Multiquip DCA-10SPX4 Outdoor Installation, Indoor Installation, Mounting, Generator Grounding

Page 17

Outdoor Installation

Install the generator in a area that is free of debris, bystanders, and overhead obstructions. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.

CAUTION - EXHAUST HAZARD

Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

Indoor Installation

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside.The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

Mounting

The generator must be mounted on a solid foundation (such as concrete) and set firmly on the foundation to isolate vibration of the generator when it is running. The generator must set at least 6 inches above the floor or grade level (in accordance to NFPA 110, Chapter 5-4.1). DO NOT remove the metal skids on the bottom of the generator. They are to resist damage to the bottom of the generator and to maintain alignment.

DCA-10SPX4 — INSTALLATION

Generator Grounding

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 250-64(b) and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper - 10 AWG (5.3 mm2) or larger.

b.Aluminum - 8 AWG (8.4 mm2) or larger.

2.When grounding the generator (Figure 2) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried aminimum of 8 ft. into the ground.

When connecting the generator

NOTEto any buildings electrical system ALWAYS consult with a licensed electrician.

DCA-10SPX4— OPERATION AND PARTS MANUAL — REV. #0 (02/17/09) — PAGE 17

Image 17
Contents Model DCA-10SPX4 Proposition 65WARNING Diesel engine exhaust and someDCA-10SPX4- Operation and Parts Manual REV. #0 02/17/09 Table of Contents Ordering parts has never been easier Parts Ordering ProceduresDCA-10SPX4 Specifications Dimension ft. mm DimensionsHazard Symbols DCA-10SPX4 Safety Message Alert SymbolsDCA-10SPX4 Safety Message Alert Symbols DCA-10SPX4 Rules for Safe Operation General SafetyInjury People Carbon monoxide gasDCA-10SPX4 Rules for Safe Operation Battery Safety Death Guidelines section in this manual Towing and Transporting SafetyDCA-10SPX4- Operation and Parts Manual REV. #0 02/17/09 Typical Generator Grounding Application DCA-10SPX4 InstallationIndoor Installation Outdoor InstallationWhen connecting the generator MountingGenerator Control Panel GeneratorOutput Terminal Panel Open Delta Excitation SystemMajor Components DCA-10SPX4 Major ComponentsDCA-10SPX4 Generator Control Panel Output Terminal Familiarization DCA-10SPX4 Output Terminal Panel FamiliarizationL5-30RTwist Lock 120VAC Receptacle Option DCA-10SPX4 Output Terminal Panel Familiarization120VAC Gfci Receptacle DCA-10SPX4 Output Terminal Panel Familiarization Connecting LoadsDCA-10SPX4 Load APPLICATION/MAXIMUM Amperage Single Phase LoadGenerator Amperage Rated Voltage Maximum AmpsCircuit Breakers DCA-10SPX4 SetupLubrication Oil Fuel CheckRefueling Refueling ProcedureAir Cleaner Fan Belt Tension Cleaning the RadiatorCoolant Antifreeze/Summer Coolant/Water Operation FreezingWeatherBattery Cable Installation BatteryWiring AlternatorEngines exhaust contains harmful emissions Before StartingDirect exhaust away from nearby personnel Close all engine enclosure doors FigureSet the Speed Control Switch to the RUN position Figure DCA-10SPX4 Generator START-UP ProcedureEmergency Shutdown Procedure Normal Shutdown ProcedureDCA-10SPX4 Maintenance Air Removal Cleaning the Fuel StrainerCheck Oil Level Replacing Oil FilterBrakes Brake AdjustmentCheck the wheel and drum for free rotation Hydraulic Surge BrakesTires/Wheels/Lug Nuts DCA-10SPX4 -TRAILER MaintenanceTireWear/Inflation SuspensionStart all wheel lug nuts by hand DCA-10SPX4 -TRAILER MaintenanceLug Nut Torque Requirements Generator Wiring Diagram DCA-10SPX4 Generatorwiring DiagramDCA-10SPX4 Enginewiring Diagram Engine Troubleshooting DCA-10SPX4 -TROUBLESHOOTING EngineDCA-10SPX4 -TROUBLESHOOTING Engine DCA-10SPX4 -TROUBLESHOOTING Generator Failure Diagnosis Lamp Code DCA-10SPX4 -TROUBLESHOOTING PRE-HEAT Lamp CodesDCA-10SPX4- Operation and Parts Manual REV. #0 02/17/09 DCA-10SPX4 Explanation of Code in Remarks Column Sample Parts ListTo 3 Units DCA-10SPX4 Suggested Spare PartsDCA -10SPX4 Generator Assy DCA 10SPX4 Generator Assy DCA 10SPX4 Control Panel Assy 0601800455 Frequency METER, 45~65 Hz 0601805745 B02240051030601800281 060184007350 DCA-10SPX4- Operation and Parts Manual REV. #0 02/17/09 0601830771 0601806640B0214002903 0017108020DCA 10SPX4 Output Receptacle Assy 0601812598 06018151090601811035 0601811033DCA 10SPX4 Engine and Radiator Assy 1638297011 B09242001741641432433 B030420040356 DCA-10SPX4- Operation and Parts Manual REV. #0 02/17/09 8702082004 08020811040016906015 0199900450DCA 10SPX4 Battery Assy B1345200114 01653080260805002904 0037808000DCA 10SPX4 Muffler Assy B0334000503 B03311007031526312371 0207008000DCA 10SPX4 Fueltank Assy 0810105800 B03640007030810105900 B0364300403DCA 10SPX4 Enclosure Assy D3414800104 B0414002202B0424001302 B049410090466 DCA-10SPX4- Operation and Parts Manual REV. #0 02/17/09 39A 0845045004 08450472040845047104 40A 0845045004DCA 10SPX4 Rubber Seals Assy 0229400695 02292006500221700900 0221700640DCA 10SPX4 Name Plate Assy 2635 0840614104B9504501204 0800650804Freightpolicy Terms and Conditions of Sale PartsDCA-10SPX4- Operation and Parts Manual REV. #0 02/17/09 Lewisville, TX Fax 972

