LOAD APPLICATION

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment's name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

 

 

 

Table 5. Power Factor By Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type Of Load

 

 

 

 

 

Power Factor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-phase induction motors

 

 

0.4 - 0.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric heaters, incandescent

 

 

1.0

 

 

 

 

lamps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fluorescent lamps, mercury lamps

 

 

0.4 - 0.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic devices, communication

 

 

1.0

 

 

 

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current in

Load In Watts

 

 

 

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amperes

At 120

 

At 240

 

#10 Wire

 

#12 Wire

#14 Wire

 

#16 Wire

 

 

Volts

 

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

 

600

 

1000 ft.

 

600

ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

5

600

 

1200

 

500

ft.

 

300

ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5

900

 

1800

 

350

ft.

 

200

ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

1200

 

2400

 

250

ft.

 

150

ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

1800

 

3600

 

150

ft.

 

100

ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

2400

 

4800

 

125

ft.

 

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load output maybe determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

PAGE 24 — DCA25USIXF/DCA25USI2XF — OPERATION AND PARTS MANUAL — REV. #2 (07/26/11)

Image 24
Contents Model DCA25USIXF Model DCA25USI2XF Diesel engine exhaust and some Proposition 65 WarningTable of Contents Parts Ordering Procedures Ordering parts has never been easierSafety Information Safety MessagesGeneral Safety Generator Safety„ Always know the location of the nearest fire extinguisherEngine Safety Before servicing equipmentFuel Safety Towing Safety„ Never use fuel as a cleaning agent 3ECURE Portable Power Cables in Cable Tray with TIE wrapsElectrical Safety Device. All installations should be„ Never use gas piping as an electrical ground Battery Safety Environmental SafetySpecifications Generator SpecificationsDimensions DimensionsDecals Generator DecalsDecals Installation Typical Generator Grounding ApplicationOutdoor Installation Indoor InstallationMounting Generator GroundingGeneral Information Familiarization Two auxilliary circuit breakers, 250V @50 amps Components Major ComponentsGenerator Control Panel Generator Control PanelEngine Operating Panel Fuel Gauge Indicates amount of diesel fuel availableOutput Terminal Panel Output Terminal PanelTerminal legs Oand Ground are considered bonded grounds Output Terminal Familiarization120VAC Gfci Receptacles F.C.I. ReceptacleConnecting Loads Connecting Loads Over Current RelaySingle Phase Load Three Phase LoadLoad Application Voltage Selector Switch Gauge READING/TERMINAL Panel ConnectionsGenerator OutputVoltages Maximum AmpsVoltage selector switch Reading VoltageThree-Phase Position Output Terminal Panel ConnectionsUvwo Terminal Output Voltages 3Ø 240/139 Output Terminal Lug VoltagesVoltage Selector Switch 240/120V Single-Phase Position 3Ø 480/277 Output Terminal Lug VoltagesSetup Circuit BreakersLubrication Oil Fuel CheckRefueling Procedure ONLY! use #2 diesel fuel when refuelingCleaning the Radiator Air Cleaner Fan Belt TensionMm when depressed with the thumb as shown below Operation FreezingWeatherBattery Battery Cable InstallationWiring AlternatorStartup Before StartingEngines exhaust contains harmful emissions Direct exhaust away from nearby personnelIgnition Switch Start Position Oil Pressure Gauge Normal Shut-down Procedure Emergency Shut-down ProcedureShutdown Automatic Shut-down SystemMaintenance Cleaning the Fuel Strainer Feed Pump Strainer CleaningAir Removal Check Oil LevelTrailer Maintenance Brake AdjustmentBrakes Check the wheel and drum for free rotationTires/Wheels/Lug Nuts TireWear/InflationSuspension Lug Nut Torque Requirements Start all wheel lug nuts by handTrailer Wiring Diagram Trailer/Towing Vehicle Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramEngine Wiring Diagram Generator Wiring Diagram Generator Wiring DiagramTroubleshooting Engine does not startStarter does not run Stuck? Generator Troubleshooting Page Sample Parts List Explanation of Code in Remarks ColumnXxxxx only Not Used on Suggested Spare Parts Qty DescriptionGenerator Assy Generator AssyBalancing Weight KIT Field AssyRectifier Surge AbsorberDCA25USIXF Control BOX Assy Control BOX ASSY. Dcausixf onlyDecal Terminal Symbol Control BOXCircuit BREAKER, 3P 60A Machine ScrewDCA25USIXF Control BOX Assy CHANGE-OVER SWITCH, Ammeter Water Temperature GaugeSWITCH, Panel Light Toothed WasherDCA25USI2XF Control BOX Assy Control BOX ASSY. DCAUSI2XF onlySelector Switch Switch BracketSwitch Cover CURRENTTRANSFORMER, 100/5ADCA25USI2XF Control BOX Assy Wire HARNESS, Generator DCA25USIXF Engine and Radiator Assy Engine and Radiator ASSY. Dcausixf onlyAIR Cleaner ELEMENT, AIR CleanerINDICATOR, AIR Cleaner BRACKET, AIR CleanerDCA25USIXF Engine and Radiator Assy UNIT, Water Temperature Drain JointPlug RingDCA25USI2XF Engine and Radiator Assy Engine and Radiator ASSY. DCAUSI2XF onlyENGINE, Isuzu BV-4LE2 DCA25USI2XF Engine and Radiator Assy M1316100603 Output Terminal Assy Output Terminal AssyTerminal Panel Output Terminal BoltTIE Screw Output WindowBattery Assy Battery AssyBattery Battery SheetBattery Band Battery Bolt SETDCA25USIXF Muffler Assy Muffler ASSY. DCA-25USIXF onlyM1332000002 810000 ~8101465M1332000012 M1335000103DCA25USI2XF Muffler Assy Muffler ASSY. DCA-25USI2XF onlyMuffler GasketStay Exhaust PipeFuel Tank Assy Fuel Tank AssyFuel Tank Fuel Tank CAPFuel Sender Unit Tank SupportDCA25USIXF Eclosure Assy Enclosure ASSY. DCA25USIXF onlyBase Acoustic SheetEnvironmental Tank Front FrameDCA25USIXF Eclosure Assy Rear Cover DuctRear Door Window PlateDCA25USIXF Eclosure Assy Fuel Leak Detected Switch Bracket StaySupport LEG BracketDCA25USI2XF Eclosure Assy Enclosure ASSY. DCA25USI2XF onlyCOVER, from Frame Front LouverDCA25USI2XF Eclosure Assy M1443302203 34A M1493305104M1443400103 35A M1493305204DCA25USI2XF Eclosure Assy Manual Holder CLAMP, Manual HolderRubber Seals Assy Rubber Seals Assy0229200790 03145005600229200630 0228901220Nameplate and Decals Assy Name Plate AssyDecal MQ POWER, DCA25USI2 Plate MQ PowerStripe Stripe WhisperwattTerms and Conditions of Sale Parts FreightpolicyPage HERE’S HOW to GET Help

