IPSO T30, T45 installation manual Electrical Requirements for Gas and Steam Models

Page 19

Tumblers – T30 and T45

Electrical Requirements for Gas and Steam Models

Refer to Table 4 and Table 5.

NOTE: Minimum wire sizes are obtained from Canadian Electrical Code for 75°C Conductors and are intended for use as a guideline only.

Electrical connections should be made only by a qualified electrical contractor in accordance with all applicable local and national requirements.

For T30 Gas and Steam Models (For Total Machine):

NOTE: Electrical specifications below are subject to change without notice. Always refer to product serial plate for most current specifications of product being installed.

NOTE: Use copper conductors only.

NOTE: 3 Phase Only – Each tumbler must be connected to its own individual branch circuit breaker, not fuses, to avoid the possibility of “single phasing” and causing premature failure of the motor(s).

 

 

 

Recommended

 

Recommended

 

Terminal Block

 

 

Minimum

Serial Plate Voltage

Current

Fuse or

Breaker

Connections

Conductor Size

 

Required

(Amps)

Breaker Rating

Poles

(AWG [mm2])

 

 

 

(Amps)

 

 

 

 

 

 

 

 

120V/60 Hz/1ph

L1, Neutral,

16.0

20

1

12 (3.31)

and ground

 

 

 

 

 

 

 

 

 

208-240V/60Hz/1ph

L1, L2, Neutral,

8.0

10

2

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

100V/60Hz/1ph

L1, Neutral,

22.0

30

1

10 (5.26)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200-220V/60Hz/1ph

L1, Neutral,

11.6

15

1

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

100V/50Hz/1ph

L1, Neutral,

24.2

35

1

8 (8.37)

and ground

 

 

 

 

 

 

 

 

 

200V/50Hz/1ph

L1, Neutral,

15.0

20

1

12 (3.31)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230-240V/50Hz/1ph

L1, Neutral,

15.0

20

1

12 (3.31)

and ground

 

 

 

 

 

 

 

 

 

200-208V/60Hz/3ph

L1, L2, L3,

6.4

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

240V/60Hz/3ph

L1, L2, L3,

6.4

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200V/50Hz/3ph

L1, L2, L3,

5.8

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

230-240V/50Hz/3ph

L1, L2, L3,

7.0

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

380V/50 or 60Hz/3ph

L1, L2, L3,

3.0

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400-415V/50Hz/3ph

L1, L2, L3,

3.2

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

460-480V/60Hz/3ph

L1, L2, L3,

3.3

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

* 3 Phase machines should not have fuses, breakers only.

 

 

 

 

 

 

Table 4

 

 

 

4-08-43

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

18

Image 19
Contents On-Premise Laundry Planning Handbook Contents Model Identification IntroductionConversion Table Multiply To Obtain Tumblers T30 and T45Inches mm Steam Coil Rating at 100 psig Boiler Horsepower Btu/hrPounds kg Cylinder SizeModels T30 Cabinet DimensionsModels Rear Exhaust Exhaust Outlet LocationsModels Gas Connection Gas Connection LocationsElectrical Connection Locations Lower Steam Connection LocationsModels Inlet Outlet T30 UpperPre-Installation Inspection InstallationW056R1 TMB2110N Venting Exhaust RequirementsLayout Make-Up AirDuct Equivalent Length of Rigid Diameter Straight Duct Individual VentingManifold Venting T438I Mm Duct Duct T30 T45TWO Manifold Assemblies Duct T30 T45 Station Mm DuctElectrical Requirements for Gas and Steam Models Connections Amps Or Breaker Rating Poles Conductor Size Terminal Block Recommended FuseCurrent MinimumAmps Poles Conductor Size Required Electrical Requirements for Electric ModelsTerminal Block Recommended Current Breaker Minimum Connections