DCA-10SPX4 specifications

The Multiquip DCA-10SPX4 is a versatile and robust portable generator designed for a variety of applications, making it an excellent choice for both homeowners and professionals alike. With its compact design and powerful output, the DCA-10SPX4 is ideal for construction sites, outdoor events, and emergency backup power.

One of the standout features of the DCA-10SPX4 is its 10,000 watts of peak power output, ensuring it can handle demanding electrical loads with ease. The generator is powered by a reliable 4-cylinder engine, delivering superior performance while maintaining fuel efficiency. This combination of power and efficiency makes it suitable for both short-term use and extended periods without frequent refueling.

The DCA-10SPX4 is equipped with advanced technologies that enhance its overall reliability. It features an automatic voltage regulator (AVR) which ensures stable voltage output, protecting sensitive equipment from surges and fluctuations. This is particularly important for users who need to power electronics, tools, and other devices that require consistent voltage levels.

Another notable characteristic of the DCA-10SPX4 is its user-friendly control panel, which provides easy access to all essential functions. With multiple outlets, including 120V and 240V options, it accommodates a range of plug types, making it versatile enough for various applications. Additionally, the generator has built-in circuit breakers to prevent overloads and ensures user safety during operation.

Durability is a key aspect of the DCA-10SPX4, as it is engineered with a heavy-duty frame that can withstand rugged conditions commonly encountered on job sites. The generator also features an integrated wheel kit, allowing for easy transportation and maneuverability, which is a significant advantage when moving power equipment from one location to another.

Maintenance is simplified with the DCA-10SPX4, as it includes easy-access service points. Routine checks and oil changes can be performed quickly, ensuring the generator remains operational and prolonging its lifespan.

Overall, the Multiquip DCA-10SPX4 shines in its class due to its powerful performance, advanced technology, and user-friendly features. Whether for emergency backup, construction, or recreational use, it stands out as a reliable and efficient generator that meets the needs of diverse users.