9.Connect and turn on the new fuel supply.
10.Check that the generator set master switch is in the OFF position.
11.Reconnect the generator set engine starting battery leads, negative
12.Reconnect power to the battery charger.
13.Start the generator set by moving the generator set master switch to the RUN position.
14.Check for leaks using a gas leak detector.
15.Move the generator set master switch to the OFF/ RESET position to shut down the generator set.
To convert from LP vapor to natural gas, remove the fuel orifice and connect the DSAI leads together.
1.8Electrical Connections
WARNING
Hazardous voltage.
Backfeed to the utility system can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install a transfer switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
NOTICE
Canadian installations only. For standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
Have an authorized distributor/dealer or a licensed electrician make the following electrical connections. Verify that the electrical installation complies with the National Electrical Code (NEC) and all applicable local codes. Ground the generator set from the GRD terminal inside the controller compartment according to applicable codes.
1.8.1AC Connections
The generator set is equipped with a
Refer to the transfer switch specifications and Figure
The electrical installation must comply with the National Electrical Code (NEC) and all applicable local codes.
Connection Procedure
See Figure
1.Connect the leads from the transfer switch emergency source lugs to the L1 and L2 connections on the generator set terminal block.
2.Connect the neutral (L0) and ground (GRD) leads from the ATS and the main panel to the corresponding connection points on the terminal block. See Section 1.8.3, Grounding.
3.The terminal block kit includes 120VAC receptacles for the battery charger and optional carburetor heater. Connect utility power to the terminal block as shown. Connect to a circuit that is supplied by the generator set if utility power is lost.