMinimum H1 Maximum Top Vent Vertical Termination Two Elbows Three ElbowsPage Rear Vent Horizontal Termination- Three elbows Rear Vent Horizontal Termination- Two elbowsRear Vent Horizontal Termination Two elbows Rear Vent Horizontal Termination- One elbowRear Vent Horizontal Termination- Three elbows Non-Combustible Wall Penetration Vent Clearances and FramingPipe Clearances to Combustibles Wall Penetration Framing Combustible Wall Penetration10 IN. X 10 Installing the Ceiling FirestopInstalling Attic Shield Vertical Penetration FramingChoosing the Top or Rear Vent Appliance PreparationCut the metal retaining band and fold the sides out Rear VentFire Risk Prevent contact with sagging, loose insulation Securing and Leveling the ApplianceAssembling Pipe Sections Installing Vent PipeAssembly of Vent Sections DVP Pipe only Attaching Vent to the Firebox AssemblyAssembling DVP-12A Slip Sections Assembling Minimum Installations MI SectionsHorizontal Sections Disassembly of Vent SectionsDVP Pipe only Securing the Vent Sections Vertical SectionsContinue Adding Vent Components Assembly of Vent Sections SL Series Pipe onlyInstall Support Brackets Attach the First Vent Component to Starting CollarsHeat Shield Requirements for Horizontal Termination Installing the Horizontal Termination CapFire Risk. Explosion Risk Installing Roof Flashing and Vertical Termination Cap 20 Assembling the Storm Collar Around the Pipe Assembling and Installing Storm CollarPressure Natural Gas Propane Gas InformationFuel Conversions Gas Connection Gas PressuresHigh Altitude Installations Connecting to the Appliance Recommendation for WireElectrical Information Intellifire Ignition System Wiring Standing Pilot Ignition System WiringWall Switch Installation for Fan Optional Junction Box InstallationFacing Material FinishingSee for combustible/non-combustible definitions Remove Shipping Materials Appliance SetupClean the Appliance AccessoriesPositioning the Logs Log Set Assembly LOGS-BE-36-C Models BE-36-CShutter Settings Glass AssemblyRemoving Glass Assembly Replacing Glass AssemblyBefore Lighting Appliance Operating InstructionsLighting Appliance Turn on all electric power to the applianceStanding Pilot Ignition For Your Safety Read Before Lighting InstructionsInitial Break-in Procedure Frequently Asked QuestionsAfter Appliance is Lit Symptom Possible Causes Corrective Action TroubleshootingStanding Pilot Ignition System Symptom Possible Cause Corrective Action TroubleshootingSympton Possible Cause Corrective Action Intellifire Ignition SystemSure must not exceed 14 in. W.C Maintaining and Servicing Appliance Recommend addition of screen if one is not present Inspect Maintenance TasksReference Materials Appliance Dimension DiagramDVP45 45 Elbow Vent Components DiagramsDVP-TRAP 13-7/8 352 mm 241 mm 24-5/8 625 mm13-1/4 367 mmVertical Termination Cap High wind 98 mm10-1/2 Vertical Termination Cap 184 mm 12-1/2 318 mm 133 mmPipe Length/Inches SL Series Vent ComponentsLog Set Assembly Service PartsIPI System ÎC. Service Parts List BE-36-CAdditional service part numbers may appear on the following Standing PilotStanding Pilot Valve Assembly Service Parts BE-36-CBE-36-CIPI IPI Valve AssemblyHearth & Home Technologies Limited Lifetime WarrantyContact Information
Related manuals
Manual 37 pages 30.79 Kb

BE-36-C specifications

Hearth and Home Technologies, a leader in innovative heating solutions, offers two remarkable gas fireplaces: the BE-36-CIPI and BE-36-C. Both models are designed to deliver efficient heating, aesthetic charm, and user-friendly features, making them ideal for modern living spaces.

The BE-36-CIPI is a direct vent fireplace that provides the warmth of a traditional fire without the hassle of wood. One of its most notable features is its contemporary design, featuring clean lines and a wide viewing area. This model comes with an impressive heat output, ensuring that spaces remain comfortably warm during chilly seasons. The BE-36-CIPI incorporates innovative technologies like the IntelliFire™ ignition system, which promotes energy efficiency by providing reliable performance while minimizing fuel consumption.

Moreover, the fireplace's advanced burner system creates a stunning flame pattern and realistic look, enhancing the ambiance of any room. With customizable options, homeowners can choose different media types, such as ceramic logs or contemporary stones, allowing for personal expression in their décor.

On the other hand, the BE-36-C model offers similar features but with its unique twist. This model is characterized by its traditional aesthetic appeal, making it an excellent choice for those who prefer a classic look with modern convenience. The BE-36-C also utilizes the IntelliFire™ system, ensuring efficiency and ease of use. With a versatile design, this fireplace can fit into various style preferences, from rustic to modern.

Both models come equipped with optional heat management systems, allowing for effective temperature regulation. This feature is particularly useful for maintaining a comfortable environment without overheating the space. The fireplaces are also designed with safety in mind, adhering to strict safety standards and offering numerous safety features like a safety pilot and tempered glass doors.

In conclusion, Hearth and Home Technologies’ BE-36-CIPI and BE-36-C gas fireplaces present an ideal blend of aesthetics, efficiency, and advanced technology. Whether opting for the contemporary style of the BE-36-CIPI or the classic allure of the BE-36-C, homeowners are guaranteed to enjoy a superior heating experience that complements their home’s design while providing warmth and comfort.