Miller Electric 300 P manual Power Required To Start Motor, How Much Power Can Generator Supply?

Page 57

11-8. Power Required To Start Motor

4

 

 

 

 

 

 

 

AC MOTOR

 

2

1

 

 

 

 

VOLTS

230

AMPS

2.5

 

 

3

 

CODE

M

Hz

60

 

 

 

HP

1/4

PHASE 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-Phase Induction Motor Starting Requirements

Motor Start

G

 

H

J

K

L

M

 

N

 

P

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVA/HP

6.3

 

7.1

8.0

9.0

10.0

11.2

 

12.5

 

14.0

 

 

 

 

 

 

 

 

 

 

 

kVA/HP x HP x 1000 = STARTING AMPERAGE

 

 

 

 

VOLTS

 

 

 

 

 

 

 

 

EXAMPLE: Calculate the starting amperage required for a 230 V, 1/4

 

HP motor with a motor start code of M.

 

 

 

 

 

 

Volts = 230

HP = 1/4 Using Table, Code M results in kVA/HP = 11.2

11.2 x 1/4 x 1000

= 12.2 A

Starting the motor requires 12.2 amperes.

230

 

 

 

 

 

 

 

 

 

 

 

1Motor Start Code

2Running Amperage

3Motor HP

4Motor Voltage

To find starting amperage:

Step 1: Find code and use table to find kVA/HP. If code is not listed, multiply running amperage by six to find starting amperage.

Step 2: Find Motor HP and Volts.

Step 3: Determine starting amper- age (see example).

Welding generator amperage out- put must be at least twice the motor’s running amperage.

S-0624

11-9. How Much Power Can Generator Supply?

1

2

1Limit Load To 90% Of Generator Output

Always start non-resistive (motor) loads in order from largest to small- est, and add resistive loads last.

2 5 Second Rule

If motor does not start within 5 seconds, turn off power to prevent motor damage. Motor requires more power than generator can supply.

Ref. ST-800 396-A / S-0625

OM-4433 Page 53

Image 57
Contents Processes OM-4433218 314KDescription File Engine DriveFrom Miller to You Table of Contents Warranty Arc Welding Hazards Symbol UsageEngine Hazards Compressed Air Hazards California Proposition 65 Warnings Principal Safety StandardsEMF Information Radiation can cause interference− Consignes DE Sécurité − Lire Avant Utilisation Signification des symbolesUN Choc Électrique peut tuer LES Fumées ET LES GAZ peuvent être dangereuxDES Particules Volantes peuvent blesser les yeux LE Soudage peut provoquer un in- cendie ou une explosionDES Pièces Chaudes peuvent provoquer des brûlures graves LE Bruit peut affecter l’ouïe’AIR Comprimé peut provoquer des blessures LA Chaleur DU Moteur peut pro- voquer un incendie’EMPLOI Excessif peut LE Surchauffement peut endom- mager le moteur électriquePour les moteurs à essence LE Soudage À L’ARC risque de provoquer des interférencesPour les moteurs diesel Boulevard, Rexdale, Ontario, Canada M9W 1R3 téléphone− Definitions − 50 h StdStd Manufacturer’s Rating Label Symbols And Definitions − Specifications Weld, Power, And Engine SpecificationsDimensions, Weights, And Operating Angles MIG Mode Stick ModeTIG Mode Volt-Ampere CurvesExceeding duty cycle can damage unit and void warranty Curve shows typical fuel use under weld or power loadsFuel Consumption Duty Cycle And Overheating150 125 100 AC Generator Power CurveInstalling Welding Generator − InstallationSee -2for lifting eye rating See -2for mounting information GroundingMounting Welding Generator Tools Needed 1/2 Installing Exhaust PipeStop engine and let cool Point exhaust pipe in desired diConnecting The Battery Activating The Dry Charge Battery If ApplicableDo not overfill battery cells Close door after connecting batteryEngine Prestart Checks Coolant Recovery TankFuel Do not use gasoline. Gasoline will damage engine OilStick and TIG Welding Connecting To Weld Output TerminalsMIG and Fcaw Welding Stop engine150 ft 200 ft 250 ft Selecting Weld Cable Sizes350 ft 400 ft 45 m 60 m 70 m 90 m 105 m 120 m Stop engine beforeSocket Information Connecting To Remote 14 Receptacle RC14Front Panel Controls See Section − Operating Welding GeneratorDescription Of Front Panel Controls See Section Process/Contactor Switch Settings Process/Contactor SwitchLift-Arc Start Method Touch Lift-ArcStart ProcedureDo not Strike Like a Match Lift-Arc t TIGRemote Voltage/Amperage Control Generator Power Receptacles − Operating Auxiliary EquipmentAt least once a month, run engine at Routine Maintenance − Maintenance & TroubleshootingMaintenance Label By the warranty Servicing Air CleanerTo clean air filter Do not clean housing with air hoseInspecting And Cleaning Optional Spark Arrestor Muffler Stop engine and let cool. Reinstall cleanout plugServicing Engine Cooling System Maximum Adjusting Engine Speed On Standard ModelsDo not set engine speed higher Stop engine. Close doorWeld/Power Speed Adjust- ment Engine Speed AdjustmentEngine Speed No Load Rpm max 62.6 Hz 1250 rpm 41.6 HzTo change oil and filter Servicing Fuel And Lubrication SystemsTo replace primary canister fuel filter To drain water from fuel systemOverload Protection Replace Damaged Brushes Checking Generator BrushesVoltmeter/Ammeter Help Displays Help 20 DisplayHelp 25 Display Welding TroubleshootingEngine Generator PowerCheck for obstructed throttle solenoid Material Thickness Reference Chart Circuit Diagram For Welding Generator − Electrical Diagrams219 228−D − RUN-IN Procedure WetstackingWelding Generator Procedure at less than Run-In Procedure Using Load BankStop engine Do not touch hot exhaust From flammables Do not PerformBank/grid Run-In Procedure Using Resistance GridFrom flammables Do not perform run-inHas this symbol − Generator Power GuidelinesSelecting Equipment Grounding Generator To Truck Or Trailer FrameHow Much Power Does Equipment Require? Grounding When Supplying Building SystemsEarth ground if supplying Use ground device as stated Electrical codesApproximate Power Requirements For Farm/Home Equipment Approximate Power Requirements For Industrial MotorsIndustrial Motors Rating Starting Watts Running Watts Farm/Home Equipment Rating Starting Watts Running WattsContractor Rating Starting Watts Running Watts Approximate Power Requirements For Contractor EquipmentHow Much Power Can Generator Supply? Power Required To Start MotorSingle-Phase Induction Motor Starting Requirements KVA/HP x HP x 1000 = Starting AmperageTypical Connections To Supply Standby Power Current Load Watts Amperes Selecting Extension Cord Use Shortest Cord Possible− Parts List 109108 -2 107 101 102 103 100 104 106 105 81 Fig 7372 71 67 66 65 PC3 Dia Part Description Quantity Mkgs Batt Panel, Front w/Components -1Item Panel, Front w/ComponentsFUEL/HM Control Panel Generator Rectifier Assembly Wiring Harnesses Service Your distributor also givesSupport Miller Electric Mfg. Co To locate a Distributor or Service Agency visitFor assistance in filing or settling claims, contact Your distributor and/or equipment manufacturer’s