ELECTRICAL CONNECTION
WARNING
Plug into a properly grounded three-prong receptacle.

A 3/4" IPS manual gas valve is shipped with each single Pasta System for field installation. Batteries have a factory installed manual gas valve for each Pasta System. The required gas pressure for proper operation of each Pasta System is 4" water column (WC) for natural gas and 10” water column (WC) for Propane gas at the burner manifold. Remove the allen head test plug on the gas valve and using a manometer to check pressure.

If the inlet gas pressure exceeds 7" WC for natural gas and 11" WC for Propane, an in-line pressure regulator is required. In-line pressure regulators are not supplied by Keating. They are to be provided and installed by others as directed by local codes. ∞NOTE: If more than one gas Pasta System is on the same supply line, you may require a larger line. Consult your local gas company to assure adequate volume and pressure. Refer to serial plate for proper gas requirements for your particular model.

The Keating Custom Pasta Gas System is equipped with a 9' neoprene covered, 3 wire electrical cord with a three-pronged grounded plug for protection against electrical shock. This plug must be placed into a

120V properly grounded three-pronged outlet (NEMA 5-15 or 5-20). For proper grounding procedures see local codes or, in the

absence of local codes, the current National Electrical Code ANSI/NFPA 70 or Canadian Electrical Code CAN 22.2 as applicable.

∞NOTE: The electrical wiring diagram for the Pasta System is attached to the inside of the Pasta System door and in Section VIII of this manual.

WARNING

DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG.

GAS LEAK TESTING

Prior to lighting your Pasta System:

1. Make sure all thermostats, switches and safety valves are in the “OFF” position.

2. Turn main supply gas cock (Item 18, page 17) to the “ON” position.

3. Have your plumber or gas company check for leaks with a soap solution or sniffer. (NEVER check with an open flame)

4. Have your plumber or gas company representative light the constant pilot. (Not necessary if your Pasta System has an optional spark ignitor.)

5

∞NOTE: It is estimated that half of all service calls made on Keating Pasta Gas Systems result from an inadequate gas supply. During installation, have a gas company representative make certain that the Pasta System is receiving adequate gas pressure and volume.

WARNING

PROPANE GAS MAY EVENTUALLY LOSE ITS ODOR AND PRECAUTIONS SHOULD BE TAKEN TO ASSURE THAT IT IS NOT PRESENT EVEN THOUGH YOU DO NOT DETECT AN ODOR. IF THERE IS ANY DOUBT, YOU SHOULD CALL YOUR LOCAL PROPANE GAS SUPPLIER FOR ASSISTANCE.

CHECK GAS SUPPLY

PRESSURE

Special attention should be given to the supply pressure and gas flow pressure at the supply connection to the Pasta System. The nominal gas should be 4" WC for natural gas and 10" WC for propane gas.

If the supply pressure is lower or higher than the rated (nominal) pressure, then the reason should be investigated and the gas supplier contacted.

If the supply is lower than 2 1/2" WC or higher than 6" WC for natural gas or lower then 9” WC or higher than 12" WC for propane gas, then the Pasta System should be shut down and a service company or supplier notified. No adjustments should be made and the Pasta System should not be operated.

1. Turn off main gas supply valve.

2. Remove pressure measuring stud screw located at the “out-flow” (closest to gas burner) of the gas valve and attach a manometer.

3. Remove cover screw from the gas value pressure adjustment valve.

4. Open main gas supply valve and start Pasta System according to instructions with the thermostat set at 190°F(87.8°C).

5. Once the Pasta System is in operation, adjust pressure valve to 4" WC for natural gas and 10” WC for propane gas.

6. Turn Pasta System off, close main gas supply valve, remove manometer and tighten cover screw into pressure measuring stud.

SPECIAL NOTICES

The Pasta System should be operated only in an area that has good air circulation.

The Pasta System must be installed under an electrically powered ventilating hood.

The operator should be properly trained to the functioning of the Pasta System.

This instruction manual should be supplied the the operator.

Image 8
Contents Custom Pasta Post this Label in a Prominent Location on Your Unit Table of Contents Introduction Clearances II Installation InstallationPositioning Damage During ShipmentSpecifications GAS ConnectionRestraining DevicesGAS Leak Testing Check GAS Supply PressureSpecial Notices Do not CUT or Remove the Grounding Prong from this PlugIII Operating CalibrationWater and Drain Connections FillingIndicating Lights CookingShutdown DrainingTimer Operation CleaningElectronic Timers Warranty Repairs IV MaintenanceElectronic Timer Operating Instructions Maintenance Preventive Maintenance ChartPreventive Limited CalibrationService Diagnosis Trouble shootingProblem Probable Cause Solution Figures in determining proper size Problem Solutions Follow SequentiallyReplacement of a and B Boards Ordering Parts VII Parts ListsCustom Pasta System Control Panel with Digital Timers Toggle Switch Pilot on GAS Pasta System Assembly Description Models PART#RADIANT, 2 Fins ALL Pasta System Wiring Diagram GAS Pasta System with BASKET-LIFT Wiring Diagram Warranty Serving Those Who Serve The Very Best

0107 specifications

Keating of Chicago 0107 is a remarkable piece of roofing technology that exemplifies the best in contemporary design and engineering. This groundbreaking product is part of a trend towards more sustainable and efficient building practices, making it an attractive option for modern construction projects.

One of the main features of Keating of Chicago 0107 is its robust construction, designed to withstand challenging weather conditions while maintaining integrity over time. The materials used in its production are carefully selected for their durability and performance, ensuring a long lifespan and minimal maintenance needs. This makes it particularly appealing for both residential and commercial applications, where reliability is paramount.

Another significant characteristic of Keating of Chicago 0107 is its advanced insulation properties. By incorporating cutting-edge insulation technology, this roofing system helps to regulate indoor temperatures, contributing to energy efficiency. This feature is especially beneficial in areas with extreme weather, as it reduces the need for additional heating or cooling, thus lowering energy costs.

The aesthetic appeal of Keating of Chicago 0107 is also worth noting. Available in a range of colors and finishes, this roofing solution allows architects and homeowners alike to achieve a tailored look for their buildings. The sleek design complements various architectural styles, from traditional to contemporary, enhancing the overall visual impact of a structure.

In terms of installation, Keating of Chicago 0107 is user-friendly, with a straightforward process that minimizes labor costs and time. This efficiency is crucial in today’s fast-paced construction environment. Moreover, the product is engineered for adaptability, making it suitable for a variety of roof types, including flat and sloped surfaces.

Technologically, Keating of Chicago 0107 incorporates innovations that address common roofing challenges. Features such as water resistance and UV protection ensure that the system remains effective under diverse environmental conditions, preventing issues like leaks or premature wear.

Additionally, sustainability is a focal point with Keating of Chicago 0107. The materials are often sourced from recycled content, and the product can be easily installed in a way that supports eco-friendly building practices. This commitment to sustainability aligns with the growing demand for greener solutions in the construction industry.

In summary, Keating of Chicago 0107 stands out due to its combination of durability, energy efficiency, aesthetic versatility, ease of installation, and commitment to sustainability. It represents a significant advancement in roofing technology, making it a compelling choice for anyone looking to invest in a high-quality roofing solution.