DCA25USI2XF, DCA25USIXF specifications

Multiquip is a renowned name in the construction and industrial equipment sector, known for delivering high-performance generators that cater to various power needs. Two standout models in their lineup are the DCA25USIXF and DCA25USI2XF, both designed for reliability, efficiency, and versatility.

The Multiquip DCA25USIXF is a compact, industrial-grade diesel generator that delivers a powerful 25 kVA, making it ideal for construction sites, outdoor events, and emergency backup applications. This model is powered by a robust Yanmar diesel engine, which ensures high fuel efficiency and low emissions, adhering to stringent environmental standards. The DCA25USIXF features an advanced digital control panel, providing users with an intuitive interface for monitoring performance, voltage output, and operational status. Its sound-attenuated enclosure significantly reduces noise levels, making it suitable for use in noise-sensitive areas.

On the other hand, the DCA25USI2XF model takes power generation a step further by offering dual voltage capabilities, allowing users to switch between 120V and 240V outputs. This flexibility makes it highly versatile, catering to a broader range of tools and equipment. Like the DCA25USIXF, the DCA25USI2XF is also equipped with Yanmar’s reliable diesel engine, which contributes to its durability and long service life. Both models come with a heavy-duty frame to withstand tough conditions, ensuring durability on job sites.

The technology implemented in these generators includes automatic voltage regulation (AVR), which stabilizes voltage output, protecting sensitive equipment from power surges. Additionally, the generators feature a low oil shutdown system, which prevents engine damage by automatically shutting down the generator when oil levels are low. This protective measure not only enhances the longevity of the generator but also contributes to safer operation.

In terms of portability, both models are equipped with rugged wheels and a lifting eye, facilitating easy transportation to various job sites. With their combination of power, efficiency, and advanced features, the Multiquip DCA25USIXF and DCA25USI2XF generators are excellent choices for professionals seeking reliable power solutions in demanding environments. Whether for construction, events, or standby power, these generators deliver exceptional performance tailored to meet diverse needs.