1.6.2Fuel Pipe Size
Ensure that the natural gas pipe size and length meet the specifications in Figure
Contact the local LP provider for LP installation information.
Maximum Pipe Length, m (ft.) | Pipe Size, in. NPT | |
|
|
|
9.2 | (30) | 3/4 |
|
|
|
30.0 | (100) | 1 |
|
|
|
68.6 | (225) | 1 1/4 |
|
|
|
Figure 1-13 12 kW Models, Fuel Pipe Size, Natural Gas
Minimum Gas Pipe Size Recommendation, in. NPT
Pipe Length, | Natural Gas | LP Vapor | |||
m (ft.) | (242,000 Btu/hr.) | (280,000 Btu/hr.) | |||
|
|
|
|
| |
8 | (25) |
| 1 | 3/4 | |
|
|
|
|
|
|
15 | (50) |
| 1 |
| 1 |
|
|
|
|
|
|
30 | (100) | 1 | 1/4 |
| 1 |
|
|
|
|
|
|
46 | (150) | 1 | 1/4 | 1 | 1/4 |
|
|
|
|
|
|
61 | (200) | 1 | 1/4 | 1 | 1/4 |
Figure 1-14 17/18 kW Models, Fuel Pipe Size, Natural Gas
1.7 Fuel Conversion
The
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger.
(3)Remove the battery cables, negative
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
1.7.1Fuel Conversion
For LP vapor fuel, an orifice is used in the fuel line. The unit is typically shipped set up for natural gas, with the loose orifice tied near the fuel line. To convert to LP vapor, install the orifice and disconnect the spark advance leads as described below. See Figure