LOAD APPLICATION

SINGLE PHASE LOAD

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is infl uenced by the effi ciency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

THREE PHASE LOAD

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fl uorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA400SSI GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (11/03/08) — PAGE 25

Image 25
Contents This Manual Must Accompany the Equipment AT ALL Times Model DCA400SSIProposition 65 Warning Administrator Reporting Safety DefectsDCA400SSI Generator Table of ContentsOrdering parts has never been easier Parts Ordering ProceduresSafety Messages Safety InformationGenerator Safety General Safety Always know the location of the nearest Before servicing equipment Engine SafetyTowing Safety Fuel SafetyGrounding Safety Electrical SafetyPower Cord/Cable Safety  The electrical voltage required toEnvironmental Safety Battery SafetyDCA400SSI SpecificationsDimensions DimensionsTypical Generator Grounding Application InstallationIndoor Installation Outdoor InstallationMounting Generator GroundingGeneral Information Item no Major ComponentsPilot Lamp Indicates the system is running Generator Control PanelOwing from the U,V, and W Output Terminal Lugs to the load Engine Operating Panel Air Filter Alarm When the air fi lterPage Output Terminal Familiarization Output Terminal Panel FamiliarizationTerminal legs O and Ground are considered bonded grounds 240V Twist-Lock Auxiliary Receptacles VAC Gfci ReceptaclesOver Current Relay Connecting LoadsThree Phase Load Single Phase LoadLoad Application Generator Output Voltages Generator OutputsVoltage Change-Over Board Generator AmperageMaximum Amps Generator OUTPUTS/GAUGE ReadingUvwo Terminal Output Voltages Output Terminal Panel Connections3Ø-240V Uvwo Terminal Output Voltages 1Ø-240V Uvwo Terminal Output Voltages1Ø-480V Uvwo Terminal Output Voltages 3Ø-480V Uvwo Terminal Output Voltages1Ø-277V Uvwo Terminal Output Voltages Circuit Breakers INSPECTION/SETUPLubrication OIL Fuel CheckOnly use #2 diesel fuel when refueling Refueling ProcedureAIR Cleaner FAN Belt Tension Cleaning the RadiatorCoolant ANTIFREEZE/SUMMER COOLANT/ Water Operation in Freezing WeatherBattery Cable Installation BatteryWiring AlternatorPlace the engine speed switch in the LOW down position Generator START-UP Procedure ManualBefore Starting Starting ManualFrequency Meter Starting Auto Mode Generator START-UP Procedure Auto ModeBefore connecting this generator to any Place the engine speed switch in the High positionNormal Shutdown Procedure Generator SHUT-DOWN ProceduresEmergency Shutdown Procedure Never stop the engine suddenly except in an emergencyGeneral Inspection AIR Cleaner MaintenanceAir Cleaner with Dust Indicator Fuel Tank Inspection Fuel AdditionAIR Removal Check OIL Level Radiator CleaningReplacing Oil Filter Flushing OUT Radiator and Replacing CoolantCharger Not used for long periods of time, apply power toTrailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Brakes Brake AdjustmentHydraulic Surge Brakes ActuatorTire Wear/Inflation TIRES/WHEELS/LUG NutsSuspension Never use an pneumatic air gun to tighten wheel lug nuts Lug Nut Torque RequirementsTrailer/Towing Vehicle Wiring Diagram Trailer Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramController Wiring Diagram Controller Wiring DiagramTroubleshooting Generator Clean/repair radiator grill Troubleshooting Engine ControllerAdjust governor actuator Adjust governor controllerMethod of Operation Troubleshooting Diagnostic LampPage Explanation of Code in Remarks Column Sample Parts ListTo 3 units Suggested Spare PartsGenerator Assy 0601823282 06018424010018205020 0040005000Generator Assy 13A 0040006000 001010606013B 0041206000 C3154400003Engine Operating Panel Assy 0207006000 C33511006031823200010 0021008080Control BOX Assy 0601801170 C32130028020027106016 0601807514Control BOX Assy 0601815154 89446070600027104016 8121468300Control BOX Assy 8224117004 8221814804C3213400604 0017110035Engine and Radiator Assy 1132402330 C39232001941132402410 8980088400Engine and Radiator Assy 0602040582 0602040779C3373200004 44A 0207010000Output Terminal Assy C0277500004 C22317004030801830904 0039320000Battery Assy C9109100704 01657210520805007804 0805006504Muffler Assy 0019110025 C33301004020047010030 C3333001903Fuel Tank ASSY. S/N 3813334 and below 0845500104 C33630025030810105400 0264100525Fuel Tank ASSY. S/N 3813335 and Above C3366704804 0130406000 Joint 1/2 01302060000131506000 Enclosure #1 Assy Base Enclosure #2 Assy Rear Frame Enclosure #3 Assy Splasher Panel Enclosure #3 Assy 0845046904 Rubber Seals Assy 0229201400 Nameplate and Decals Assy Control BOX Group Nameplate and Decals Assy Battery Group Freight Policy Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help
Related manuals
Manual 4 pages 63.04 Kb

DCA400SSI specifications

The Multiquip DCA400SSI is a robust and versatile generator designed for various demanding applications, particularly in construction and industrial settings. This powerful unit is part of Multiquip’s premium line of portable generators, known for their reliability and efficiency.

At the heart of the DCA400SSI is a formidable 400 kW diesel engine that provides exceptional power output while maintaining optimal performance. The generator features a highly efficient cooling system that ensures the engine operates within safe temperature ranges, thus extending its lifespan. Additionally, the DCA400SSI integrates sound attenuation technology that minimizes noise levels, making it suitable for use in noise-sensitive environments such as residential areas or during night-time operations.

One of the standout features of the DCA400SSI is its advanced digital controller. This state-of-the-art technology offers enhanced monitoring and control capabilities, allowing users to easily adjust settings and monitor essential parameters such as voltage, frequency, and running hours. The digital controller includes protective features that safeguard the engine against potential damage, thereby enhancing reliability during operation.

The DCA400SSI also emphasizes user-friendliness. Its intuitive control panel and easy-to-read displays ensure that operators can quickly understand and manage the generator's functions. This is particularly important in emergency situations or during critical operations when time is of the essence. The generator is designed with mobility in mind, equipped with heavy-duty wheels and a sturdy frame, allowing for easy transportation across job sites.

In terms of fuel efficiency, the DCA400SSI stands out with an extended fuel tank that supports longer operation times between refueling. This characteristic is crucial for operations that require continuous power supply without interruptions. The unit’s fuel efficiency is complemented by its eco-friendly emissions level, adhering to stringent environmental regulations, which is vital for contractors seeking sustainable solutions.

Overall, the Multiquip DCA400SSI is engineered to deliver high performance, reliability, and user-friendly operation. Its combination of advanced technologies, operational efficiency, and robust construction makes it an ideal choice for any job that demands dependable power. Whether for construction, industrial applications, or emergency backup, the DCA400SSI continues to reinforce Multiquip's reputation for quality and innovation in the generator market.