GDP-5H — LOAD APPLICATION/EARTH LEAKAGE BREAKER

Three Phase Load — 180 Hz

180 Hz, three phase, 230V, motor-in-head vibrators can be operated with this generator. When operating more than one concrete vibrator, the ON/OFF switch of each concrete vibrators shall be turned on one at a time.

If they are switched on simultaneously, the circuit breaker may trip or the engine may be overloaded.

The vibrators can be operated simultaneously if the total power consumption does not exceed the rated output of the generator (5.0 KVA).

How to Use

Always conduct the following in order that the earth leakage breaker will operate safely. Also, if the leakage breaker should for some reason actuate, first stop the generator and then repair or eliminate the source of the earth leakage before resetting the leakage breaker.When setting up the generator perform the following:

Ground the Generator

Ground the generator from its ground connector so that resistance to ground is 500 ohms or less.

 

If output (kVA) is not given on the

NOTE

vibrators nameplate, approximate output

may be determined by multiplying

 

 

voltage by amperage by

.

Ground the Tool

Ground the tool (load) in the same manner as the generator.

Earth Leakage Breaker (180 Hz)

The earth leakage detection breaker (Figure 3) is used for

NOTE

Test Operation

Simply because the generator is equipped with a earth leakage breaker does not mean that grounding of the load can be neglected, please be sure to properly ground load equipment.

180 Hz application (3-phase vibrators). Before operating the generator test this breaker to make sure that is functioning correctly.

For safety’s sake, the operation of the earth leakage breaker should be tested periodically according to the following procedure:

1.Start the engine and set it to high speed.

2.Turn the leakage breaker ON.

3.During normal operation, press the earth leakage indicator test button on the front of the generator and observe that indicator button pops out and the leakage breaker trips.

4.Push the indicator button back in when resetting.

Figure 3. Earth Leakage Breaker

Before operating generator press earth leakage test button.The earth leakage

NOTE breaker's earth leakage detection sensitivity is 30 mA, and the actuation time is 0.1 sec.

GDP-5H A.C. GENERATOR — PARTS & OPERATION MANUAL — REV. #2 (10/05/05) — PAGE 17

Image 17 Contents
Model GDP-5H Page Heres HOW to GET Help Table of Contents When ordering parts Please supply the following information Parts Ordering ProceduresRespiratory Hazards Burn HazardsRotating Parts Hazards Equipment DamageRead this manual GDP-5H Rules for Safe OperationGDP-5H Rules for Safe Operation Emergencies DeathOperation and Safety Decals Machine Safety DecalsEffects of Altitude and Heat GDP-5H Specifications Generator Specifications Engine Dimensions GDP-5H DimensionsGenerator Phase Vibrator ApplicationControl Box Excitation SystemExtension Cables Single Phase Load 60 HzGDP-5H Load Application How to Use Three Phase Load 180 HzGround the Generator Ground the ToolGDP-5H Controls and Indicators 240V Full Power Switch GDP-5H Controls and IndicatorsFuelTank Fuel tank capacity is 5 gallons 19 liters Generator Refueling GDP-5H Generator RefuelingOutdoor Installation GDP-5H InstallationIndoor Installation MountingConnecting the Ground GDP-5H InstallationExtension Cable General Inspection Prior to Operation Ground Power ToolsGDP-5H PRE-INSPECTION Before Starting GDP-5H PRE-INSPECTION EngineEngine Oil Check Fuel CheckChoke Lever 180 Hz Circuit Breakers OFF Position Starting the EngineGDP-5H Initial START-UP/GENERATOR Operation Hz Output Receptacles Connecting the LoadGenerator Storage Stopping the EngineEngine Maintenance Schedule GDP-5H Maintenance EngineEngine Oil Draining Spark Plug GapGDP-5H Wiring Diagram Generator S/N 5541049 and below GDP-5H -WIRING Diagram Generator S/N 5543731 and Above GDP-5H -TROUBLESHOOTING Engine GDP-5H -TROUBLESHOOTING Engine GDP-5H -TROUBLESHOOTING Generator Page GDP-5H Explanation of Code in Remarks Column How to read the marks and remarks used in this partsItems Found In the Remarks Column Items Found In the Items Number ColumnDescription To 3 UnitsGDP-5H Nameplate and Decals Part Name QTY Remarks GDP-5H Nameplate and DecalsGDP-5H Generator Assy SET Bolt Rotor GDP-5H Control BOX Assy Control BOX GDP-5H Muffler Assy GDP-5H Muffler Assy GDP-5H Pipe Frame Assy Pipe Frame Honda GX340K1EDN2 Engine AIR Cleaner Assy Part Name Honda GX340K1EDN2 Engine Camshaft Assy ROD, Push Honda GX340K1EDN2 Engine Carburetor Assy Gasket SET Honda GX340K1EDN2 Engine Control Assy ARM, Governor Honda GX340K1EDN2 Engine Crankcase Cover Assy GASKET, Case Cover Honda GX340K1EDN2 Engine Crankshaft Assy Part Name QTY. Remarks Honda GX340K1EDN2 Engine Cylinder Barrel Assy Switch ASSY., OIL Level Honda GX340K1EDN2 Engine Cylinder Head Assy Cylinder Head Honda GX340K1EDN2 Engine FAN Cover Assy COVER, FAN *NH1* Black Honda GX340K1EDN2 Engine Flywheel Assy FAN, Cooling Honda GX340K1EDN2 Engine Ignition Coil Assy Coil ASSY., Ignition Honda GX340K1EDN2 Engine Piston Assy Piston STD Honda GX340K1EDN2 Engine Recoil Starter Assy PULLEY, Recoil Starter Honda GX340K1EDN2 Engine Solenoid Assy SPRING, Choke Return Honda GX340K1EDN2 Engine Labels Assy Emblem Effective October 1, 2002 Terms and Conditions of Sale Parts Page Your Local Dealer is